Specifications

117
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — INPUTS (cont)
*The display text changes depending on the remote switch configuration (
Configuration
UNIT
RM.CF
). If
RM.CF
is set to 0 (No Remote
Switch), then the display text will be “On” or “Off. If
RM.CF
is set to 1 (Occupied/Unoccupied Switch), then the display text will be “Occupied” or
“Unoccupied.” If
RM.CF
is set to 2 (Start/Stop), then the display text will be “Stop” or “Start.” If
RM.CF
is set to 3 (Override Switch), then the display
text will be “No Override” or “Override.
MODE — OUTPUTS
MODE — CONFIGURATION
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS
4-20
4-20 MILLIAMP INPUTS
IAQ.M
IAQ Milliamps ma IAQ_MA
OAQ.M
OAQ Milliamps ma OAQ_MA
SP.R.M
SP Reset milliamps ma SPRST_MA
DML.M
4-20 ma Demand Signal ma DMDLMTMA forcible
EDR.M
EDT Reset Milliamps ma EDTRESMA
ORH.M
OARH Milliamps ma OARH_MA
RRH.M
RARH Milliamps ma RARH_MA
BP.M
BP Milliamps ma BP_MA
BP.M.T
Bldg. Pressure Trim (ma) –2.0 - 2.0 BPMATRIM config
SP.M
SP Milliamps ma SP_MA
SP.M.T
Static Press. Trim (ma) –2.0 - 2.0 SPMATRIM config
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS
FANS
FANS
S.FAN
Supply Fan Relay ON/OFF SFAN_RLY
S.VFD
Supply Fan VFD Speed 0-100 % SFAN_VFD
P.E .A
Power Exhaust Relay A ON/OFF PE_A
P.E .B
Power Exhaust Relay B ON/OFF PE_B
P.E .C
Power Exhaust Relay C ON/OFF PE_C
CD.F.A
Condenser Fan Circuit A ON/OFF CONDFANA
CD.F.B
Condenser Fan Circuit B ON/OFF CONDFANB
COOL
COOLING
A1
Compressor A1 Relay ON/OFF CMPA1
A2
Compressor A2 Relay ON/OFF CMPA2
MLV
Min. Load Valve (HGBP) ON/OFF MLV
B1
Compressor B1 Relay ON/OFF CMPB1
B2
Compressor B2 Relay ON/OFF CMPB2
HEAT
HEATING
HT.1
Heat Relay 1 ON/OFF HS1
HT.2
Heat Relay 2 ON/OFF HS2
HT.3
Relay 3 W1 Gas Valve 2 ON/OFF HS3
HT.4
Relay 4 W2 Gas Valve 2 ON/OFF HS4
HT.5
Relay 5 W1 Gas Valve 3 ON/OFF HS5
HT.6
Relay 6 W2 Gas Valve 3 ON/OFF HS6
H.I.R
Heat Interlock Relay ON/OFF HIR forcible
ECON
ECONOMIZER
ECN.P
Economizer Act.Curr.Pos. 0-100 % ECONOPOS
ECN.C
Economizer Act.Cmd.Pos. 0-100 % ECONOCMD forcible
E.PWR
Economizer Power Relay ON/OFF ECON_PWR forcible
GEN.O
GENERAL OUTPUTS
ALRM
Remote Alarm Relay ON/OFF ALRM forcible
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.
UNIT
UNIT CONFIGURATION
C.TYP
Machine Control Type 1 - 6 (multi-text strings) CTRLTYPE 4 29
CV.FN
Fan Mode (0=Auto, 1=Cont) 0 - 1 (multi-text strings) FAN_MODE 1 29
RM.CF
Remote Switch Config 0 - 3 (multi-text strings) RMTINCFG 0 29
CEM
CEM Module Installed Yes/No CEM_BRD No 29
TCS.C
Temp.Cmp.Strt.Cool Factr 0 - 60 min TCSTCOOL 0 29
TCS.H
Temp.Cmp.Strt.Heat Factr 0 - 60 min TCSTHEAT 0 29
SFS.S
Fan Fail Shuts Down Unit Yes/No SFS_SHUT No 29
SFS.M
Fan Stat Monitoring Type 0 - 2 (multi-text strings) SFS_MON 0 29
VAV.S
VAV Unocc.Fan Retry Time 0 - 720 min SAMPMINS 50 29
SIZE
Unit Size (20-60) 20 - 60 UNITSIZE20 29
DP.XR
Disch.Press. Transducers Yes/No DP_TRANS No 30
MAT.S
MAT Calc Config 0 - 1 (multi-text strings) MAT_SEL 1 30
MAT.R
Reset MAT Table Entries? Yes/No MATRESET No 30
ALTI
Altitude……..in feet: 0 - 60000 ALTITUDE 0 30
SENS
INPUT SENSOR CONFIG 30
SENS
SPT.S
Space Temp Sensor Enable/Disable SPTSENS Disable 30
SENS
SP.O.S
Space Temp Offset Sensor Enable/Disable SPTOSENS Disable 30
SENS
SP.O.R
Space Temp Offset Range 1 - 10 SPTO_RNG 5 30
SENS
RRH.S
Return Air RH Sensor Enable/Disable RARHSENS Disable 30
SENS
FLT.S
Filter Stat.Sw.Enabled ? Enable/Disable FLTS_ENA Disable 30
SENS
SP.RS
Stat. Pres. Reset Sensor Enable/Disable SPRSTSEN Disable 30