Specifications

120
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
MODE — TIME CLOCK
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.
ALLM
ALERT LIMIT CONFIG.
SP.L.O
SPT lo alert limit/occ –10-245 dF SPLO 60 60
SP.H.O
SPT hi alert limit/occ –10-245 dF SPHO 85 60
SP.L.U
SPT lo alert limit/unocc –10-245 dF SPLU 45 60
SP.H.U
SPT hi alert limit/unocc –10-245 dF SPHU 100 60
SA.L.O
EDT lo alert limit/occ –40-245 dF SALO 40 61
SA.H.O
EDT hi alert limit/occ –40-245 dF SAHO 100 61
SA.L.U
EDT lo alert limit/unocc –40-245 dF SALU 40 61
SA.H.U
EDT hi alert limit/unocc –40-245 dF SAHU 100 61
RA.L.O
RAT lo alert limit/occ –40-245 dF RALO 60 61
RA.H.O
RAT hi alert limit/occ –40-245 dF RAHO 90 61
RA.L.U
RAT lo alert limit/unocc –40-245 dF RALU 40 61
RA.H.U
RAT hi alert limit/unocc –40-245 dF RAHU 100 61
R.RH.L
RARH low alert limit 0-100 % RRHL 0 61
R.RH.H
RARH high alert limit 0-100 % RRHH 100 61
SP.L
SP low alert limit 0-5 "H2O SPL 0 61
SP.H
SP high alert limit 0-5 "H2O SPH 2 61
BP.L
BP lo alert limit –0.25-0.25 "H2O BPL -0.25 61
BP.H
BP high alert limit –0.25-0.25 "H2O BPH 0.25 61
IAQ.H
IAQ high alert limit 0-5000 IAQH 1200 61
TRIM
SENSOR TRIM CONFIG.
SAT.T
Air Temp Lvg SF Trim –10 - 10 ^F SAT_TRIM 0 61
RAT.T
RAT Trim –10 - 10 ^F RAT_TRIM 0 61
OAT.T
OAT Trim –10 - 10 ^F OAT_TRIM 0 62
SPT.T
SPT Trim –10 - 10 ^F SPT_TRIM 0 62
CTA.T
Cir A Sat.Cond.Temp Trim –30 - 30 ^F SCTATRIM 0 62
CTB.T
Cir B Sat.Cond.Temp Trim –30 - 30 ^F SCTBTRIM 0 62
SP.A.T
Suct.Press.Circ.A Trim –50 - 50 PSIG SPA_TRIM 0 62
SP.B.T
Suct.Press.Circ.B Trim –50 - 50 PSIG SPB_TRIM 0 62
DP.A.T
Dis.Press.Circ.A Trim –50 - 50 PSIG DPA_TRIM 0 62
DP.B.T
Dis.Press.Circ.B Trim –50 - 50 PSIG DPB_TRIM 0 62
SW.LG
SWITCH LOGIC: NO / NC
FTS.L
Filter Status Inpt-Clean Open/Close FLTSLOGC Open 62
IGC.L
IGC Feedback - Off Open/Close GASFANLG Open 62
RMI.L
RemSw Off-Unoc-Strt-NoOv Open/Close RMTINLOG Open 62
ECS.L
Economizer Switch - No Open/Close ECOSWLOG Open 62
SFS.L
Fan Status Sw. - Off Open/Close SFSLOGIC Open 62
DL1.L
Dmd.Lmt.Sw.1 - Off Open/Close DMD_SW1L Open 62
DL2.L
Dmd.Lmt.Sw.2 - Off Open/Close DMD_SW2L Open 62
IAQ.L
IAQ Disc.Input - Low Open/Close IAQINLOG Open 62
FSD.L
Fire Shutdown - Off Open/Close FSDLOGIC Open 62
PRS.L
Pressurization Sw. - Off Open/Close PRESLOGC Open 62
EVC.L
Evacuation Sw. - Off Open/Close EVACLOGC Open 62
PRG.L
Smoke Purge Sw. - Off Open/Close PURGLOGC Open 62
DISP
DISPLAY CONFIGURATION
TEST
Test Display LEDs ON/OFF TEST Off 62
METR
Metric Display ON/OFF DISPUNIT Off 62
LANG
Language Selection 0-1(multi-text strings) LANGUAGE 0 62
PAS.E
Password Enable ENABLE/DISABLE PASS_EBL Enable 62
PASS
Service Password 0000-9999 PASSWORD 1111 62
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.
TIME
TIME OF DAY
HH.MM
Hour and Minute 00:00 TIME 64
DATE
MONTH,DATE,DAY AND YEAR
MNTH
Month of Year multi-text strings MOY 64
DOM
Day of Month 0-31 DOM 64
DAY
Day of Week multi-text strings DOWDISP 64
YEAR
Year e.g. 2003 YOCDISP 64
SCH.L
LOCAL TIME SCHEDULE
PER.1
PERIOD 1
PER.1
DAYS
DAY FLAGS FOR PERIOD 1 Period 1 only 64
PER.1
DAYS
MON
Monday in Period YES/NO PER1MON Yes 64
PER.1
DAYS
TUE
Tuesday in Period YES/NO PER1TUE Yes 64
PER.1
DAYS
WED
Wednesday in Period YES/NO PER1WED Yes 64
PER.1
DAYS
THU
Thursday in Period YES/NO PER1THU Yes 64
PER.1
DAYS
FRI
Friday in Period YES/NO PER1FRI Yes 64
PER.1
DAYS
SAT
Saturday in Period YES/NO PER1SAT Yes 64
PER.1
DAYS
SUN
Sunday in Period YES/NO PER1SUN Yes 64
PER.1
DAYS
HOL
Holiday in Period YES/NO PER1HOL Yes 65
PER.1
OCC
Occupied from 00:00 PER1_OCC 00:00 65
PER.1
UNC
Occupied to 00:00 PER1_UNC 24:00 65
Repeated for periods 2-8………..
HOL.L
LOCAL HOLIDAY SCHEDULES
HD.01
HOLIDAY SCHEDULE 01
HD.01
MON
Holiday Start Month 0-12 HOL_MON1 65
HD.01
DAY
Start Day 0-31 HOL_DAY1 65
HD.01
LEN
Duration (Days) 0-99 HOL_LEN1 65