Specifications

121
APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — TIME CLOCK (cont)
MODE — OPERATING MODES
MODE — ALARMS
APPENDIX B — CCN TABLES
All A series units with ComtfortLink™ controls have a port
for interface with the Carrier Comfort Network (CCN). On
TB3 there is a J11 jack which can be used for temporary con-
nection to the CCN network or to computers equipped with
CCN software like the Service Tool. Also on TB3 there are
screw connections that can be used for more permanent CCN
connections.
In the following tables the structure of the tables which are
used with the Service Tool as well as the names and data that
are included in each table are shown. As a reference the equiv-
alent Scrolling Marquee tables and names are included. There
are several CCN variables that are not displayed through the
Scrolling Marquee and are used for more extensive diagnostics
and system evaluations.
STATUS DISPLAY TABLES
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.
Repeated for holidays 2-30……..
DAY.S
DAYLIGHT SAVINGS TIME
DS.ST
DAYLIGHT SAVINGS START
DS.ST
ST.MN
Month 1 - 12 STARTM 4 65
DS.ST
ST.WK
Week 1 - 5 STARTW 1 65
DS.ST
ST.DY
Day 1 - 7 STARTD 7 65
DS.ST
MIN.A
Minutes to Add 0 - 90 MINADD 60 65
DS.SP
DAYLIGHTS SAVINGS STOP
DS.SP
SP.MN
Month 1 - 12 STOPM 10 65
DS.SP
SP.WK
Week 1 - 5 STOPW 5 65
DS.SP
SP.DY
Day 1 - 7 STOPD 7 65
DS.SP
MIN.S
Minutes to Subtract 0 - 90 MINSUB 60 65
ITEM EXPANSION RANGE UNITS CCN POINT
SYS.M
ascii string spelling out the system mode string
HVAC
ascii string spelling out the hvac modes string
CTRL
ascii string spelling out the “control type” string
MODE
MODES CONTROLLING UNIT
OCC
Currently Occupied ON/OFF MODEOCCP
T.OVR
TimedOverrideinEffect ON/OFF MODETOVR
DCV
DCV Resetting Min Pos ON/OFF MODEADCV
SA.R
Supply Air Reset ON/OFF MODESARS
DMD.L
Demand Limit in Effect ON/OFF MODEDMLT
T.C.ST
Temp.Compensated Start ON/OFF MODETCST
IAQ.P
IAQ Pre-Occ Purge Active ON/OFF MODEIQPG
LINK
Linkage Active - CCN ON/OFF MODELINK
LOCK
Mech.Cooling Locked Out ON/OFF MODELOCK
ITEM EXPANSION RANGE UNITS CCN POINT WRITE STATUS
CURR
CURRENTLY ACTIVE ALARMS
this is a dynamic list of active alarms strings
R.CUR
Reset All Current Alarms YES/NO ALRESET ram config
HIST
ALARM HISTORY
this is a record of the last 20 alarms strings
R.HIS
Reset Alarm History YES/NO ALHISCLR ram config
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
COOLING
HVAC Mode…………..: ascii text strings
Control Mode………..: ascii text strings
Current Running Capacity % CAPTOTAL
Cooling Control Point dF COOLCPNT
Evaporator Discharge Tmp dF EDT
Mixed Air Temperature dF MAT
COOL_A
Compressor A1 Relay CMPA1
Compressor A1 Feedback CSB_A1
Compressor A1 Timeguard CMPA1_TG
Compressor A2 Relay CMPA2
Compressor A2 Feedback CSB_A2
Compressor A2 Timeguard CMPA2_TG
Minimum Load Valve MLV
Cir A Discharge Pressure PSIG DP_A
Cir A Suction Pressure PSIG SP_A
Cir A Sat.Condensing Tmp dF SCTA
Cir A Sat.Suction Temp. dF SSTA