Specifications

122
APPENDIX B — CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
COOL_B
Compressor B1 Relay CMPB1
Compressor B1 Feedback CSB_B1
Compressor B1 Timeguard CMPB1_TG
Compressor B2 Relay CMPB2
Compressor B2 Feedback CSB_B2
Compressor B2 Timeguard CMPB2_TG
Cir B Discharge Pressure PSIG DP_B
Cir B Suction Pressure PSIG SP_B
Cir B Sat.Condensing Tmp dF SCTB
Cir B Sat.Suction Temp. dF SSTB
ECONDIAG
Economizer Active ? Yes/No ECACTIVE
Conditions which prevent
economizer being active:
Econ Act. Unavailable? Yes/No ECONUNAV
Remote Econ. Disabled ? Yes/No ECONDISA
DBC - OAT lockout? Yes/No DBC_STAT
DEW - OA Dewpt. lockout? Yes/No DEW_STAT
DDBC- OAT > RAT lockout? Yes/No DDBCSTAT
OAEC- OA Enth Lockout? Yes/No OAECSTAT
DEC - Diff.Enth.Lockout? Yes/No DEC_STAT
EDT Sensor Bad ? Yes/No EDT_STAT
OAT Sensor Bad ? Yes/No OAT_STAT
Economizer forced ? Yes/No ECONFORC
Supply Fan not on 30s ? Yes/No SFONSTAT
Cool Mode not in effect? Yes/No COOL_OFF
OAQ lockout in effect ? Yes/No OAQLOCKD
Econ recovery hold off? Yes/No ECONHELD
ECONOMZR
Economizer Act.Curr.Pos. % ECONOPOS
Economizer Act.Cmd.Pos. % ECONOCMD forcible
Economizer Active ? ECACTIVE
Economizer Control Point dF ECONCPNT
Outside Air Temperature dF OAT forcible
Evaporator Discharge Tmp dF EDT
Controlling Return Temp dF RETURN_T forcible
GENERAL
Occupied ? Yes/No OCCUPIED forcible
Static Pressure "H2O SP
Building Pressure "H2O BP
Outside Air Rel.Humidity % OARH forcible
Return Air Rel.Humidity % RARH forcible
Space Temperature Offset ^FSPTO forcible
Supply Air Setpnt. Reset ^F SASPRSET forcible
Static Pressure Reset SPRESET forcible
IAQ - PPM Return CO2 IAQ forcible
OAQ - PPM Return CO2 OAQ forcible
IAQ Min.Pos.Override % IAQMINOV forcible
GENERIC
20 points dependent upon
the configuration of the
“generics” table in the
Service-Config section on page 128.