Specifications

124
APPENDIX B — CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
SET POINT TABLE
CONFIG TABLES
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
UINPUTS
Filter Status Input Dirty/Clean FLTS forcible
Fan request from IGC On/Off IGCFAN
Fire Shutdown Switch Alarm/Normal FSD forcible
Thermostat G Input On/Off G forcible
Thermostat W2 Input On/Off W2 forcible
Thermostat W1 Input On/Off W1 forcible
Thermostat Y2 Input On/Off Y2 forcible
Thermostat Y1 Input On/Off Y1 forcible
Economizer Control Input On/Off ECOSW forcible
Remote Economizer Enable Yes/No ECONENBL forcible
Econo Position Override Yes/No ECOORIDE forcible
Remote Input State On/Off RMTIN forcible
Supply Fan Status Switch On/Off SFS forcible
Demand Limit Switch 1 On/Off DMD_SW1 forcible
Demand Limit Switch 2 On/Off DMD_SW2 forcible
Pressurization Input Alarm/Normal PRES forcible
Evacuation Input Alarm/Normal EVAC forcible
Smoke Purge Input Alarm/Normal PURG forcible
IAQ - Discrete Input High/Low IAQIN forcible
UOUTPUTS
FANS
Supply Fan Relay On/Off SFAN_RLY
Supply Fan VFD Speed 0-100 % SFAN_VFD
Supply Fan Request Yes/No SFANFORC forcible
Power Exhaust Relay A On/Off PE_A
Power Exhaust Relay B On/Off PE_B
Power Exhaust Relay C On/Off PE_C
Condenser Fan A On/Off CONDFANA
Condenser Fan B On/Off CONDFANB
COOLING
Compressor A1 Relay On/Off CMPA1
Compressor A2 Relay On/Off CMPA2
Minimum Load Valve On/Off MLV
Compressor B1 Relay On/Off CMPB1
Compressor B2 Relay On/Off CMPB2
HEATING
Heat Relay 1 On/Off HS1
Heat Relay 2 On/Off HS2
Relay 3 W1 Gas Valve 2 On/Off HS3
Relay 4 W2 Gas Valve 2 On/Off HS4
Relay 5 W1 Gas Valve 3 On/Off HS5
Relay 6 W2 Gas Valve 3 On/Off HS6
Heat Interlock Relay On/Off HIR forcible
ECONOMIZER
Economizer Act.Curr.Pos. 0-100 % ECONOPOS
Economizer Act.Cmd.Pos. 0-100 % ECONOCMD forcible
Economizer Power Relay On/Off ECON_PWR forcible
GENERAL OUTPUTS
Remote Alarm Relay On/Off ALRM
TABLE NAME RANGE UNITS POINT NAME DEFAULT
SET_PNT
Occupied Heat Setpoint 55-80 dF OHSP 68
Occupied Cool Setpoint 55-80 dF OCSP 75
Unoccupied Heat Setpoint 40-80 dF UHSP 55
Unoccupied Cool Setpoint 75-95 dF UCSP 90
Heat-Cool Setpoint Gap 2-10 deltaF HCSP_GAP 5
VAV Occ. Cool On Delta 0-25 deltaF VAVOCON 3.5
VAV Occ. Cool Off Delta 1-25 deltaF VAVOCOFF 2
Supply Air Setpoint 45-75 dF SASP 55
Supply Air Setpoint Hi 45-75 dF SASP_HI 55
Supply Air Setpoint Lo 45-75 dF SASP_LO 60
Heating Supply Air Setpt 90-145 dF SASPHEAT 85
Tempering Purge SASP –20-80 dF TEMPPURG 50
Tempering in Cool SASP 5-75 dF TEMPCOOL 5
Tempering in Vent Occ SASP –20-80 dF TEMPVOCC 65
Tempering Vent Unocc. SASP –20-80 dF TEMPVUNC 50
TABLE NAME RANGE UNITS POINT NAME DEFAULT
ALARMDEF
Alarm Routing Control 00000000-11111111 ALRM_CNT 11000000
Equipment Priority 0 - 7 EQP_TYPE 5
Comm Failure Retry Time 1 - 240 min RETRY_TM 10
Re-Alarm Time 1 - 255 min RE-ALARM 30
Alarm System Name up to 8 alphanum ALRM_NAM A-SERIES