Specifications

125
APPENDIX B — CCN TABLES (cont)
CONFIG TABLES (cont)
TABLE NAME RANGE UNITS POINT NAME DEFAULT
BRODEFS
CCN Time/Date Broadcast Off/On CCNBC Off
CCN OAT Broadcast Off/On OATBC Off
CCN OARH Broadcast Off/On OARHBC Off
CCN OAQ Broadcast Off/On OAQBC Off
Global Schedule Broadcst Off/On GSBC Off
Daylight Savings Start:
Month 1 - 12 STARTM 4
Week 1 - 5 STARTW 1
Day 1 - 7 STARTD 7
Minutes to Add 0 - 90 MINADD 60
Daylight Savings Stop:
Month 1 - 12 STOPM 10
Week 1 - 5 STOPW 5
Day 1 - 7 STOPD 7
Minutes to Subtract 0 - 90 MINSUB 60
Ctlr-ID
Device Name: A-Series
Description: A Series Rooftop
Location:
Software Part Number: CESR131343-XX-XX
Model Number:
Serial Number:
Reference Number:
HOLIDAY Broadcast Supervisory
HOLDY01S Holiday Start Month 1-12 HOL-MON 0
to Start Day 1-31 HOL-DAY 0
HOLDY30S Duration (days) 1-99 HOL-LEN 0
OCCDEFCS Occupancy Supervisory
Timed Override Hours 0 OVR-EXT
Period 1 DOW (MTWTFSSH) 00000000 DOW1
Occupied From 0:00 OCCTOD1
Occupied To 0:00 UNOCTOD1
Period 2 DOW (MTWTFSSH) 00000000 DOW2
Occupied From 0:00 OCCTOD2
Occupied To 0:00 UNOCTOD2
Period 3 DOW (MTWTFSSH) 00000000 DOW3
Occupied From 0:00 OCCTOD3
Occupied To 0:00 UNOCTOD3
Period 4 DOW (MTWTFSSH) 00000000 DOW4
Occupied From 0:00 OCCTOD4
Occupied To 0:00 UNOCTOD4
Period 5 DOW (MTWTFSSH) 00000000 DOW5
Occupied From 0:00 OCCTOD5
Occupied To 0:00 UNOCTOD5
Period 6 DOW (MTWTFSSH) 00000000 DOW6
Occupied From 0:00 OCCTOD6
Occupied To 0:00 UNOCTOD6
Period 7 DOW (MTWTFSSH) 00000000 DOW7
Occupied From 0:00 OCCTOD7
Occupied To 0:00 UNOCTOD7
Period 8 DOW (MTWTFSSH) 00000000 DOW8
Occupied From 0:00 OCCTOD8
Occupied To 0:00 UNOCTOD8
SCHEDOVR
Schedule Number 0-99 SCHEDNUM 0
Accept Global Holidays? Yes/No HOLIDAYT No
Override Time Limit 0-4 hours OTL 1
Timed Override Hours 0-4 hours OVR_EXT0
Accepting an Override:
SPT Override Enabled ? Yes/No SPT_OVER Yes
T58 Override Enabled ? Yes/No T58_OVER Yes
Allowed to Broadcast a
Global Sched. Override ? Yes/No GLBLOVER No
SET_PNT
Occupied Heat Setpoint 55-80 dF OHSP 68
Occupied Cool Setpoint 55-80 dF OCSP 75
Unoccupied Heat Setpoint 40-80 dF UHSP 55
Unoccupied Cool Setpoint 75-95 dF UCSP 90
Heat-Cool Setpoint Gap 2-10 deltaF HCSP_GAP 5
VAV Occ. Cool On Delta 0-25 deltaF VAVOCON 3.5
VAV Occ. Cool Off Delta 1-25 deltaF VAVOCOFF 2
Supply Air Setpoint 45-75 dF SASP 55
Supply Air Setpoint Hi 45-75 dF SASP_HI 55
Supply Air Setpoint Lo 45-75 dF SASP_LO 60
Heating Supply Air Setpt 90-145 dF SASPHEAT 85
Tempering Purge SASP –20-80 dF TEMPPURG 50
Tempering in Cool SASP 5-75 dF TEMPCOOL 5
Tempering in Vent Occ SASP –20-80 dF TEMPVOCC 65
Tempering Vent Unocc. SASP –20-80 dF TEMPVUNC 50