APPENDIX B — CCN TABLES (cont)
SERVICE-CONFIG TABLES
TABLE NAME RANGE UNITS POINT NAME DEFAULT
ALLM
SPT lo alert limit/occ –10-245 dF SPLO 60
SPT hi alert limit/occ –10-245 dF SPHO 85
SPT lo alert limit/unocc –10-245 dF SPLU 45
SPT hi alert limit/unocc –10-245 dF SPHU 100
EDT lo alert limit/occ –40-245 dF SALO 40
EDT hi alert limit/occ –40-245 dF SAHO 100
EDT lo alert limit/unocc –40-245 dF SALU 40
EDT hi alert limit/unocc –40-245 dF SAHU 100
RAT lo alert limit/occ –40-245 dF RALO 60
RAT hi alert limit/occ –40-245 dF RAHO 90
RAT lo alert limit/unocc –40-245 dF RALU 40
RAT hi alert limit/unocc –40-245 dF RAHU 100
RARH low alert limit 0-100 % RRHL 0
RARH high alert limit 0-100 % RRHH 100
SP low alert limit 0-5 "H2O SPL 0
SP high alert limit 0-5 "H2O SPH 2
BP lo alert limit –0.25-0.25 "H2O BPL -0.25
BP high alert limit –0.25-0.25 "H2O BPH 0.25
IAQ high alert limit 0-5000 IAQH 1200
BP__
Building Press. Config 0-2 BLDG_CFG 0
Power Exhaust Motors 0-2 PWRM 1
0=None,1=4 Mtr, 2=6 Mtr
Building Pressure Sensor Enable/Disable BPSENS Dsable
Bldg Press (+/-) Range 0-1 BP_RANGE 0.25
Building Pressure Setp. –0.25 -> 0.25 "H2O BPSP 0.05
Power Exhaust On Setp.1 0-100 % PES1 35
Power Exhaust On Setp.2 0-100 % PES2 75
Modulating PE Alg. Slct. 1-3 BPSELECT 1
BP PID Evaluation Time 0-10 min BPPERIOD 1
BP Threshold Adjustment 0.1-10 BPZ_GAIN 1
High BP Level 0-1 BPHPLVL 0.05
Low BP Level 0-1 BPLPLVL 0.04
COOL
Capacity Threshold Adjust –10 -> 10 Z_GAIN 1
Compressor Lockout Temp –20 -> 55 dF OATLCOMP 40
Fan-off Delay, Mech Cool 0-600 sec COOL_FOD 60
Minimum Load Valve? Yes/No MLV_SEL No
Motor Master Control ? Yes/No MOTRMAST No
Head Pressure Setpoint 80-150 dF HPSP 110
Enable Compressor A1 Enable/Disable CMPA1ENA Enable
Enable Compressor A2 Enable/Disable CMPA2ENA Enable
Enable Compressor B1 Enable/Disable CMPB1ENA Enable
Enable Compressor B2 Enable/Disable CMPB2ENA Enable
CSB A1 Feedback Alarm Enable/Disable CSB_A1EN Dsable
CSB A2 Feedback Alarm Enable/Disable CSB_A2EN Dsable
CSB B1 Feedback Alarm Enable/Disable CSB_B1EN Dsable
CSB B2 Feedback Alarm Enable/Disable CSB_B2EN Dsable
Rev. Rotation Verified ? Yes/No REVR_VER No
DISP
Metric Display Off/On DISPUNIT Off
Language Selection 0-1 LANGUAGE 0
Password Enable Enable/Disable PASS_EBL Enable
Service Password 0000-9999 PASSWORD 1111
Contrast Adjustment –255 - 255 CNTR_ADJ 0
Brightness Adjustment –255 - 255 BRTS_ADJ 0
DLVT
Dmd Level Lo Heat On –1 - 2 ^F DMDLHON 1.5
Dmd Level(+) Hi Heat On 0.5 - 2.0 ^F DMDHHON 0.5
Dmd Level(-) Lo Heat Off 0.5 - 2 ^FDMDLHOFF 1
Dmd Level Lo Cool On –1 - 2 ^F DMDLCON 1.5
Dmd Level(+) Hi Cool On 0.5 - 2 ^F DMDHCON 0.5
Dmd Level(-) Lo Cool Off 0.5 - 2 ^FDMDLCOFF 1
Cool Trend Demand Level 0.1 - 5 ^F CTRENDLV 0.1
Heat Trend Demand Level 0.1 - 5 ^F HTRENDLV 0.1
Cool Trend Time 30 - 600 sec CTRENDTM 120
Heat Trend Time 30 - 600 sec HTRENDTM 120
DMDL
Demand Limit Select 0 - 3 DMD_CTRL 0
Demand Limit at 20 ma 0 - 100 % DMT20MA 100
Loadshed Group Number 0 - 99 SHED_NUM 0
Loadshed Demand Delta 0 - 60 % SHED_DEL 0
Maximum Loadshed Time 0 - 120 min SHED_TIM 60
Demand Limit Sw.1 Setpt. 0 - 100 % DLSWSP1 80
Demand Limit Sw.2 Setpt. 0 - 100 % DLSWSP2 50