Specifications

135
Table B — VFD Configurations
VFD Operation The VFD keypad is shown in Fig. B.
The function of SOFT KEYS 1 and 2 change depending on
what is displayed on the screen. The function of SOFT KEY 1
matches the word in the lower left-hand box on the display
screen. The function of SOFT KEY 2 matches the word in the
lower right-hand box on the display screen. If the box is empty,
then the SOFT KEY does not have a function on that specific
screen. The UP and DOWN keys are used to navigate through
the menus. The OFF key is used to turn off the VFD. The
AUTO key is used to change control of the drive to automatic
control. The HAND key is used to change control of the drive
to local (hand held) control. The HELP button is used to access
the help screens.
PARAMETER GROUP PARAMETER TITLE PARAMETER INDEX CARRIER DEFAULT
Start-Up Data
LANGUAGE 9901 ENGLISH
APPLIC MACRO 9902 USER 1
MOTOR CTRL MODE 9904 SCALAR: FREQ
MOTOR NOM VOLT 9905 460v
MOTOR NOM CURR 9906 *TBD*
MOTOR NOM FREQ 9907 60 Hz
MOTOR NOM SPEED 9908 1750 rpm
Start/Stop/Dir
EXT1 COMMANDS 1001 DI-1
DIRECTION 1003 REVERSE
Analog Inputs
MINIMUM AI1 1301 20.0 %
MAXIMUM AI1 1302 100.0 %
Relay Outputs
RELAY OUTPUT 1 1401 STARTED
RELAY OUTPUT 2 1402 RUN
RELAY OUTPUT 3 1403 FAULT (-1)
System Controls
RUN ENABLE 1601 NOT SELECTED
START ENABLE 1 1608 DI-4
OVER RIDE
OVERRIDE SEL 1701 DI-3
OVERRIDE FREQ 1702 60 Hz
OVERRIDE SPEED 1703 1750 rpm
OVER PASS CODE 1704 ENTERED
OVERRIDE 1705 ON
STOP FUNCTION 2102 RAMP
Accel/Decel
ACCELER TIME 1 2202 30.0s
DECELER TIME 1 2203 30.0s
MOTOR SWITCHING FREQ 2606 8 kHz
Fig. B — VFD Keypad