Specifications
CL-2
-
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
CUT ALONG DOTTED LINE CUT ALONG DOTTED LINE
ITEM EXPANSION RANGE DEFAULT ENTRY
HEAT
HEATING CONFIGURATION
→
HT.CF
Heating Control Type 0 - 4 0
→
HT.SP
Heating Supply Air Setpt 80 - 120 dF 85
→
OC.EN
Occupied Heating Enabled Yes/No No
→
LAT.M
MBB Sensor Heat Relocate Yes/No No
→
G.FOD
Fan-Off Delay, Gas Heat 45-600 45
→
E.FOD
Fan-Off Delay, Elec Heat 10-600 30
→
SG.CF
STAGED GAS CONFIGS
→
SG.CF
→
HT.ST
Staged Gas Heat Type 0 - 4 0
→
SG.CF
→
CAP.M
Max Cap Change per Cycle 5 - 45 45
→
SG.CF
→
M.R.DB
S.Gas DB min.dF/PID Rate 0 - 5 0.5
→
SG.CF
→
S.G.DB
St.Gas Temp. Dead Band 0 - 5 ^F2
→
SG.CF
→
RISE
Heat Rise dF/sec Clamp 0.05 - 0.2 0.06
→
SG.CF
→
LAT.L
LAT Limit Config 0 - 20 ^F10
→
SG.CF
→
LIM.M
Limit Switch Monitoring? Yes/No No
→
SG.CF
→
SW.H.T
Limit Switch High Temp 110 - 180 dF 170
→
SG.CF
→
SW.L.T
Limit Switch Low Temp 100 - 170 dF 160
→
SG.CF
→
HT.P
Heat Control Prop. Gain 0 - 1.5 1
→
SG.CF
→
HT.D
Heat Control Derv. Gain 0 - 1.5 1
→
SG.CF
→
HT.TM
Heat PID Rate Config 60 - 300 sec 90
SP
SUPPLY STATIC PRESS.CFG.
→
SP.CF
Static Pressure Config 0 - 1 (multi-text strings) No
→
SP.FN
Static Pres.Fan Control? Yes Yes
→
SP.S
Static Pressure Sensor Enable/Disable Disable
→
SP.LO
Static Press. Low Range -10 - 0 0
→
SP.HI
Static Press. High Range 0 - 10 5
→
SP.SP
Static Pressure Setpoint 0 - 5 "H2O 1.5
→
SP.MN
VFD Minimum Speed 10 - 50 % 20
→
SP.MX
VFD Maximum Speed 50 - 100 % 100
→
SP.FS
VFD Fire Speed Override 0 - 100 100
→
S.PID
STAT.PRESS.PID CONFIGS
→
S.PID->SP.TM
Stat.Pres.PID Run Rate 1 - 200 sec 2
→
S.PID->SP.P
Static Press. Prop. Gain 0 - 100 20
→
S.PID->SP.I
Static Pressure Intg. Gain 0 - 50 2
→
S.PID->SP.D
Static Pressure Derv. Gain 0 - 50 0
→
S.PID->SP.SG
Static Press.System Gain 0 - 50 1
ECON
ECONOMIZER CONFIGURATION
→
EC.EN
Economizer Installed? Yes/No Yes
→
EC.MN
Economizer Min.Position 0 - 100 % 5
→
EC.MX
Economizer Max.Position 0 - 100 % 98
→
E.TRM
Economzr Trim For SumZ ? Yes/No Yes
→
E.SEL
Econ ChangeOver Select 0 - 3 (multi-text strings) 1
→
OA.E.C
OA Enthalpy ChgOvr Selct 1 - 5 (multi-text strings) 4
→
OA.EN
Outdr.Enth Compare Value 18 - 28 24
→
OAT.L
High OAT Lockout Temp –40 - 120 dF 60
→
O.DEW
OA Dewpoint Temp Limit 50 - 62 dF 55
→
ORH.S
Outside Air RH Sensor Enable/Disable Disable
→
E.TYP
Economizer Control Type 1-3 (multi-text strings) 1
→
EC.SW
Economizer Switch Config 0 - 2 (multi-text strings) 0
→
E.CFG
ECON.OPERATION CONFIGS
→
E.CFG->E.P.GN
Economizer Prop.Gain 0.7 - 3.0 1
→
E.CFG->E.RNG
Economizer Range Adjust 0.5 - 5.0 ^F2.5
→
E.CFG->E.SPD
Economizer Speed Adjust 0.1 - 10.0 0.75
→
E.CFG->E.DBD
Economizer Deadband 0.1 - 2.0 ^F0.5
→
UEFC
UNOCC.ECON.FREE COOLING
→
UEFC->FC.CF
Unoc Econ Free Cool Cfg 0-2 (multi-text strings) 0
→
UEFC->FC.TM
Unoc Econ Free Cool Time 0 - 720 min 120
→
UEFC->FC.L.O
Un.Ec.Free Cool OAT Lock 40 - 70 dF 50