Specifications
CL-3
ITEM EXPANSION RANGE DEFAULT ENTRY
BP
BUILDING PRESS. CONFIG
→
BP.CF
Building Press. Config 0-2 0
→
BP.MT
Power Exhaust Motors 1-2 1
→
BP.S
Building Pressure Sensor Enable/Dsable Dsable
→
BP.R
Bldg Press (+/-) Range 0 - 1.00 0.25
→
BP.SP
Building Pressure Setp. –0.25
→
0.25 "H2O 0.05
→
BP.P1
Power Exhaust On Setp.1 0 - 100 % 35
→
BP.P2
Power Exhaust On Setp.2 0 - 100 % 75
→
B.CFG
BP ALGORITHM CONFIGS
→
B.CFG
→
BP.SL
Modulating PE Alg. Slct. 1-3 1
→
B.CFG
→
BP.TM
BP PID Evaluation Time 0 - 10 min 1
→
B.CFG
→
BP.ZG
BP Threshold Adjustment 0.1 - 10.0 1
→
B.CFG
→
BP.HP
High BP Level 0 - 1.000 0.05
→
B.CFG
→
BP.LP
Low BP Level 0 - 1.000 0.04
D.LV.T
COOL/HEAT SETPT. OFFSETS
→
L.H.ON
Dmd Level Lo Heat On –1 - 2 ^F1.5
→
H.H.ON
Dmd Level(+) Hi Heat On 0.5 - 2.0 ^F0.5
→
L.H.OF
Dmd Level(-) Lo Heat Off 0.5 - 2 ^F1
→
L.C.ON
Dmd Level Lo Cool On –1 - 2 ^F1.5
→
H.C.ON
Dmd Level(+) Hi Cool On 0.5 - 2 ^F0.5
→
L.C.OF
Dmd Level(-) Lo Cool Off 0.5 - 2 ^F1
→
C.T.LV
Cool Trend Demand Level 0.1 - 5 ^F0.1
→
H.T.LV
Heat Trend Demand Level 0.1 - 5 ^F0.1
→
C.T.TM
Cool Trend Time 30 - 600 sec 120
→
H.T.TM
Heat Trend Time 30 - 600 sec 120
DMD.L
DEMAND LIMIT CONFIG.
→
DM.L.S
Demand Limit Select 0 - 3 (multi-text strings) 0
→
D.L.20
Demand Limit at 20 ma 0 - 100 % 100
→
SH.NM
Loadshed Group Number 0 - 99 0
→
SH.DL
Loadshed Demand Delta 0 - 60 % 0
→
SH.TM
Maximum Loadshed Time 0 - 120 min 60
→
D.L.S1
Demand Limit Sw.1 Setpt. 0 - 100 % 80
→
D.L.S2
Demand Limit Sw.2 Setpt. 0 - 100 % 50
IAQ
INDOOR AIR QUALITY CFG.
→
DCV. C
DCV ECONOMIZER SETPOINTS
→
DCV. C
→
EC.MN
Economizer Min.Position 0 - 100 % 5
→
DCV. C
→
IAQ.M
IAQ Demand Vent Min.Pos. 0 - 100 % 0
→
AQ.CF
AIR QUALITY CONFIGS
→
AQ.CF
→
IQ.A.C
IAQ Analog Sensor Config 0 - 4 (multi-text strings) 0
→
AQ.CF
→
IQ.A.F
IAQ4-20maFanConfig 0-2(multi-textstrings) 0
→
AQ.CF
→
IQ.I.C
IAQ Discrete Input Config 0 - 2 (multi-text strings) 0
→
AQ.CF
→
IQ.I.F
IAQ Disc.In. Fan Config 0 - 2 (multi-text strings) 0
→
AQ.CF
→
OQ.A.C
OAQ 4-20ma Sensor Config 0 - 2 (multi-text strings) 0
→
AQ.SP
AIR QUALITY SETPOINTS
→
AQ.SP
→
IQ.O.P
IAQ Econ Override Pos. 0 - 100 % 100
→
AQ.SP
→
DAQ.L
Diff.Air Quality LoLimit 0 - 1000 100
→
AQ.SP
→
DAQ.H
Diff.Air Quality HiLimit 100 - 2000 700
→
AQ.SP
→
D.F.OF
DAQ PPM Fan Off Setpoint 0 - 2000 200
→
AQ.SP
→
D.F.ON
DAQ PPM Fan On Setpoint 0 - 2000 400
→
AQ.SP
→
IAQ.R
Diff. AQ Responsiveness –5 - 5 0
→
AQ.SP
→
OAQ.L
OAQ Lockout Value 0 - 2000 0
→
AQ.SP
→
OAQ.U
User Determined OAQ 0 - 5000 400
→
AQ.S.R
AIR QUALITY SENSOR RANGE
→
AQ.S.R
→
IQ.R.L
IAQ Low Reference 0 - 5000 0
→
AQ.S.R
→
IQ.R.H
IAQ High Reference 0 - 5000 2000
→
AQ.S.R
→
OQ.R.L
OAQ Low Reference 0 - 5000 0
→
AQ.S.R
→
OQ.R.H
OAQ High Reference 0 - 5000 2000
→
IAQ.P
IAQ PRE-OCCUPIED PURGE
→
IAQ.P
→
IQ.PG
IAQ Purge Yes/No No
→
IAQ.P
→
IQ.P.T
IAQ Purge Duration 5-60 min 15
→
IAQ.P
→
IQ.P.L
IAQ Purge LoTemp Min Pos 0-100 % 10
→
IAQ.P
→
IQ.P.H
IAQ Purge HiTemp Min Pos 0-100 % 35
→
IAQ.P
→
IQ.L.O
IAQ Purge OAT Lockout 35-70 dF 50