Specifications

25
VFD Control — On VFD equipped supply fans, supply
duct static pressure control may be left under unit control or be
externally controlled. To control a VFD externally with a 4 to
20 mA signal, set SP.CF to 0, under the Configuration
SP
menu. This will disable the ComfortLink™ control from vary-
ing the VFD speed in response to duct pressure with its 4 to
20 mA output. The signal is connected directly to the VFD.
See Appendix C and the VFD literature supplied with the unit
for VFD configurations and field wiring connections to the VFD.
Supply Air Reset With the installation of the Control
Expansion Module (CEM), the ComfortLink control is capable
of accepting a 4 to 20 mA signal, to reset the supply-air temper-
atureuptoamaximumof20F.
Under Configuration
EDT.R set RS.CF to 3 (external 4
to 20 mA supply air reset control). The 4 to 20 mA input to the
control system (TB6-1 and 3), will be linearized and range
from 0º to 20 F. For example, 4 mA = 0º F reset, 12 mA = 10º F
reset and 20 mA = 20º F reset.
Demand Limit Control — The term Demand Limit
Control refers to the restriction of the machine’s mechanical
cooling capacity to control the amount of power that a machine
may use.
Demand Limiting using mechanical control is possible via
two means:
Two discrete inputs tied to demand limit set point percentages.
OR
A 4 to 20 mA input that can reduce or limit capacity linearly to
a set point percentage.
In either case, it will be necessary to install a Controls Ex-
pansion Module (CEM).
DEMAND LIMIT DISCRETE INPUTS First, set DM.L.S
in Configuration
DMD.L to1(2switches).
When Inputs
GEN.I
DL.S1 (Demand Switch no. 1) is
OFF, the control will not set any limit to the capacity, and
when ON, the control sets a capacity limit to the Configura-
tion
DMD.L
D.L.S1 set point.
Likewise, when Inputs
GEN.I
DL.S2 (Demand Switch
no. 2) is OFF, the control will not set any limit to the capacity,
and when ON, the control sets a capacity limit to the Configu-
ration
DMD.L
D.L.S2 set point.
If both switches are ON, Inputs
GEN.I
DL.S2 is used
as the limiter of capacity.
Under Configuration
SW.LG, set the logic state appropri-
ately for the action desired. Set the DL1.L and DL2.L configu-
rations. They can be set normally open or normally closed. For
example, if DL1.L is set to OPEN, the user will need to close
the switch to cause the control to limit capacity to the demand
limit 1 set point. Likewise, if DL1.L is set to CLSE (closed),
the user will need to open the switch to cause the control to
limit capacity to the demand limit 1 set point.
DEMAND LIMIT 4 TO 20 mA INPUT — Under Configu-
ration
DMD.L, set configuration DM.L.S to2(2=4to
20 mA control). Under the same menu, set D.L.20 to a value
from 0 to 100% to set the demand limit range. For example,
with D.L.20 set to 50, a 4 mA signal will result in no limit to
the capacity and 20 mA signal will result in a 50% reduction in
capacity.
Demand Controlled Ventilation Control — There
are multiple methods for externally controlling the economizer
damper.
IAQ DISCRETE INPUT CONFIGURATION — The IAQ dis-
crete input configuration requires a CEM module (optional) to
be installed and an interface to a switch input at TB5-6 and 7.
The state of the input on the display can be found at
Inputs
AIR.Q
IAQ.I.
Before configuring the switch functionality, first determine
how the switch will be read. A closed switch can indicate either
a low IAQ condition or a high IAQ condition. This is set at
Configuration
SW.LG and IAQ.L. The user can set what a
low reading would mean based on the type of switch being
used. Setting IAQ.L to OPEN means that when the switch is
open the input will read LOW. When the switch is closed, the
input will read HIGH. Setting IAQ.L to CLSE (closed) means
that when the switch is closed the input will read LOW, and
therefore, when the switch is open the switch will read HIGH.
There are two possible configurations for the IAQ discrete
input. Select item Configuration
IAQ
AQ.CF
IQ.I.C
and configure for either 1 (IAQ Discrete) or 2 (IAQ Discrete
Override).
IQ.I.C
=1(IAQ Discrete) — If the user sets IQ.I.C to 1 (IAQ
Discrete), and the switch logic (Configuration
SW.LG
IAQ.L) is set to OPEN, then an open switch reads low and a
closed switch reads high.
If the switch is open, the economizer will be commanded to
the IAQ Demand Vent Minimum Position.
These settings may be adjusted and are located at Configura-
tion
IAQ
DCV.C
IAQ.M.
If the switch is closed, the IAQ reading will be high and the
economizer will be commanded to the Economizer Minimum
Position.
These settings may be adjusted and are located at Configura-
tion
IAQ
DCV.C
EC.MN.
IQ.I.C
=2(IAQ Discrete Override) — If the user sets IQ.I.C
to 2 (IAQ Discrete Override), and Configuration
SW.LG
IAQ.L is set to OPEN, then an open switch reads low and a
closed switch reads high.
If the switch reads low, no action will be taken. If the switch
reads high, the economizer will immediately be commanded to
the IAQ Economizer Override Position. This can be set from 0
to 100% and can be found at Configuration
IAQ
AQ.SP
IQ.O.P.
FAN CONTROL FOR THE IAQ DISCRETE INPUT
Under Configuration
IAQ
AQ.CF, the IQ.I.F (IAQ Dis-
crete Input Fan Configuration) must also be set. There are
three configurations for IQ.I.F. Select the configuration which
will be used for fan operation. This configuration allows the
user to decide (if the supply fan is not already running),
whether the IAQ discrete switch will start the fan, and in which
state of occupancy the fan will start.
IAQ ANALOG INPUT CONFIGURATION — This input is
an analog input located on the main base board (MBB). There
are 4 different functions for this input. The location of this con-
figuration is at Configuration
IAQ
AQ.CF
IQ.A.C.
The functions possible for IQ.A.C are:
0 = no IAQ analog input
1 = IAQ analog input
2 = IAQ analog input used to override to a set position
3 = 4 to 20 mA 0 to 100% economizer minimum position
control
4 = 0 to 10 kohms 0 to 100% economizer minimum posi-
tion control
Options 2, 3, and 4 are dedicated for third party control.
IQ.I.F = 0 Minimum Position Override Switch input
will not start fan
IQ.I.F = 1 Minimum Position Override Switch input
will start fan in occupied mode only
IQ.I.F = 2 Minimum Position Override Switch input
will start fan in both occupied and unoccu-
pied modes