Specifications

45
Staged Gas Heat Staging
Different unit sizes will control
heat stages differently based on the amount of heating capacity
included. These staging patterns are selected based on the mod-
el number. The selection of a set of staging patterns is con-
trolled via the heat stage type configuration parameter (HT.ST).
As the heating capacity rises and falls based on demand, the
staged gas control logic will stage the heat relay patterns up and
down, respectively. The Heat Stage Type configuration selects
one of 4 staging patterns that the stage gas control will use. In
addition to the staging patterns, the capacity for each stage
is also determined by the staged gas heating PID control. There-
fore, choosing the heat relay outputs is a function of the capaci-
ty desired, the heat staging patterns based on the heat stage type
(HT.ST) and the capacity presented by each staging pattern. As
the staged gas control desired capacity rises, it is continually
checked against the capacity of the next staging pattern.
When the desired capacity is greater than or equal to the
capacity of the next staging pattern, the next heat stage is select-
ed (Run Status
VIEW
HT.ST = Run Status
VIEW
HT.ST + 1). Similarly, as the capacity of the control drops, the
desired capacity is continually checked against the next lower
stage. When the desired capacity is less than or equal to the next
lower staging pattern, the next lower heat stage pattern is select-
ed (Run Status
VIEW
HT.ST = Run Status
VIEW
HT.ST - 1). The first two staged gas heat outputs are located on
the MBB board and outputs 3, 4, 5, and 6 are located on
the SCB board. These outputs are used to yield from 5 to
11 stages as shown in Table 51. The heat stage selected (Run
Status
VIEW
HT.ST) is clamped between 0 and the
maximum number of stages possible (Run Status
VIEW
H.MAX) for the chosen set of staging patterns. See
Tables 52-55.
INTEGRATED GAS CONTROL BOARD LOGIC — All gas
heat units are equipped with one or more Integrated Gas
Control (IGC) boards. This board provides control for the igni-
tion system for the gas heat sections. On size 030-050 low heat
units there will be one IGC board. On size 030-050 high heat
units and 060 low heat units there are two IGC boards. On size
060 high heat units there are three IGC boards. When a call for
gas heat is initiated, power is sent to W on the IGC boards. For
standard 2-stage heat, all boards are wired in parallel. For
staged gas heat, each board is controlled separately. When
energized, an LED on the IGC board will be turned on. See
Table 56 for LED explanations. Each board will ensure that the
rollout switch and limit switch are closed. The induced-draft
motor is then energized. When the speed of the motor is proven
with the Hall Effect Sensor on the motor, the ignition activation
period begins. The burners ignite within 5 seconds. If the burn-
ers do not light, there is a 22-second delay before another
5-second attempt is made. If the burners still do not light, this
sequence is repeated for 15 minutes. After 15 minutes have
elapsed and the burners have not ignited then heating is locked
out. The control will reset when the request for W (heat) is tem-
porarily removed. When ignition occurs, the IGC board will
continue to monitor the condition of the rollout switch, limit
switches, Hall Effect Sensor, and the flame sensor. Forty-five
seconds after ignition has occurred, the IGC will request that
the indoor fan be turned on. The IGC fan output (IFO) is
connected to the indoor fan input on the MBB which will
indicate to the controls that the indoor fan should be turned on
(if not already on). If for some reason the overtemperature limit
switch trips prior to the start of the indoor fan blower, on the
next attempt the 45-second delay will be shortened by 5 sec-
onds. Gas will not be interrupted to the burners and heating will
continue. Once modified, the fan delay will not change back to
45 seconds unless power is reset to the control. The IGC boards
only control the first stage of gas heat on each gas valve. The
second stages are controlled directly from the MBB board. The
IGC board has a minimum on-time of 1 minute. In modes such
as Service Test where long minimum on times are not
enforced, the 1-minute timer on the IGC will still be followed
and the gas will remain on for a minimum of 1 minute.
Table 51 — Staged Gas Heat
Table 52 — Staged Gas Heat Control Steps (
Configuration
Heat
SG.CF
HT.ST
= 1)
UNIT SIZE HEAT CAPACITY
UNIT MODEL NO.
POSITION NO. 5
Configuration
HEAT
SG.CF
HT.ST
ENTRY VALUE
020-035
Low S 1= 5STAGE
High T 2= 7STAGE
040-050
Low S 1= 5STAGE
High T 1= 5STAGE
060
Low S 4 = 11 STAGE
High T 3= 9STAGE
STAGE
RELAY OUTPUT
CAPACITY
%
Heat 1 Heat 2 Heat 3 Heat 4 Heat 5 Heat 6
MBB-RLY8 MBB-RLY7 SCB-RLY1 SCB-RLY2 SCB-RLY3 SCB-RLY4
IGC1 MGV1 IGC2 MGV2 IGC3 MGV3
0 OFF OFF OFF OFF OFF OFF 0
1 ON OFF OFF OFF OFF OFF 37
2 ON ON OFF OFF OFF OFF 50
3 ON OFF ON OFF OFF OFF 75
4 ON ON ON OFF OFF OFF 87
5 ON ON ON ON OFF OFF 100