Specifications

55
Table 63 — Building Pressure Configuration
*Some configurations are machine dependent.
Table 64 — Power Exhaust Staging (
BP.CF
=1)
Table 65 — Power Exhaust Staging (
BP.CF
=2)
The configurations of interest in the controlling of building
pressure with this algorithm are:
Configuration
BP
B.CFG
BP.HP (building pressure
high threshold level)
Configuration
BP
B.CFG
BP.LP (building pressure
low threshold level)
Configuration
BP
B.CFG
BP.TM (building pressure
timer)
This control function is allowed to add or select power ex-
haust stages at any time, except that a delay time must expire
after a stage is added or subtracted. Any time a stage change is
made, a timer is started which delays staging for 10 * BP.TM
seconds. The default for BP.TM is 1, therefore the delay
between stage changes is set to 10 seconds.
The logic to add or subtract a stage of power exhaust is:
If building pressure (Pressures
AIR.P
BP) is greater
than the building pressure set point (Configuration
BP
BPSP) plus the building pressure high threshold level
(Configuration
BP
B.CFG
BP.HP) add a stage of
power exhaust.
If building pressure (Pressures
AIR.P
BP)islessthan
the building pressure set point (Configuration
BP
BPSP) minus the building pressure low threshold
level (Configuration
BP
B.CFG
BP.LP) subtract a
stage of power exhaust.
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT
BP
BUILDING PRESS. CONFIG
BP.CF
Building Press. Config 0-2 BLDG_CFG 0*
BP.MT
Power Exhaust Motors 1-2 PWRM 1*
BP.S
Building Pressure Sensor Enable/Dsable BPSENS Dsable*
BP.R
Bldg Press (+/–) Range 0 - 1.00 BP_RANGE 0.25
BP.SP
Building Pressure Setp. -0.25 -> 0.25 "H2O BPSP 0.05
BP.P1
Power Exhaust On Setp.1 0 - 100 % PES1 35
BP.P2
Power Exhaust On Setp.2 0 - 100 % PES2 75
B.CFG
BP ALGORITHM CONFIGS
BP.SL
Modulating PE Alg. Slct. 1-3 BPSELECT 1
BP.TM
BP PID Evaluation Time 0 - 10 min BPPERIOD 1
BP.ZG
BP Threshold Adjustment 0.1 - 10.0 BPZ_GAIN 1
BP.HP
High BP Level 0 - 1.000 BPHPLVL 0.05
BP.LP
Low BP Level 0 - 1.000 BPLPLVL 0.04
BP.MT
= 1 (4 motors) PE.A PE.B PE.C
Power Exhaust Stage 0 OFF OFF OFF
Power Exhaust Stage 1 OFF ON OFF
Power Exhaust Stage 2 ON ON ON
BP.MT
= 2 (6 motors) PE.A PE.B PE.C
Power Exhaust Stage 0 OFF OFF OFF
Power Exhaust Stage 1 OFF OFF ON
Power Exhaust Stage 2 ON ON ON
BP.MT
= 1 (4 motors) PE.A PE.B PE.C
Power Exhaust Stage 0 OFF OFF OFF
Power Exhaust Stage 1 ON OFF OFF
Power Exhaust Stage 2 OFF ON OFF
Power Exhaust Stage 3 ON ON OFF
Power Exhaust Stage 4 ON ON ON
BP.MT
= 2 (6 motors) PE.A PE.B PE.C
Power Exhaust Stage 0 OFF OFF OFF
Power Exhaust Stage 1 ON OFF OFF
Power Exhaust Stage 2 OFF ON OFF
Power Exhaust Stage 3 ON ON OFF
Power Exhaust Stage 4 ON OFF ON
Power Exhaust Stage 5 OFF ON ON
Power Exhaust Stage 6 ON ON ON