Specifications

60
Table 67 — CCN Configuration
CCN Bus Number (
CCNB) — This configuration is the CCN
bus the rooftop is assigned.
CCN Baud Rate (
BAUD) This configuration is the CCN
baud rate.
CCN Time/Date Broadcast (
TM.DT) If this configuration
is set to ON, the control will periodically send the time and date
out onto the CCN bus once a minute. If this device is on a CCN
network then it will be important to make sure that only one
device on the bus has this configuration set to ON. If more than
one time broadcaster is present, problems with the time will
occur.
NOTE: Only the time and date broadcaster can perform
daylight savings time adjustments. Even if the rooftop is stand
alone, the user may want to set this to ON to accomplish the
daylight/savings function.
CCN OAT Broadcast (
OAT.B) If this configuration is set
to ON, the control will periodically broadcast its outside-air
temperature at a rate of once every 30 minutes.
CCN OARH Broadcast (
ORH.B) If this configuration is
set to ON, the control will periodically broadcast its outside air
relative humidity at a rate of once every 30 minutes.
CCN OAQ Broadcast (
OAQ.B) If this configuration is set
to ON, the control will periodically broadcast its outside air
quality reading at a rate of once every 30 minutes.
Global Schedule Broadcast (
G. S .B) If this configuration is
set to ON and the schedule number (SCH.N) is between 65 and
99, then the control will broadcast the internal time schedule
once every 2 minutes.
CCN Broadcast Acknowledger (
B.ACK) If this configu-
ration is set to ON, then when any broadcasting is done on the
bus, this device will respond to and acknowledge. Only one de-
vice per bus can be configured for this option.
Schedule Number (
SCH.N) This configuration determines
what schedule the control may follow.
SCH.N = 0 The control is always occupied.
SCH.N = 1 The control follows its internal time sched-
ules. The user may enter any number
between 1 and 64 but it will be overwritten
to “1” by the control as it only has one
internal schedule.
SCH.N = 65-99 The control is either set up to receive to a
broadcasted time schedule set to this
number or the control is set up to broadcast
its internal time schedule (G. S . B )tothe
network and this is the global schedule
number it is broadcasting. If this is the case,
then the control still follows its internal time
schedules.
Accept Global Holidays? (
HOL.T) If a device is broad-
casting the time on the bus, it is possible to accept the time yet
not accept the global holiday from the broadcast message.
Override Time Limit (
O.T.L) This configuration allows
the user to decide how long an override occurs when it is initi-
ated. The override may be configured from 1 to 4 hours. If the
time is set to 0, the override function will become disabled.
Timed Override Hours (
OV.EX) This displays the current
number of hours left in an override. It is possible to cancel an
override in progress by writing “0” to this variable, thereby
removing the override time left.
SPT Override Enabled? (
SPT.O) If a space sensor is
present, then it is possible to override an unoccupied period by
pushing the override button on the T55 or T56 sensor. This
option allows the user to disable this function by setting this
configuration to NO.
T58 Override Enabled? (
T58.O) —TheT58sensorisaCCN
device that allows cooling/heating set points to be adjusted,
space temperature to be written to the rooftop unit, and the abil-
ity to initiate a timed override. This option allows the user to
disable the override initiated from the T58 sensor by setting
this option to NO.
Global Schedule Override? (
GL.OV) If the control is set
to receive global schedules then it is also possible for the global
schedule broadcaster to call out an override condition as well.
This configuration allows the user to disable the global sched-
ule broadcaster from overriding the control.
Alert Limit Configuration — The ALLM submenu is
used to configure the alert limit set points. A list is shown in
Table 68.
SPT Low Alert Limit/Occ (
SP.L.O) If the space tempera-
ture is below the configurable occupied SPT Low Alert Limit
(SP.L.O), then Alert 300 will be generated and the unit will be
stopped. The alert will automatically reset.
SPT High Alert Limit/Occ (
SP.H.O) — If the space tempera-
ture is above the configurable occupied SPT High Alert Limit
(SP.H.O), then Alert 301 will be generated and the unit will be
stopped. The alert will automatically reset.
SPT Low Alert Limit/Unocc (
SP.L.U) If the space tem-
perature is below the configurable unoccupied SPT Low Alert
Limit (SP.L.U), then Alert 300 will be generated and the unit
will be stopped. The alert will automatically reset.
SPT High Alert Limit/Unocc (
SP.H.U) If the space tem-
perature is above the configurable unoccupied SPT High Alert
Limit (SP.H.U), then Alert 301 will be generated and the unit
will be stopped. The alert will automatically reset.
ITEM EXPANSION RANGE UNITS POINT DEFAULT
CCN
CCN CONFIGURATION
CCNA
CCN Address 1 - 239 CCNADD 1
CCNB
CCN Bus Number 0 - 239 CCNBUS 0
BAUD
CCN Baud Rate 1 - 5 CCNBAUDD 3
BROD
CCN BROADCST DEFINITIONS
TM.DT
CCN Time/Date Broadcast ON/OFF CCNBC On
OAT.B
CCN OAT Broadcast ON/OFF OATBC Off
ORH.B
CCN OARH Broadcast ON/OFF OARHBC Off
OAQ.B
CCN OAQ Broadcast ON/OFF OAQBC Off
G.S.B
Global Schedule Broadcst ON/OFF GSBC Off
B.ACK
CCN Broadcast Ack'er ON/OFF CCNBCACK Off
SC.OV
CCN SCHEDULES-OVERRIDES
SCH.N
Schedule Number 0 - 99 SCHEDNUM 1
HOL.T
Accept Global Holidays? YES/NO HOLIDAYT No
O.T.L.
Override Time Limit 0 - 4 HRS OTL 1
OV.E X
Timed Override Hours 0 - 4 HRS OVR_EXT0
SPT.O
SPT Override Enabled ? YES/NO SPT_OVER Yes
T58.O
T58 Override Enabled ? YES/NO T58_OVER Yes
GL.OV
Global Sched. Override ? YES/NO GLBLOVER No