Specifications

61
Table 68 — CONFIGURATION — ALLM Submenu
EDT Low Alert Limit/Occ (
SA.L.O) — If the space tempera-
ture is below the configurable occupied evaporator discharge
temperature (EDT) Low Alert Limit (SA.L.O), then Alert 302
will be generated and cooling operation will be stopped but
heating operation will continue. The alert will automatically
reset.
EDT High Alert Limit/Occ (
SA.H.O) — If the space temper-
ature is above the configurable occupied EDT High Alert Limit
(SA.H.O), then Alert 303 will be generated and heating opera-
tion will be stopped but cooling operation will continue. The
alert will automatically reset.
EDT Low Alert Limit/Unocc (
SA.L.U) If the space tem-
perature is below the configurable unoccupied EDT Low Alert
Limit (SA.L.U), then Alert 302 will be generated and cooling
operation will be stopped but heating operation will continue.
The alert will automatically reset.
EDT High Alert Limit/Unocc (
SA.H.U) If the space tem-
perature is above the configurable unoccupied EDT High Alert
Limit (SA.H.U), then Alert 303 will be generated and heating
operation will be stopped but cooling operation will continue.
The alert will automatically reset.
RAT Low Alert Limit/Occ (
RA.L.O) — If the return-air tem-
perature is below the configurable occupied RAT Low Alert
Limit (RA.L.O), then Alert 304 will be generated and internal
routines will be modified. Unit operation will continue but
VAV heating operation will be disabled. The alert will automat-
ically reset.
RAT High Alert Limit/Occ (
RA.H.O) If the return-air
temperature is above the configurable occupied RAT High
Alert Limit (RA.H.O), then Alert 305 will be generated and
operation will continue. The alert will automatically reset.
RAT Low Alert Limit/Unocc (
RA.L.U) If the return-air
temperature is below the configurable unoccupied RAT Low
Alert Limit (RA.L.U), then Alert 304 will be generated. Unit
operation will continue but VAV heating operation will be dis-
abled. The alert will automatically reset.
RAT High Alert Limit/Unocc (
RA.H.U) If the return-air
temperature is above the configurable unoccupied RAT High
Alert Limit (RA.H.U), then Alert 305 will be generated. Oper-
ation will continue. The alert will automatically reset.
RARH Low Alert Limit (
R.RH.L) If the unit is config-
ured to use a return air relative humidity sensor (Configura-
tion
UNIT
SENS
RRH.S), and the measured level is
below the configurable RH Low Alert Limit (R.RH.L), then
Alert 308 will occur. The unit will continue to run and the alert
will automatically reset.
RARH High Alert Limit (
R.RH.H) If the unit is config-
ured to use a return air relative humidity sensor (Configura-
tion
UNIT
SENS
RRHS), and the measured level is
above the configurable RARH High Alert Limit (R.RH.H),
then Alert 309 will occur. The unit will continue to run and the
alert will automatically reset.
Supply Duct Pressure Low Alert Limit (
SP.L) If the unit
is a VAV unit with a supply duct pressure sensor and the mea-
sured supply duct static pressure is below the configurable SP
Low Alert Limit (DP.L), then Alert 310 will occur. The unit
will continue to run and the alert will automatically reset.
Supply Duct Pressure High Alert Limit (
SP.H) If the unit
is a VAV unit with a supply duct pressure sensor and the mea-
sured supply duct static pressure is above the configurable SP
High Alert Limit (SP.H), then Alert 311 will occur. The unit
will continue to run and the alert will automatically reset.
Building Pressure Low Alert Limit (
BP.L) If the unit is
configured to use modulating power exhaust then a building
static pressure limit can be configured using the BP Low Alert
Limit (BP.L). If the measured pressure is below the limit then
Alert 312 will occur.
Building Pressure High Alert Limit (
BP.H) If the unit is
configured to use modulating power exhaust then a building
static pressure limit can be configured using the BP Hi Alert
Limit (BP.H). If the measured pressure is above the limit, then
Alert 313 will occur.
Indoor Air Quality High Alert Limit (
IAQ.H) If the unit
is configured to use a CO
2
sensor and the level is above the
configurable IAQ High Alert Limit (IAQ.H) then the alert will
occur. The unit will continue to run and the alert will automati-
cally reset.
Sensor Trim Configuration — The TRIM submenu
is used to calibrate the sensor trim settings. The trim settings
are used when the actual measured reading does not match the
sensor output. The sensor can be adjusted to match the actual
measured reading with the trim function. A list is shown in
Table 69.
Air Temperature Leaving Supply Fan Sensor (
SAT.T) —This
variable is used to adjust the supply fan temperature sensor
reading. The sensor reading can be adjusted ± 10° F to match
the actual measured temperature.
Return Air Temperature Sensor Trim (
RAT.T) —Thisvari-
able is used to adjust the return air temperature sensor reading.
The sensor reading can be adjusted ± 10° F to match the actual
measured temperature.
ITEM EXPANSION RANGE UNITS POINT DEFAULT
SP.L.O
SPT lo alert limit/occ -10-245 dF SPLO 60
SP.H.O
SPT hi alert limit/occ -10-245 dF SPHO 85
SP.L.U
SPT lo alert limit/unocc -10-245 dF SPLU 45
SP.H.U
SPT hi alert limit/unocc -10-245 dF SPHU 100
SA.L.O
EDT lo alert limit/occ -40-245 dF SALO 40
SA.H.O
EDT hi alert limit/occ -40-245 dF SAHO 100
SA.L.U
EDT lo alert limit/unocc -40-245 dF SALU 40
SA.H.U
EDT hi alert limit/unocc -40-245 dF SAHU 100
RA.L.O
RAT lo alert limit/occ -40-245 dF RALO 60
RA.H.O
RAT hi alert limit/occ -40-245 dF RAHO 90
RA.L.U
RAT lo alert limit/unocc -40-245 dF RALU 40
RA.H.U
RAT hi alert limit/unocc -40-245 dF RAHU 100
R.RH.L
RARH low alert limit 0-100 % RRHL 0
R.RH.H
RARH high alert limit 0-100 % RRHH 100
SP.L
SP low alert limit 0-5 "H2O SPL 0
SP.H
SP high alert limit 0-5 "H2O SPH 2
BP.L
BP lo alert limit -0.25-0.25 "H2O BPL -0.25
BP.H
BP high alert limit -0.25-0.25 "H2O BPH 0.25
IAQ.H
IAQ high alert limit 0-5000 IAQH 1200
IMPORTANT: Sensor trim must not be used to extend
unit operation past the allowable operating range.
Doing so may void the warranty.