Specifications

63
Table 70 — Switch Logic Configuration
Table 71 — CONFIGURATION — DISP Submenu
Remote Control Switch Input — The remote switch
input is located on the ECB-1 board and connected to TB6 ter-
minals 1 and 3. The switch can be used for several remote con-
trol functions. See Table 72.
Table 72 — Remote Switch Configuration
Remote Input State
(Inputs
GEN.I
REMT) —Thisis
the actual real time state of the remote input.
Remote Switch Config
(Configuration
UNIT
RM.CF)
This is the configuration that allows the user to assign dif-
ferent types of functionality to the remote discrete input.
0 — NO REMOTE SW — The remote switch will not be
used.
1 — OCC-UNOCC SW — The remote switch input will
control the occupancy state. When the remote switch
input is ON, the unit will forced into the occupied mode.
When the remote switch is OFF, the unit will be forced
into the unoccupied mode.
2 STRT/STOP The remote switch input will start
andstoptheunit.Whentheunitiscommandedtostop,
any timeguards in place on compressors will be honored
first. When the remote switch is ON, the unit will be
commanded to stop. When the remote switch is OFF the
unit will be enabled to operate.
3 — OVERRIDE SW — The remote switch can be used
to override any internal or external time schedule being
used by the control and force the unit into an occupied
mode when the remote input state is ON. When the
remote switch is ON, the unit will be forced into an occu-
pied state. When the remote switch is OFF, the unit will
use its internal or external time schedules.
Remote Switch Logic Configuration
(Configuration
SW.LG
RMI.L) The control allows for the configuration
of a normally open/closed status of the remote input switch via
RMI.L. If this variable is configured OPEN, then when the
switch is open, the remote input switch perceives the logic state
as OFF. Correspondingly, if RMI.L is set to CLOSED, the re-
mote input switch will perceive a closed switch as meaning
OFF. See Table 73.
Hot Gas Bypass — Hot gas bypass is an active part of
the A-Series ComfortLink™ capacity staging and minimum
evaporator load protection functions. It is controlled though the
Minimum Load Valve function.
The hot gas bypass option consists of a solenoid valve with
a fixed orifice sized to provide a nominal 3-ton evaporator load
bypass. A hot gas refrigerant line routes the bypassed hot gas
from Circuit As discharge line to Circuit As evaporator
distributor. When the unit control calls for hot gas bypass, the
hot gas enters the evaporator coil and adds refrigeration load
to the compressor circuit to reduce the cooling effect from
Circuit A.
The hot gas bypass system is a factory-installed option
installed on Circuit A only. This function is enabled at Config-
uration
COOL
MLV. When this function is enabled, an
additional stage of cooling capacity is provided by the unit
control staging sequences (see Table 42).
ITEM EXPANSION RANGE CCN POINT DEFAULT
SW.LG
SWITCH LOGIC: NO / NC
FTS.L
Filter Status Inpt-Clean Open/Close FLTSLOGC Open
IGC.L
IGC Feedback - Off Open/Close GASFANLG Open
RMI.L
RemSw Off-Unoc-Strt-NoOv Open/Close RMTINLOG Open
ECS.L
Economizer Switch - No Open/Close ECOSWLOG Open
SFS.L
Fan Status Sw. - Off Open/Close SFSLOGIC Open
DL1.L
Dmd.Lmt.Sw.1 - Off Open/Close DMD_SW1L Open
DL2.L
Dmd.Lmt.Sw.2 - Off Open/Close DMD_SW2L Open
IAQ.L
IAQ Disc.Input - Low Open/Close IAQINLOG Open
FSD.L
Fire Shutdown - Off Open/Close FSDLOGIC Open
PRS.L
Pressurization Sw. - Off Open/Close PRESLOGC Open
EVC.L
Evacuation Sw. - Off Open/Close EVACLOGC Open
PRG.L
Smoke Purge Sw. - Off Open/Close PURGLOGC Open
ITEM EXPANSION RANGE UNITS POINT DEFAULT
TEST
Test Display LEDs ON/OFF TEST Off
METR
Metric Display ON/OFF DISPUNIT Off
LANG
Language Selection 0-1(multi-text strings) LANGUAGE 0
PAS.E
Password Enable ENABLE/DISABLE PASS_EBL Enable
PASS
Service Password 0000-9999 PASSWORD 1111
ITEM EXPANSION RANGE
CCN
POINT
REMT
Remote
Input State
ON/OFF RMTIN
RM.CF
Remote Switch
Config
0 - 3 RMTINCFG
RMI.L
RemSw
Off-Unoc-Strt-NoOv
Open/Close RMTINLOG