Table 2B Electrical Data (Units With Optional Convenience Outlet) (cont)
ELECTRIC HEAT BRANCH CIRCUIT FOR 208/240-V 75-kW ELECTRIC HEAT
FEEDER CIRCUIT FOR 208/230-V UNIT WITH 75-kW ELECTRIC HEAT
See Legend and Notes on page 10.
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
DISCONNECT
SIZE
No. 1 No. 2 No. 3
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP* FLA
020
208/230 187 253 16.7 130.0 16.7 130.0 22.4 184.0 4.0
1
/
4
1.5
——
5.0 16.7/15.2
—— 89/ 88 110/110 100/ 90
2 1.0 5.9 101/ 99 110/110 110/110
7.5 24.2/22.0
—— 97/ 94 110/110 100/100
2 1.0 5.9 109/106 125/125 125/110
19/25 52/ 60
5.0 16.7/15.2
—— 92/100 110/110 100/ 90
2 1.0 5.9 107/115 110/125 110/110
7.5 24.2/22.0
—— 102/109 110/110 100/100
2 1.0 5.9 116/124 125/125 125/110
38/50 104/120
5.0 16.7/15.2
—— 157/145 175/150 150/175
2 1.0 5.9 172/160 175/175 175/175
7.5 24.2/22.0
—— 167/154 175/175 150/175
2 1.0 5.9 181/169 200/175 175/200
56/75 156/180
5.0 16.7/15.2
—— 89/ 88 110/110 100/ 90
2 1.0 5.9 101/ 99 110/110 110/110
7.5 24.2/22.0
—— 97/ 94 110/110 100/100
2 1.0 5.9 109/106 125/125 125/110
460 414 506 9.0 70.0 9.0 70.0 10.7 90.0 4.0
1
/
4
0.7
——
5.0 7.6
—— 45 50 45
21.03.1 51 60 60
7.5 11.0
—— 48 50 50
21.03.1 54 60 60
25 30
5.0 7.6
—— 51 60 45
21.03.1 59 60 60
7.5 11.0
—— 55 60 50
21.03.1 63 70 60
50 60
5.0 7.6
—— 73 80 80
21.03.1 81 90 90
7.5 11.0
—— 78 80 90
21.03.1 85 90 90
75 90
5.0 7.6
—— 103 125 125
2 1.0 3.1 111 125 125
7.5 11.0
—— 108 125 125
2 1.0 3.1 115 125 125
575 518 633 7.0 55.0 7.0 55.0 9.3 73.0 4.0
1
/
4
0.7
——
5.0 6.1
—— 38 45 40
21.03.1 44 50 45
7.5 9.0
—— 40 45 45
21.03.1 47 50 50
25 24
5.0 6.1
—— 41 45 40
21.03.1 49 50 45
7.5 9.0
—— 45 45 45
21.03.1 53 60 50
48 46
5.0 6.1
—— 69 70 60
21.03.1 77 80 70
7.5 9.0
—— 73 80 70
21.03.1 80 90 80
78 75
5.0 6.1
—— 86 100 100
2 1.0 3.1 94 100 110
7.5 9.0
—— 90 100 100
2 1.0 3.1 98 100 110
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
DISCONNECT
SIZE
No. 1 No. 2 No. 3
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP* FLA
020 208/240 187 253 NA NA NA NA NA NA NA NA NA 56/75 156/180 NA NA NA NA NA 156/180 175/200 200/225
UNIT
SIZE
50HG
NOMINAL
VOLTAGE
(3 Ph, 60 Hz)
VOLTAGE
RANGE
COMPRESSOR
OFM
ELECTRIC
HEAT
IFM
POWER
EXHAUST
POWER
SUPPLY
DISCONNECT
SIZE
No. 1 No. 2 No. 3
Min Max RLA LRA RLA LRA RLA LRA Qty Hp
FLA
(ea)
kW FLA Hp FLA Qty Hp
FLA
(ea)
MCA MOCP* FLA
020 208/230 187 253 16.7 130.0 16.7 130.0 22.4 184.0 4.0
1
/
4
1.5 56/75 156/180
5.0 16.7/15.2
—— 183/205 200/225 200/225
2 1.0 5.9 198/220 200/225 225/250
7.5 24.2/22.0
—— 193/214 200/225 225/250
2 1.0 5.9 207/229 225/250 225/250