Specifications

e. Configure High Reference. Scroll down to IRH. De-
fault is 2000 ppm. Range is 0 to 5000 ppm.
IAQ Algorithms
IQMP = ECON + 100 x IAQG x (Demand)/IAQS
Where:
ECON = Current position of economizer damper
(Demand) = IAQS - IAQ
NOTE: IQMP will not be recalculated until (Demand) ex-
ceeds 3% of IAQS.
IAQ (Pre-Occupancy) PURGE If outdoor air conditions
permit, IAQ Pre-Occupancy Purge will open economizer and
energize supply fan 2 hours before next Occupied period, to
provide complete exchange of indoor air with fresh air.
Duration of purge mode is user-configured (typically 5 min-
utes). The IAQ Purge is Mode 28. See Table 25. The factory-
installed economizer option is required.
Sequence of Operation The IAQ Purge will operate only
if the following conditions exist:
Current Time and next Occupied Time are valid.
Purge option is enabled.
Unit is in Unoccupied state.
Time is within 2 hours of next Occupied period.
Time is within Purge Duration.
Outside-Air Temperature reading is available.
If IAQ Purge is permitted, then IAQ Pre-Occupancy Purge
is enabled. The supply fan and Heat Interlock Relays are en-
ergized. The economizer minimum position is set to PURGEMP.
The economizer opens to PURGEMP. The purge continues
until Purge Duration expires or Occupied period begins.
NOTE: IAQ Purge is limited to one per Unoccupied period.
If PURGEMP = 0% then IAQ Purge is not enabled.
Configuration See Table 27. To configure:
1. Enable Purge option. Press to enter the sub-
function. Scroll down to PURG. Set to 1 to Enable. (Set
to 0 to disable.)
NOTE: The following user-configured options require use
of Service Tool or CCN Building Supervisor to change.
2. Select Purge Duration period. Change IQPD set point. De-
fault is 5 minutes. Range is 5 to 60 minutes.
3. Select Low Temperature Minimum Position. Change LTMP
set point. Default is 10%. Range is 0 to 100%.
4. Select High Temperature Minimum Position. Change HTMP
set point. Default is 35%. Range is 0 to 100%.
OUTDOORAIR CONTROL (OAC) The Outdoor Air Con-
trol function will maintain a minimum quantity of outdoor
airflow into an occupied space, regardless of space comfort
load conditions. The OAC is permitted only during Occu-
pied periods. Occupied Cooling (including Economizer Cool-
ing) and Occupied Heating are permitted during OAC and
will function normally, except when OAC mode is active,
then OAC mode may dictate a more open economizer po-
sition. See Table 28. The factory-installed economizer op-
tion and factory-installed control options module (PSIO-2)
are required.
An OAC Accessory package (consists of velocity sensor
and pressure transducer) (P/N 50DJ-900---791) is required.
Table 26 Configuring Indoor Air Quality (IAQ)
DESCRIPTION HOW TO CONFIGURE AT HISO SET POINT RANGE
Enable by selecting VENT option
VENT
1 = Use IAO only
3 = Use IAQ and OAC
Select IAQ Priority
LEVEL
1 = High
2 = Medium (Space Comfort Overrides)
3 = Low (Alert only)
Select IAQ Set Point
IAQS 1 to 5000 ppm
Specify IAQ Max Damper Position
IQMX 0 to 100%
Table 27 Configuring IAQ (Pre-Occupancy) Purge
DESCRIPTION HOW TO CONFIGURE AT HSIO SET POINT RANGE
Enable Purge
PURG Enable = 1; Disable = 0
LEGEND
IAQ Indoor Air Quality
IAQS IAQ Set Point
IRH IAQ Sensor High Reference
IRL IAQ Sensor Low Reference
IVH IAQ Sensor High Voltage Point
IVL IAQ Sensor Low Voltage Point
NOTE: Voltage range is 0 to 10.
Fig. 13 Sensor Use Example
26