Specifications
e. Configure High Reference. Scroll down to IRH. De-
fault is 2000 ppm. Range is 0 to 5000 ppm.
IAQ Algorithms
IQMP = ECON + 100 x IAQG x (Demand)/IAQS
Where:
ECON = Current position of economizer damper
(Demand) = IAQS - IAQ
NOTE: IQMP will not be recalculated until (Demand) ex-
ceeds 3% of IAQS.
IAQ (Pre-Occupancy) PURGE — If outdoor air conditions
permit, IAQ Pre-Occupancy Purge will open economizer and
energize supply fan 2 hours before next Occupied period, to
provide complete exchange of indoor air with fresh air.
Duration of purge mode is user-configured (typically 5 min-
utes). The IAQ Purge is Mode 28. See Table 25. The factory-
installed economizer option is required.
Sequence of Operation — The IAQ Purge will operate only
if the following conditions exist:
• Current Time and next Occupied Time are valid.
• Purge option is enabled.
• Unit is in Unoccupied state.
• Time is within 2 hours of next Occupied period.
• Time is within Purge Duration.
• Outside-Air Temperature reading is available.
If IAQ Purge is permitted, then IAQ Pre-Occupancy Purge
is enabled. The supply fan and Heat Interlock Relays are en-
ergized. The economizer minimum position is set to PURGEMP.
The economizer opens to PURGEMP. The purge continues
until Purge Duration expires or Occupied period begins.
NOTE: IAQ Purge is limited to one per Unoccupied period.
If PURGEMP = 0% then IAQ Purge is not enabled.
Configuration — See Table 27. To configure:
1. Enable Purge option. Press to enter the sub-
function. Scroll down to PURG. Set to 1 to Enable. (Set
to 0 to disable.)
NOTE: The following user-configured options require use
of Service Tool or CCN Building Supervisor to change.
2. Select Purge Duration period. Change IQPD set point. De-
fault is 5 minutes. Range is 5 to 60 minutes.
3. Select Low Temperature Minimum Position. Change LTMP
set point. Default is 10%. Range is 0 to 100%.
4. Select High Temperature Minimum Position. Change HTMP
set point. Default is 35%. Range is 0 to 100%.
OUTDOORAIR CONTROL (OAC) — The Outdoor Air Con-
trol function will maintain a minimum quantity of outdoor
airflow into an occupied space, regardless of space comfort
load conditions. The OAC is permitted only during Occu-
pied periods. Occupied Cooling (including Economizer Cool-
ing) and Occupied Heating are permitted during OAC and
will function normally, except when OAC mode is active,
then OAC mode may dictate a more open economizer po-
sition. See Table 28. The factory-installed economizer op-
tion and factory-installed control options module (PSIO-2)
are required.
An OAC Accessory package (consists of velocity sensor
and pressure transducer) (P/N 50DJ-900---791) is required.
Table 26 — Configuring Indoor Air Quality (IAQ)
DESCRIPTION HOW TO CONFIGURE AT HISO SET POINT RANGE
Enable by selecting VENT option
VENT
1 = Use IAO only
3 = Use IAQ and OAC
Select IAQ Priority
LEVEL
1 = High
2 = Medium (Space Comfort Overrides)
3 = Low (Alert only)
Select IAQ Set Point
IAQS 1 to 5000 ppm
Specify IAQ Max Damper Position
IQMX 0 to 100%
Table 27 — Configuring IAQ (Pre-Occupancy) Purge
DESCRIPTION HOW TO CONFIGURE AT HSIO SET POINT RANGE
Enable Purge
PURG Enable = 1; Disable = 0
LEGEND
IAQ — Indoor Air Quality
IAQS — IAQ Set Point
IRH — IAQ Sensor High Reference
IRL — IAQ Sensor Low Reference
IVH — IAQ Sensor High Voltage Point
IVL — IAQ Sensor Low Voltage Point
NOTE: Voltage range is 0 to 10.
Fig. 13 — Sensor Use Example
26