Specifications

Configuration To configure:
1. Enable Demand Limit. Press to enter the sub-
function. Scroll down to DLEN. Press to
ENTER
enable.
2. Select Loadshed Groups. Press to enter
the subfunction. Scroll down to LSGP. Coordinate Group
selection with CCN Loadshed Module equipment sched-
ules. Default is group 1. Range is 1 to 16.
3. Specify Demand Limit Set Point. Press to enter
the subfunction. Scroll down to LSP. The default is 50%.
The range is 0 to 100 %.
DIGITAL AIR VOLUME (DAV) Carrier rooftop units
with PIC may also have a communication linkage with the
VAV terminal units in a particular application. This linkage
is called the DAV linkage. The DAV mode indicates the unit
is being controlled through a CCN network and is connected
to DAV system. Digital Air Volume (DAV) is Mode 39. The
CCN Building Supervisor system is required. The CCN must
be connected to PSIO1, COMM1 port.
Linkage Data and Operation The values from the Termi-
nal System Manager (TSM) which are used as linkage data
by the rooftop PIC control are found in Table 39.
Table 39 TSM Linkage Codes
ITEM DEFINITION
AOCS Average Occupied Cool Set Point
AOHS Average Occupied Heat Set Point
AOZT Average Occupied Zone Temperature
AUCS Average Unoccupied Cool Set Point
AUHS Average Unoccupied Heat Set Point
AZT Average Zone Temperature
NEXTOCCD Next Occupied Day
NEXTOCCT Next Occupied Time
NEXTUNOD Next Unoccupied Day
NEXTUNOT Next Unoccupied Time
OCCSTAT Occupancy Status
PREVUNOD Previous Unoccupied Day
PREVUNOT Previous Unoccupied Time
Cooling/Heating Routines When the rooftop unit PIC is
part of a DAV system, the rooftop unit PIC utilizes infor-
mation supplied by the TSM to control cooling, heating, and
economizer routines instead of using its own return air and
space temperature sensors. The AOHS, AOCS, AUHS, and
AUCS from the TSM are used instead of the rooftop unit
PIC configured set points. The rooftop unit uses the occu-
pancy status information through the communication link-
age, such as NEXTOCCT and NEXTUNOT, instead of its
internal occupancy schedule.
VAV Systems During occupied and biased occupied pe-
riods on VAV systems, the rooftop unit PIC uses the AOZT
from the TSM to replace the rooftop unit PIC return-air tem-
perature sensor value. During unoccupied periods, the roof-
top unit PIC uses the AZT from the TSM instead of the roof-
top unit PIC space temperature and return-air temperature
sensor values.
Optimal Start Routine The following TSM points are used
in the optimal start portion of the rooftop unit PIC adaptive
optimal start/stop routine (AOSS): AZT, NEXTOCCT, NEX-
TOCCD, PREVUNOT, and PREVUNOD from the TSM. The
rooftop PIC uses this information to calculate a bias time
that is then used by both the rooftop PIC and the TSM. When
the current time of day is greater than the biased start time,
the rooftop PIC uses the AOZT from the TSM to determine
when the occupied set point has been achieved.
Unoccupied Free Cooling When the unoccupied free cool-
ing is configured, the rooftop PIC uses the AZT from the
TSM instead of the space temperature to determine if un-
occupied free cooling should operate.
Supply-Air Set Point (SASP) When Space Temperature
(SASP) reset is configured, the rooftop unit PIC uses theAOZT
and the AOCS from the TSM instead of the space tempera-
ture to determine the amount of reset required.
Linkage Alarms If the rooftop unit PIC which had pre-
viously been operating as part of a DAV system detects a
communication failure between the rooftop unit and the TSM,
the rooftop unit PIC continues to operate for 5 minutes using
the last information it received from the TSM. If commu-
nication resumes within the 5-minute period, normal system
operation continues. If the communication failure persists be-
yond 5 minutes, the rooftop unit PIC generates a linkage fail-
ure alarm. At that time, the rooftop unit PIC will return to
stand-alone operation using its own sensors and set points.
If the internal occupancy schedule for the rooftop unit PIC
has not been configured, the controls will maintain the same
occupancy state as prior to the linkage failure. If the occu-
pancy schedule is configured on the rooftop unit PIC, the
controls will maintain the same occupancy state as prior to
the linkage failure until the next scheduled occupancy tran-
sition. At that time, the rooftop unit PIC will revert to its
own internal occupancy schedule.
If communication is restored, normal DAV system opera-
tion resumes, and the rooftop unit PIC generates a linkage
return−to−normal message.