Specifications

109
APPENDIX D — BACnet Points List
CCN
TABLE
NAME
CCN
POINT
NAME
BACnet
OBJECT
NAME
EXPANDED NAME
BACnet
OBJECT
TYPE
BACnet
OBJECT
PROPERTIES
BACLink
DEFAULT
TEMPLATE
DISPLAY FORMAT/
ENGINEERING UNITS
STATUS01
SPT SPT Space Temperature AI RO Y –10 to +245 F
SAT SAT Supply Air Temperature AI RO Y –10 to +245 F
RAT RAT Return Air Temperature AI RO Y –10 to +245 F
SFS SFS Supply Fan Status BI RO Y on/off
SF SF Supply Fan Relay BO RO Y on/off
SP SP Duct Static Pressure AI RO Y 0.0 to 5.0 in. wg
IGV IGV Inlet Guide Vanes AI RO Y 0 to 100%
OAT OAT Outside Air Temperature AI RO –40 to +245 F
ECON ECON Economizer Damper AO RO Y 0 to 100%
BP BP Building Pressure AI RO –0.5 to +0.5 in. wg
EFRF EFRF Exhaust/Return Fan BO RO on/off
FLTS FLTS Filter Status BI RO dirty/clean
EXTCLK EXTCLK External Clock Input BV RW Y on/off
PED PED Power Exhaust Damper AO RO 0 to 100%
STATUS02
MM MM Motormaster/Fan Stage 1 BO RO on/off
FR2 FR2 Condenser Fan Stage 2 BO RO on/off
FR3 FR3 Condenser Fan Stage 3 BO RO on/off
HS1 HS1 Heat Stage 1 BO RO Y on/off
HS2 HS2 Heat Stage 2 BO RO Y on/off
STATUS03
RH RH Return/Space Humidity AI RO 0 to 100%
OARH OARH Outside Air Humidity AI RO 0 to 100%
ENTH ENTH Enthalpy Status BI RO hi/low
OAC OAC Outside Air CFM AI RO 0 to 50,000 CFM
IAQ IAQ IAQ (CO
2
) AI RO 0 to 5000 PPM
EVAC EVAC Evacuation BV RW alarm/norm
PRES PRES Pressurization BV RW alarm/norm
PURG PURG Smoke Purge BV RW alarm/norm
FSD FSD Fire Shutdown BV RW alarm/norm
FRZ FRZ Freezestat Status BI RO alarm/norm
HCV HCV Heating Valve AO RO 0 to 100%
STATUS04
STRST STRST Space Temperature Reset AI RO no/yes
UNCHT UNCHT Unoccupied Heating BV RO no/yes
UNCCL UNCCL Unoccupied Cooling BV RO no/yes
STDBY STDBY Unit in Standby BV RO no/yes
OPTST OPTST Optimal Start BV RO no/yes
UNOCC UNOCC Unoccupied BV RO no/yes
IAQPG IAQPG IAQ Purge BV RO no/yes
OPTSP OPTSP Optimal Stop BV RO no/yes
OCCHT OCCHT Occupied Heating BV RO no/yes
OCCCL OCCCL Occupied Cooling BV RO no/yes
OCCFO OCCFO Occupied Fan Only BV RO no/yes
NTFCL NTFCL Night Time Free Cooling BV RO no/yes
PRESS PRESS Pressurization BV RO no/yes
EVACN EVACN Evacuation BV RO no/yes
SMKPG SMKPG Smoke Purge BV RO no/yes
FIRES FIRES Fire Shutdown BV RO no/yes
TIMOV TIMOV Timed Override BV RO no/yes
HHOVR HHOVR High Humidity Override BV RO no/yes
IAQCL IAQCL IAQ/Outdoor Air CFM Ctrl* BV RO no/yes
STATUS05
CMPA1 CMPA1 Compressor A1 BO RO Y on/off
CPSA1 CPSA1 Compressor A1 Status BI RO on/off
ULDA1 ULDA1 Unloader A1 BO RO on/off
CMPA2 CMPA2 Compressor A2* BO RO on/off
ULDA2 ULDA2 Unloader A2* BO RO on/off
CPFA1 CPFA1 Compressor A1 Safety BI RO alarm/norm
STATUS06
CMPB1 CMPB1 Compressor B1 BO RO Y on/off
CMPB2 CMPB2 Compressor B2* BO RO on/off
CPSB1 CPSB1 Compressor B1 Status BI RO on/off
ULDB1 ULDB1 Unloader B1 BO RO on/off
ULDB2 ULDB2 Unloader B2* BO RO on/off
CPFB1 CPFB1 Compressor B1 Safety BI RO alarm/norm
CPFB2 CPFB2 Compressor B2 Safety* BI RO alarm/norm