Specifications

26
4. Specify IAQ Maximum Damper Position. Press
to enter the subfunction. Scroll down to
IQMX. Enter the new value. The default is 50%. The
range is 0 to 100%.
5. If non-Carrier sensor used (see Fig. 13):
a. Specify IAQ sensor curve. Press to enter
the subfunction.
b. Configure Low Voltage Point. Scroll down to IVL.
Default is 0 v. Range is 0 to 10 v.
c. Configure Low Reference. Scroll down to IRL.
Default is 0 ppm. Range is 0 to 5000 ppm.
d. Configure High Voltage Point. Scroll down to IVH.
Default is 10 v. Range is 0 to 10 v.
e. Configure High Reference. Scroll down to IRH.
Default is 2000 ppm. Range is 0 to 5000 ppm.
IAQ Algorithms
IMP = ECON + 100 x IAQG x (Demand)/IAQS
Where: ECON = Current position of economizer damper
(Demand) = IAQS – IAQ
NOTE: IMP will not be recalculated until (Demand) exceeds
3% of IAQS.
IAQ (Pre-Occupancy) PURGE — If outdoor air conditions
permit, IAQ Pre-Occupancy Purge will open economizer and
energize supply fan 2 hours before next Occupied period, to
provide complete exchange of indoor air with fresh air. Dura-
tion of purge mode is user-configured (typically 5 minutes).
The IAQ Purge is Mode 28. See Table 27. The factory-
installed economizer option is required.
Sequence of Operation
— The IAQ Purge will operate only if
the following conditions exist:
Economizer installed and enabled.
Current Time and next Occupied Time are valid.
Purge option is enabled.
Unit is in Unoccupied state.
Time is within 2 hours of next Occupied period.
Time is within Purge Duration.
Outdoor-Air Temperature reading is available.
If all the conditions above are satisfied, then IAQ Pre-
Occupancy Purge is enabled. The supply fan and Heat Inter-
lock Relays are energized. The economizer minimum position
is set to PURGEMP. The economizer opens to PURGEMP.
The purge continues until Purge Duration expires or Occupied
period begins.
NOTE: IAQ Purge is limited to one per Unoccupied period. If
PURGEMP = 0% then IAQ Purge is not enabled.
The control determines PURGEMP in the following manner:
NTLO OCSP
OAT <-------------|-----------------------------|--------------->Incr
Table 27 — Indoor-Air Quality Purge Definitions
Table 26 — Configuring Indoor Air Quality (IAQ)
PURGEMP
= LTMP
If Enthalpy Good:
PURGEMP
= HTMP
PURGEMP - 100%
-----------------------------
If Enthalpy
Not Acceptable:
PURGE MP = HTMP
ITEM DEFINITION
ENTH
Enthalpy
HTMP
High Temperature Minimum Position
IAQPG
IAQ Pre-Occupancy Purge Mode
IQPD
Purge Duration
LTMP
Low Temperature Minimum Position
NTLO
Nighttime Lockout Temperature
OAT
Outdoor-Air Temperature
OCSP
Occupied Cooling Set Point
PURG
Purge Option
PURGEMP
Purge Minimum Damper Position
DESCRIPTION HOW TO CONFIGURE AT HISO SET POINT RANGE
Enable by selecting VENT option
VENT
1 = Use IAQ only
3 = Use IAQ and OAC
Select IAQ Priority
LEVEL
1 = High
2 = Medium (Space Comfort Overrides)
3 = Low (Alert only)
Select IAQ Set Point
IAQS 1 to 5000 ppm
Specify IAQ Max Damper Position
IQMX 0 to 100%
LEGEND
NOTE: Voltage range is 0 to 10.
Fig. 13 — Sensor Use Example
IAQ
Indoor Air Quality
IAQS
IAQ Set Point
IRH
IAQ Sensor High Reference
IRL
IAQ Sensor Low Reference
IVH
IAQ Sensor High Voltage Point
IVL
IAQ Sensor Low Voltage Point