Instruction manual

16
Table 4 Wet Coil Air Delivery
ENGLISH
400 VOLT
UNIT
MOTOR
SPEED
EXTERNAL STATIC PRESSURE (IN. W.C)
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
50JZ---A24
Low
Watts 303 305 306 300 --- --- --- --- --- --- ---
Cfm 969 879 785 687 --- --- --- --- --- --- ---
High
Watts --- --- --- --- 435 428 428 422 --- --- ---
Cfm --- --- --- --- 963 833 758 676 --- --- ---
50JZ---A30
Low
Watts --- 1002 954 921 889 853 814 --- --- --- ---
Cfm --- 1189 1115 1041 971 903 833 --- --- --- ---
High
Watts --- --- --- --- --- --- --- 700 683 688 755
Cfm --- --- --- --- --- --- --- 1223 1142 1075 1058
50JZ---A36
Low
Watts 552 540 529 523 514 480 --- --- --- --- ---
Cfm 1296 1237 1167 1097 1029 952 --- --- --- --- ---
High
Watts --- --- --- --- --- 782 765 736 721 780 1002
Cfm --- --- --- --- --- 1467 1398 1321 1237 1165 1137
50JZ---A48
Low
Watts 692 686 678 664 652 664 736 --- --- --- ---
Cfm 1571 1509 1444 1370 1295 1240 1237 --- --- --- ---
High
Watts --- --- 1112 930 856 834 825 811 793 --- ---
Cfm --- --- 1693 1670 1601 1521 1447 1378 1294 --- ---
SI
400 VOLT
UNIT
MOTOR
SPEED
EXTERNAL STATIC PRESSURE (Pa)
0 25 50 75 100 125 150 175 200 225 250
50JZ---A24
Low
Watts 303 305 303 300 --- --- --- --- --- --- ---
L/s 458 415 371 324 --- --- --- --- --- --- ---
High
Watts --- --- --- --- 435 428 428 422 --- --- ---
L/s --- --- --- --- 455 393 358 319 --- --- ---
50JZ---A30
Low
Watts --- 1002 954 921 889 853 814 --- --- --- ---
L/s --- 561 526 491 458 426 393 --- --- --- ---
High
Watts --- --- --- --- --- --- --- 700 683 688 755
L/s --- --- --- --- --- --- --- 577 539 508 499
50JZ---A36
Low
Watts 552 540 529 523 514 480 --- --- --- --- ---
L/s 612 584 551 518 486 449 --- --- --- --- ---
High
Watts --- --- --- --- --- 782 765 736 721 780 1002
L/s --- --- --- --- --- 693 660 624 584 550 536
50JZ---A48
Low
Watts 692 686 678 664 652 664 736 --- --- --- ---
L/s 741 712 681 647 611 585 584 --- --- --- ---
High
Watts --- --- 1112 930 856 834 825 811 793 --- ---
L/s --- --- 799 788 756 718 683 650 611 --- ---
*Air delivery values are based on operatin g voltage of 400---v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain static
pressure available for ducting.
NOTES: 1. Do not operate the un it a t a cooling a irflow that is less than 350 cfm for each 12,000 Btuh (165 L/s for each 3.5 kW) of rated cooling capacity. Evaporator
coil frosting may occur at airflow below this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.
Table 5 Filter Pressure Drop (IN. W.C.) (Pa)
FILTER SIZE
in.
CFM
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300
20X20X1 0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15
20X24X1 --- 0.09 0.10 0.11 0.13 0.14 0.15 0.16
24X30X1 --- --- --- --- 0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18
FILTER SIZE
mm
L/s
236 283 330 378 425 472 519 566 614 661 707 755 802 850 896 944 991 1038 1085
508X508X25 12.4 17.4 19.9 24.9 29.9 32.3 34.8 37.3
508X610x25 --- 22.4 24.9 27.4 32.3 34.8 37.4 39.9
610X762x25 --- --- --- --- 17.4 19.9 22.4 24.9 27.4 29.9 32.3 34.8 37.3 39.8 42.3 44.6
Table 6 Accessory Electric Heat Pr essur e Dr op IN. W.C. (Pa)
HEATER kW
CFM
600 800 1000 1200 1400 1600 1800 2000 2200
6.5--17.4
0.030 0.033 0.037 0.042 0.047 0.052 0.060 0.067 0.075
L/s
283 378 472 569 661 755 850 944 1038
7.5 8.2 9.2 10.4 11.7 12.9 14.9 16.7 18.7
50JZ-- A