System information
11
Table 1 - Physical data
50JZ 024 030 036 048
Nominal cooling capacity* kW 6.9 8.6 10.7 14.4
Nominal heating capacity** kW 7.0 8.1 10.6 13.1
Operating weight kg 136 145 149 161
Compressor One scroll compressor
Refrigerant R-410A
Refrigerant meteringdevice AccuRater
Quantity kg 3.10 4.35 4.50 5.40
Orifice, inside diameter mm 1.50 1.55 1.70 1.98
Orifice, outside diameter mm 0.81 1.02 1.02 1.17
Outdoor coil
Rows .. fin spacing mm 2 ... 1.5 2 ... 1.5 2 ... 1.5 2 ... 1.5
Face area m
2
0.8 1.0 1.0 1.3
Outdoor fan
Nominal air flow l/s 1038 1038 1038 1133
Diameter mm 559 559 559 559
Motor power input kW 0.19 0.19 0.19 0.25
Motor speed r/s 15 15 15 22
Indoor coil
Rows .. fin spacing mm 3 ... 1.7 3 ... 1.7 4 ... 1.7 4 ... 1.7
Face area m
2
0.34 0.34 0.34 0.44
Indoor fan
Nominal air flow l/s 377 472 566 755
Size mm 254 x 254 254 x 254 254 x 254 254 x 279
Motor power input kW 0.19 0.37 0.37 0.75
Motor speed r/s 17.9 22.0 22.0 20.0
Return air filters Throwaway type
Size mm 508 x 508 508 x 508 508 x 610 610 x 762
* Based on 27°C db/19°C wb indoor air temperature, 35°C outdoor air temperature and nominal air flow.
** Based on 20°C db indoor air temperature, 6°C outdoor air temperature and nominal air flow.
*** The required filter sizes shown are based on the larger of the rated cooling air flows or the heating air flow velocity of 1.5 m/s for throwaway type filters or 2.3 m/s for
high-capacity type filters. Air filter pressure drop for non-standard filters must not exceed 20 Pa.
Table 2 - Minimum air flow for reliable electric heater operation
50JZ 024 030 036 048
Air flow l/s 377 472 566 755