Table 4--Wet Coil Air Delivery
Unit 50JZ 024-060 (Deduct 10 percent for 208-v)*
UNIT
024
030
036
042
048
06O
MOTOR SPEED
Watts
Low
Cfm
Watts
Med
Cfm
Watts
High Cfm
watts
Low
Cirri
Watts
Med
Cfm
Watts
High Cfm
Watts
Low
Cfm
Watts
Med
Cfm
Watts
High Cfm
Watts
Low
Cirn
Watts
Med
Cfm
Watts
High Cfm
Watts
Low
Cfm
Watts
Med
Cfm
Watts
High Cfm
Watts
Low
Clm
Watts
Med
Cfm
Watts
High Cfm
EXTERNAL STATIC PRESSURE (iN. WG)
0.0 0.1 0.2 0.3
275 273 271 270
923 844 754 669
359
941
276 276 272
963 929 781
375 377 371 362
1202 1170 1079 976
462 451 431 411
1374 1290 1205 1116
523 506 490 471
1500 1408 1301 1190
645 628 610
1474 1369 1267
660 639 524 611
1701 1659 1618 1576
620 600 586 574
1662 1621 1581 1540
763 747 729 709
1917 1868 1822 1774
852
1982
597 592 578 526
2265 2190 2101 2033
754 730 707 687
2383 2282 2202 2134
901 876 856 838
2480 2383 2301 2233
0.4 9.5 0.6 0.7 0.8 0.9 1.0
353 350 347 341
876 814 737 622
447 439 431 423
968 869 765 659
354 350
884 807
469 449 435 428
1174 988 828 718
394 381
1020 916
449 426
1082 977
595 584 575
1169 1069 962
598 583 564 841 518 495 473
1531 1481 1425 1363 1293 1223 1154
704 675 645 614 582 550
1701 1631 1550 1460 1361 1256
806- 777 749 726
1708 1614 1521 1435
562 548 530 510 487
1496 1447 1392 1331 1263
686 661 634 606 577 547 517
1722 1662 1594 1515 1427 1330 1227
832 809 784 757 730 704 682
1914 1839 1757 1669 1577 1486 1402
460 452 445
1974 1869 1614
671 658 646 630 603 558 486
2070 2005 t935 1858 1771 1667 1576
813 785 755 723 696 681 687
2175 2122 2066 1998 1910 1788 1619
* Air delivery values are based on operaf_ng voltage of 230-v or 460-v, wet coil, without filter or electric heater. Deduct l#ter and elect#t: heater pressure drop (see Tables
5 and 6) to obtain sta'6c pressure available for dueling.
NOTES:
1. DO not operate the unit at a cOOlingairflow that is less than 350 cfrn for each 12.000 Btuh of rated cooling capacity¸ Evaporator coil frosting may occur at ain3ows below
this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.
3. Deduct 10 percent for 208-v.
Table _FILTER PRESSURE DROP TABLE (In, wg)
FILTER SIZE CFM
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 210012200 2300
20X2OX1 0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15 -- --
20 X 24 X 1 0,09 0.10 0.11 0.13 0.14 0.15 0.16
0.09 ! 0.10
24X30X1 -- 0.07 0.08 0.11 0.12 0,13 0.1410.15 0.16 0.17 0.18
3-SPEED
Black = high
Violet = jumper
Orange = medium
Red = low
To change the speed of the blower motor (BM), remove fan motor
speed lead from the blower relay {BR_ and replace with the lead
for the desired blower motor speed. The motor speed lead is
attached to terminal BM, For low and medium speeds, black must
be connected to the jumper wire. Insulate removed lead end to
avoid contact with chassis parts. To select high speed on 460-v GE
motors, separate the black female quick connect (QC) from the
jumper lead male quick connect (QC) and connecl the black lead
to the BR. Insulate the jumper to avoid contact with any chassis
parts.
18