Installation guide

clear water. Do not splash water on the insulation, motor, wiring,
or air filter(sl. If the drain trough is restricted, clear it with a
"plumbers snake" or similar probe device.
Step 4.--Outdoor Fan
1. Remove 6 screws holding outdoor grille and motor to top
Cover.
2. Turn motor/grille assembly upside down on top cover to
expose fan blade.
3. Inspect the fan blades for cracks or bends.
4. If fan needs to be removed, loosen sctscrew and slide fan off
motor shaft.
5. When replacing fan blade, position blade so that the hub is 1/8
in. away from the motor end (1/8 in. of motor shaft will be
visible) (See Fig. 21 ).
6. Ensure that setscrew engages the flat area on the motor shaft
when tightening.
7. Replace grille.
Step 5_Electrical Controls and Wiring
Inspect and check the electrical controls and wiring annually. Be
.ruJ_ to turn off" the electrical power to the unit.
Remove access panel to locate all the electrical controls and
wiring. Check all electrical connections for tightness. Tighten all
screw connections. If any smoky or burned connecrous are
noticed, disassemble the connection, clean all the parts, restrip the
wire end and reassemble the connection properly and securely.
After inspecting the electrical controls and wiring, replace all the
panels. Start the unit, and observe at least one complete cooling
cycle to ensure proper operation. If discrepancies are observed in
operating cycle, or if a suspected malfunction has occurred, check
each electrical component with the proper electrical instrumenta-
tion. Refer to the unit wiring label when making these checkouts.
Step 6_Refrigerant Circuit
Inspect all refrigerant tubing connections and the unit base for oil
accumulation annually. Detecting oil generally indicates a refrig-
erant leak.
If oil is detected or if low performance is suspected, leak-test all
refrigerant tubing using an electronic leak detector, or liquid-soap
solution. If a refrigerant leak is detected, refer to Check for
Refrigerant Leaks section.
If no refrigerant leaks are found and low performance is suspected,
refer to Checking and Adjusting Refrigerant Charge section.
Step 7---Indoor Airflow
The heating and/or cooling airflow does not require checking
unless improper performance is suspected, lfa problem exists, be
sure that all supply- and return-air grilles are open and free from
obstructions, and that the alr f!lter is clean. When necessary, refer
to Indoor Airflow and Airflow Adjustments section to check the
system airflow.
Step 8_Metering Deviees-Accurater Piston
This metering device is a fixed orifice and is contained in the brass
hex-body in t/_ liquid line feeding the indoor and outdoor coils.
Step 9---Pressure Switches
Pressure switches are protective devices wired into cooWol circuit
(low voltage). They shut off compressor if abnormally high or low
C99097
Fig. 32--Refrigerant Circuit
pressures are present in the refrigeration circuit• These pressure
switches are specifically designed to operate with Puron (R-410A)
systems. R-22 pressure switches must not he used as replacements
for the Puron (R410A) system.
Step 10--Loss of Charge Switch
This switch is located on the liquid line and protects against low
suction pressures caused by such events as loss of charge, low
airflow across indoor coil, dirty filters, etc. It opens on a pressure
drop at about 20 psig. If system pressure is above this, switch
should be closed. To check switch:
1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohm meter leads across switch. You should have
continuity on a good switch.
NOTE: Because these switches are attached to refrigeration
system under pressure, it is not advisable to remove this device for
troubleshooting unless you are reasonably certain that a problem
exists. If switch must be removed, remove and recover all system
charge so that pressure gauges read 0 psi. Never open system
without breaking vacuum with dry nitrogen.
Step 11_igh-Pressure Switch
The high-pressure switch is located in the discharge /ine and
protects against excessive condenser coil pressure. It opens at 610
psig.
High pressure may be caused by a dirty outdoor coil, failed fan
motor, or outdoor air recirculation.
To check switch:
1. Turn off all power to unit.
2. Disconnect leads on switch.
3. Apply ohm meter leads across switch. You should have
continuity on a good switch.
Step 12--Copelanfl Scroll Compressor (Puron Refriger-
ant)
The compressor used in this product is specifically designed to
operate with Puron (R-410A) refrigerant and cannot be inter-
changed.
23