Fig. 17 — 50PEC Unit Manual or Auto Changeover with Complete C Controller Wiring
Complete C
10
Complete C
LEGEND
NOTES:
1. Compressor and blower motor thermally pro-
tected internally.
2. All wiring to the unit must comply with local
codes.
3. Transformer is wired to 240-V (ORG) lead for
240-1-50 units. For 220-1-50 operation, switch
the RED and ORG leads at L1 and insulate the
RED lead. Transformer is energy limiting or
may have a circuit breaker.
4. FP1 thermistor provides freeze protection for
water. When using anti-freeze solutions, cut
JW3 jumper.
5. For remote sensor, position jumper J1 on upper
2 pins.
6. For metric display, position jumper on 1 pin.
7. Transformer secondary ground via GRN/YEL
wire from C to control box.
8. Mate-N-Lok† plug is optional.
9. See view A for wiring of units with water valve
(part no. 23B00112N01) or view B for units with
water valve (part no. 23B00112N03).
10. Factory cut jumper (JW1). Dry contact will be
available between AL1 and AL2.
AL Alarm Relay Contacts
BM Blower Motor
BR Blower Relay
CAP Capacitor
CB Circuit Breaker
CO Sensor, Condensate Overflow
CR Compressor Relay
DM Damper Motor
ES End Switch
FP1 Sensor, Water Coil Freeze Protection
FP2 Sensor, Air Coil Freeze Protection
HPS High Pressure Switch
HPWS High Presure Water Switch
JW1 Jumper Wire for Alarm
LOC Loss of Charge Pressure Switch
PDB Power Distribution Block
RAS Return Air Sensor
RVS Reversing Valve Solenoid
TRANS
Transformer
WV
Water Valve
---------- Field Line Voltage Wiring
Field Low-Voltage Wiring
Printed Circuit Trace
Option Low Voltage Wiring
*Optional wiring.
†Registered trademark of AMP Incorporated.
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker
Relay Contacts-N.O.
Switch-Temperature
Switch-High Pressure
Switch-Low Pressure
Ground
Wire Nut
Mate-N-Lok
>
>