Fig. 18 — 50PEC Unit with Complete C and LON Controllers
Complete C
Complete C
LEGEND
*Optional wiring.
NOTES:
1. Compressor and blower motor thermally pro-
tected internally.
2. All wiring to the unit must comply with local
codes.
3. Transformer is wired to 240-V (ORG) lead for
240-1-50 units. For 220-1-50 operation, switch
the RED and ORG leads at L1 and insulate the
RED lead. Transformer is energy limiting or may
have a circuit breaker.
4. FP1 thermistor provides freeze protection for
water. When using anti-freeze solutions, cut JW3
jumper.
5. Low voltage wiring must be class 1 and voltage
rated equal or greater than unit supply voltage.
6. Factory cut jumper (JW1). Dry contact will be
available between AL1 and AL2.
7. Transformer secondary ground via GRN/YEL
wire from C to control box.
8. See view A for wiring of units with water valve
(part no. 23B00112N01) or view B for units with
water valve (part no. 23B00112N03).
AL Alarm Relay Contacts
BM Blower Motor
BR Blower Relay
CAP Capacitor
CB Circuit Breaker
CO Sensor, Condensate Overflow
CR Compressor Relay
DM Damper Motor
ES End Switch
FP1 Sensor, Water Coil Freeze Protection
FP2 Sensor, Air Coil Freeze Protection
FSS Fan Speed Switch
HP High-Pressure Switch
HPS High-Pressure Switch
HPWS High-Pressure Water Switch
JW1 Jumper Wire for Alarm
LOC Loss of Charge Pressure Switch
LON Local Operating Network
PB Power Terminal Block
RVS Reversing Valve Solenoid
TRANS Tra ns fo r me r
WV Water Valve
---------- Field Line Voltage Wiring
Field Low-Voltage Wiring
Option Low-Voltage Wiring
Printed Circuit Trace
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker
Relay Contacts-N.O.
Switch-Temperature
Switch-High Pressure
Switch-Low Pressure
Ground
Wire Nut
Mate-N-Lock
>
>