Installation guide

wireY)andECMboard(throughunitwireG)
acrossthe24-v.secondaryoftransformer(TRAN).
ThermidistatorThermostatandHumidistat:
Whentheroomtemperaturerisestoapointthatis
slightlyabovethecoolingcontrolsettingofthe
thermostat,thethermostatcompletesthecircuit
betweenthermostatterminalRtoterminalsY,O,
DH,andG.Thesecompletedcircuitsthroughthe
thermostatconnectcontactorcoil(C)(throughunit
wireY)andECMboard(thoughunitwireG)
acrossthe24-v.secondaryoftransformer
(TRANS).
(3.)PlacesystemswitchorMODEcontrolinHEAT
position.Setcontrolaboveroomtemperature.
Observethatcompressor,outdoorfan,andindoor
blowermotorsstart.Observethatheatingcycle
shutsdownaccordingtotimedelayselectedonthe
EasySelectboard(SeeEasySelectSection)when
controlsettingissatisfied.
(4.)Whenusinganautomaticchangeoverroom
thermostatplacebothSYSTEMorMODEcontrol
andFANmodeswitchesinAUTOpositions.
ObservethatunitoperatesinCoolingmodewhen
temperaturecontrolissetto"callforCooling"
(belowroomtemperature),andunitoperatesin
Heatingmodewhentemperaturecontrolissetto
"callforHeating"(aboveroomtemperature).
NOTE:Oncethecompressorhasstartedandthenhasstopped,it
shouldnotbestartedagainuntil5 minutes have elapsed. The
cooling cycle remains "on" until the room temperature drops to
point that is slightly below the cooling control setting of the room
thermostat. At this point, the thermostat "breaks" the circuit
between thermostat terminal R to terminals Y and G. These open
circuits de-energize contactor coil C and ECM board. The
condenser and compressor motors stop. After the time delay setting
selected on the Easy Select board (See Easy Select Section) , the
blower motor stops. The unit is in a "standby" condition, waiting
for the next "call for cooling" from the room thermostat. The 5
minute compressor delay also applies to heat pump heating mode.
Step 2 -- Check for Refrigerant Leaks
Locate and repair refrigerant leaks and charge the unit as follows:
1. 1. Use both high- and low-pressure ports to relieve system
pressure and reclaim remaining refrigerant.
2. Repair leak following accepted practices.
NOTE: Install a bi-flow filter drier whenever the system has been
opened for repair.
3. Check system for leaks using an approved method.
4. Evacuate refrigerant system and reclaim refrigerant if no
additional leaks are found.
5. Charge unit with R-410A refrigerant, using a
volumetriccharging cylinder or accurate scale. Refer to unit
rating plate for required charge.
Step 3 -- Start-Up Adjustments
Complete the required procedures given in the Pre-Start-Up
section before starting the unit. Do not jumper any safety devices
when operating the unit. Do not operate the unit in Cooling mode
when the outdoor temperature is below 40°F (4°C) (unless
accessory low-ambient kit is installed). Do not rapid-cycle the
compressor. Allow 5 rain. between "on" cycles to prevent
compressor damage.
CHECKING COOLING AND HEATING CONTROL
OPERATION
Start and check the unit for proper control operation as follows:
1. Place room thermostat SYSTEM switch or MODE control
in OFF position. Observe that blower motor starts when
FAN mode is placed in FAN ON position and shuts down
within 60 sec (030-060 size) or 30 sec (024 size) when
FAN MODE switch is placed in AUTO position.
2. Place system switch or MODE control in HEAT position.
Set control above room temperature. Observe that
compressor, outdoor fan, and indoor blower motors start.
Observe that heating cycle shuts down when control setting
is satisfied.
LEGEND
OUTDOORCOIL
I-"
1-"
¢
Bypass
Position
TXV in Meterin(
Position
r-q
LCS
NNDOOR COIL
HPS - High Pressure Switch
LCS - Loss of Charge Switch
_ _ _i}_Accuratet_Metering Device
f}-] Arrow indicates direction of flow
Fig. 23 - Typical Heat Pump Operation, Cooling Mode
D
0
C03011
17