Instruction manual
© 2014 Pentair Equipment Protection
89074139
- 16 -
ETHERNET COMMUNICATION MODE
• From Tools menu select Use Ethernet
• When Use Ethernet is checked, Comm Port selection is disabled, Device IP and Community boxes are shown and
Ethernet communication can be used.
• Enter unit’s IP Address and Community string in Device IP and Community boxes at the bottom of the PC Interface
Tool.
Each unit has two community strings. One is a Read/Write community string (defaulted to
‘private’) that can be changed by the customer (must be 4 to 8 characters long). The other is a
Read-Only community string (‘public’) and cannot be changed.
VIEWING AIR CONDITIONER UNIT VALUES
To view Air Conditioner Unit values
• Select the ACU Values tab
• Select the Enable Comm button (the PC Interface will now be communicating with unit)
• To stop communication select the Disable Comm button
CHANGING AIR CONDITIONER UNIT VALUES
To change ACU Values
• Select the Settings tab
• Select the value to change
• Make the change to the value
• Select the Change Setting button
• Change can be verified in ACU Values tab
VIEWING AND CHANGING ETHERNET INFORMATION
To view and change Ethernet Information
• Select Ethernet Info tab
To view Ethernet Information
• Click Read Ethernet Info button
To change to dynamically assigning IP Address Mode
• Check Use DHCP Server checkbox
• Enter Trap IP Address and Community
• Click Load Ethernet Info button
To change to statically assigning IP Address Mode
• Uncheck Use DHCP Server checkbox
• Enter Device IP Address, Subnet Mask, Gateway IP Address, Trap IP Address and Community
• Click Load Ethernet Info button
ALARM LOG ACCESSIBLE WITH SNMP
• Using custom software with the provided MIB file gives the ability to view a log of the last 25 alarms