7. Carefully check the compressor for proper operation - motor should cause slight vibration and the
outer case of the compressor should be warm. Is the compressor showing signs of this?
YES, wait 5 minutes, proceed to step 8.
NO, possible problem:
Defective start or run capacitor
Defective overload
Defective start relay
Defective contactor
Defective compressor
Repair or Replace
defective part
8. Make sure the coils are clean then check the evaporator “air in” and “air out” temperatures. If the
temperatures are the same:
Possible loss of refrigerant
Possible bad valves in compressor
Repair or Replace
defective part
SYMPTOMS AND POSSIBLE CAUSES  REMOTE ACCESS CONTROL VERSION
SYMPTOM POSSIBLE CAUSE
Unit won’t cool
Clogged fins on coil(s)
Dirty filter
Impellers not running
Compressor not running
Compressor runs, but has bad valves
Loss of refrigerant
Compressor tries to start but won’t run
Low line voltage at start. Should be +/-10% rated voltage.
Compressor motor stuck
Bad contactor
Bad overload switch
Bad run/start capacitor
Unit blows breakers
Undersized breaker/fuse or not time delayed
Short in system
Getting water in enclosure
Drain plugged
Drain tube kinked
Enclosure not sealed (allowing humidity in)
Mounting gasket damaged
For additional technical support, contact Pentair Equipment Protection at 800-896-2665.