® to the Expertg_ Installation, Start-Up, and Operating Instructions for Sizes 040-140, Series 110 & 120 Visit www.Carrier.com NOTE: Read the installation. the entire instruction manual before starting ISO 9001:2000 @ NOTE: This furnace can be installed as a (2-pipe) direct vent or (1-pipe) non-direct vent condensing gas furnace.
Required Notice for Massachusetts Installations IMPORTANT The Commonwealth of Massachusetts 5.08: Modifications to NFPA-54, 2) Revise 10.8.3 by adding requires Chapter the following additional a.
Check TABLE SAFETY OF CONTENTS CONSIDERATIONS CODES .......................... AND STANDARDS ELECTROSTATIC INTRODUCTION DISCHARGE (ESD) .................................... APPLICATIONS General 3 ........................... ... ..................................... Applications Downflow 13 16 Furnace Location and Application ..................... AIR FOR COMBUSTION AND VENTILATION ......... AIRFLOW A93041 18 18 .......... Fig. 1 - Multipoise 21 ...........................
Install this furnace only in a location and position as specified in LOCATION and INSTALLATION sections of these instructions. FIRE, EXPLOSION, CARBON MONOXIDE ELECTRICAL POISONING SHOCK HAZARD Always provide adequate combustion and ventilation air specified in section Combustion Air and Vent Pipe Systems these instructions to the furnace. AND Combustion products must be discharged outdoors.
The fl_rnace are protected shall be installed from water. so that the electrical components (Manufactured ANSI/NCS These furnaces are shipped with the following in proper fl_rnace installation. These materials main blower compartment. materials to assist are shipped in the Mobile Sites, and/or and Set-Ups), MH Series NSCNGPIC.
© 28 1_, (724mm) A_RFLOW _26 -- 1_6' (S94mm)_ 26 1_, (667mm) 22 _6 '(567n1 (21ram) I e_ ' C/ I (14ram) OUTLET CONDENSATE DRAIN .......... ON _'_'_19'(483mm) m) T _ _1..... o......... _ (DOWNFLOW & _, HORIZONTAL RIGHT 7 OR ALTERNATE 1_ IN DIAGAS CONN ) l GAS -+-f- % CONN NLET i OO;OENS:TEJ ./7 INLET DRAIN LOCATION DIMPLE LOCATORS / _ HORIZONTAL HANGING TYP "----'--_-I BOTTOM _NLET (S14mm) A05053 NOTES: 1. 2.
NSTALLATION e • • • e e ® e • • This forced air fumace is equipped for use with natural gas at altitudes 0 - 10,000 ft (0 - 3,050m), except 140 size furnaces are only approved for altitudes 0 - 7,000 fL (0 - 2,135m). An accessory kit, supplied by the manufacturer, shah be used to convert to propane gas use or may be _quired for some natural gas applications. This famace is for indoor installation in a building constructed on site.
ANY WIRE CONNECTED TO DISCHARGING YOUR CHARGE 2. Firmly furnace CONTROL PRIOR ELECTROSTATIC Step 2--Upflow hand discharged. touching DO NOT ungrounded during grounding 4. If you touch ungrounded with static electricity), 5.
BLOWERSHELF '_ \ CONDENSATE TRAP FURNACE DOOR _ CONDENSATE '_ X DOOR FURNACE _I;Z (INSIDE) !TRAP i URNACE L IDE 4 t (102mm) FIELD 26 DRAIN 261/4 (667mm) 11/2 (667mm) CONN ALTERNATE TUBE LOCATION DRAIN /4 4__. ( 146mm ) 3/4 (19mm) DRAIN (38mm) _5_3/4 CONN .
[W- NI__ PLUG--_I PLUG _-, / III COLLEOTORBOX"- ]11 II CAP _, COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED) COLLECTOR BOX '_ TUBE (PINK) "_ COLLECTOR BO×--,4 X'xL-_ COLLECTOR BOX TUBE (GREEN) _-_ I,, COLLECTOR BOX -DRAIN TUBE (BLUE) DRAIN TUBE) r_F I J _ _ IIII I!lL IIII FACTORY-BUPPUED/ ! I / cou7 A' ' / // O O CONDENSATETRAP ,.,.----.t__ IAI/ ,/, INDUCER J HOUSING DRAIN TUBE (VIOLET) /111/ A94164 Fig.
COLLECTOR DRAIN TUBE (BLUE) COLLECTOR BOX TUBE (GREEN) 0 COLLECTOR BOX EXTENSION TUBE BOX 0 DRAIN TUBE (BLUE) BOX COLLECTOR BOX TUBE (PINK) TUBE (PINK) BOX TUBE (GREEN) BOX EXTENSION TUBE COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED) BOX DRAIN TUBE (BLUE & WHITE STRIPED) COLLECTOR BOX EXTENSION TUBE BOX EXTENSION TUBE INDUCER HOUSING DRAIN TUBE (VIOLET) ! TRAP © TRAP )R BOX EXTENSION DRAIN TUBE INDUCER HOUSING COUPLING DRAINTUBE(VIOLET) A94165 Fig.
c. Install cap and clamp housing drain connection tube was removed. d. Use inducer housing CONDENSATE on UPPER inducer where molded drain drain tube (violet label inducer condensate (1.) and Condensate Trap Located b. Connect Condensate 1. Remove 3 tubes connected to condensate trap. to 2. Remove trap from blower shelf by gently pushing inward and rotating trap. 3. Install casing hole filler cap (factory-supplied in loose parts bag) into blower shelf hole where trap was removed. and cut.
PLUG -- "J" BOX AUXILIARY -X/ CAP COLLECTOR BOX DRAIN TUBE (BLUE AND WHITE STRIPED) _ 0 O © CONDENSATE TRAP COLLECTC BOX EXTENSION DRAIN TUBE UCER HOUSING DRAIN TUBE (VIOLET) \ \\ \_-- COLLECTOR COLLECTOR BOX DRAIN TUBE (BLUE) BOX EXTE S,O O E DRAIN TUBE COUPLING _ COLLECTOR BOX TUBE (PINK) BLOWER SHELF AND INDUCER HOUSING FOR 040,060, AND 080 HEATING INPUT FURNACES RELOCATE TUBE BETWEEN %. A00215 Fig. 10 - Horizontal c. Determine d.
COMBUSTION INTAKE A 12-1N. (305 mm) MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH SHORT (5 TO 8 FT / 1.5 TO 2.4 M) VENT SYSTEMS TO REDUCE EXCESSIVE CONDENSATE DROPLETS FROM EXITING THE VENT PIPE. 30" (762 mm)MIN (146 mm) MAN1 SHUTOFF GAS VALVE ACCESS OPENING FOR TRAP DRAIN SEDIMENT TRAP CONDENSATE TRAP NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE FURNACE AND CONDENSATE TRAP WHEN A CONDENSING FURNACE IS INSTALLED ABOVE FINISHED CEILINGS. A93031 Fig.
COLLECTOR BOX DRAIN TUBE (BLUE) COLLECTOR BOX TUBE (GREEN) BOX EXTENSION PLUG COLLECTOR TUBE BOX TUBE (PINK) "J" BOX RELOCATED HERE _ATE TRAP COLLECTOR BOX DRAIN TUBE (BLUE AND WHITE STRIPED) INDUCER HOUSING DRAIN TUBE (VIOLET) COLLECTOR BOX EXTENSION TUBE AO0214 Fig. 13 - Horizontal PROPERTY codes may require condensate application NOTE: In Canada, NSCNGPIC NOTE: The a drain pan under installations Installation junction Failure death.
2. Inducer Housing a. Remove inducer Drain Tube factory-installed housing ' 1 cap and clamp from LOWER drain connection. t b. Remove and discard UPPER (molded) inducer housing drain tube which was previously connected to condensate trap. c. Install cap and clamp on UPPER inducer housing drain connection where molded drain tube was removed. d. Use inducer housing drain extension tube (violet label f. Clamp 3. Relief appropriate trap.
UNIT DAMAGE HAZARD This gas furnace provided that: may -The furnace is permanently piping, air filters, venting be used for construction heat installed with all electrical wiring, and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace.
Step 3--Hazardous Locations FURNACE FIRE, EXPLOSION, Improper location or explosion. INJURY OR DEATH or inadequate protection Failure to follow component life. HAZARD could CORROSION result in fire and Application • Laundry Furnace • Hobby provisions located for dilution in a confined or ventilation space without in reduced furnace cleaning products. solvents, special air.
• Spaces having at least 50 cubic feet per 1,000 Btuh may use the INDOOR COMBUSTION AIR, STANDARD or KNOWN AIR INFILTRATION METHOD. Outdoor Combustion Size openings c. TWO HORIZONTAL DUCTS require 1 square inch of free area per 2,000 Btuh (1,100 mm'-/kW) of combined input for all gas appliances in the space per Fig. 18 and Table 1. Air Method 1.
.4_ DUCTS---k To q OUTDOORS , 1 SQIN. PER 4000 // B H* CIRCULATING DUCTS ................ ......... [ "_'[i , i l l I I AIR VENT THROUGH II I I I i £c 1 SQ IN. A / I I PER2000 T /lIB BTUH* z_ r./) I VENT ___ _ _ I THROUGH ROOF I I I L_J MAX I FI_ (305mm) 1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL M 4o00 UNCONFINED SPACE INTERIOR HEATED SPACE O o o 6" MIN (152mm) (FRONT)0 1 SQ IN 1 SQ IN. PER 1000 BTUH* IN DOOR OR WALL TO OUTDOORS ( i SQ,N.
construction, additional methods described in Method INSTALLATION air MUST be provided using the the Outdoor Combustion Air NOTE: section. Unusually Construction tight with: construction is defined as or sealed have are a When and b. Doors and openable c. Other openings windows are weatherstripped are caulked or sealed. These wall panels, at penetrations and gas lines, etc.
jumper close short circuit. to connector MAY NOT Failure to follow unit operation. remove wire to avoid FURNACE Step 3--Installation UNIT and in Horizontal (OR COIL CASING WHEN USED) Applications OPERATE this COMBUSTIBLE FLOORING caution may result in intermittent The entire length of furnace MUST be supported when furnace is used in a horizontal position to ensure proper draining. When suspended, bottom brace supports sides and center blower shelf.
Table FURNACE CASING WIDTH 3 - Opening Dimension - In.
COMBUSTION-AIR (NON-DIRECT INTAKE VEN% COMBUSTION-AIR PiPE DIRECT VENT/2-PIPE CATION) ,,ALL SIZES) 3-IN. (76 mm) MINIMUM CLEARANCE TO ___ COMBUSTION-AIR INTAKE IS REQUIRED_ _ (NON-DIRECT VENT/1 -PIPE APPLiCATiON,) 3/8-1N. (10 mm) ROD ANGLE IRON OR EQL 5 3/4" (146 mm) ALTERNATE SUPPORT LOCATION 4qN. (102 mm) MIN B-IN. (203 mm) MAX (B) I (A) ROD LOCATION USING DIMPLE LOCATORS (SEE DIMENSIONAL DWG FOR LOCATIONS) 3/8-1N.
Table 4 - Filter Information AIR FILTER LOCATED FIRE FURNACE CASING HAZARD IN BLOWER COMPARTMENT FILTER SIZE - IN (mm) WIDTH A failure to follow injury, or death. Never connect this warning return-air could ducts Return-air duct connections upflow applications only. result in fire, personal to the back on furnace IN (mm) of the furnace.
Step 6--Bottom Closure Panel These furnaces are shipped with bottom enclosure panel installed in bottom return-air opening. This panel MUST be in place when side return air is used. To remove bottom closure panel, perform following: 1. Tilt or raise furnace and remove filler panel. (See Fig. 28.) 2 screws holding front 2. Rotate to release holding tabs. front 3. Remove 4. Reinstall filler panel downward bottom closure I panel. front filler panel | I | t and screws. 21 -iN.
nipple into lower end of tee. Capped nipple should level of gas controls. Place a ground joint union control manifold and manual gas shutoff valve. extend below between gas The gas supply pressure shall be within the maximum minimum inlet supply pressures marked on the rating plate the furnace burners ON and OFE (See Fig. 29.) Step 8--Electrical If local codes allow the use of a flexible gas appliance connector, always use a new listed connector.
COMBUSTION-AIR PIPEGROMMET _ UNUSED 1-3/4 -IN. (44 mm) DIAMETER GAS CONN. HOLE OMBUSTION -AIR PIPE )GAS _(__ _VENT GAS LINE ENTRY HOLE FILLER PLUG PIPE GAS LINE GROMMET VENT PIPE GROMMET NOTE: PIPE GROMMETS AND ENTRY HOLE FILLER PLUGS ARE INCLUDED IN FACTORY-SUPPLIED LOOSE PARTS BAG A05057 Fig. 30 - Typical Gas Pipe Arrangement .... .... -- NOTE 2 THREE.WIRE HEATING-ONLY .
Table 6UNIT SIZE VOLTSHERTZPHASE OPERATING VOLTAGE RANGE Electrical MAX UNIT AMPS Data UNIT AM PACITY'I" MIN WIRE SIZE MAX WIRE LENGTH FT (a):l: 44 (13.4) 37 (11.2) 44 (13.4) 38 (11.5) 29 (8.8) 36 (10.9) 28 (8.5) 040-08 / 024040 115--60--1 Max* 127 Min* 104 6.1 8.4 14 040-12 / 036040 115--60--1 127 104 7.3 10.0 14 060-08 060-12 / 024060 / 036060 115--60--1 127 104 127 104 8.4 9.8 14 115--60--1 6.1 7.1 060-16 / 048060 115--60--1 127 104 9.5 12.
3. Install electrical entry hole loose parts Bag) in unused filler plugs (factory-supplied power entry holes. (See Fig. shown in Fig. 31. The 24-v connection of field wiring. 34.) contains a 3-amp, automotive-type control. (See Fig. 36.) Any electrical installation,service, or maintenance ELECTRICAL SHOCK AND Failure to follow this warning and death, or property damage. FIRE HAZARD could result fuse located on furnace shorts of 24-v wiring during may cause fuse to blow.
Table ASTM SPECIFICATION (MARKED ON MATERIAL) 7 - Approved Combustion-Air and Vent Pipe, Fitting and Cement Materials MATERIAL PIPE FITTINGS SOLVENT CEMENT AND PRIMERS DESCRIPTION D1527 ABS Pipe -- -- Schedule-40 D1785 PVC Pipe -- -- Schedule-40 D2235 For ABS -- -- Solvent Cement For ABS D2241 PVC Pipe -- -- SDR-21 & SDR-26 D2466 PVC -- Fittings -- Schedule-40 D2468 ABS -- Fittings -- Schedule-40 D2564 For PVC -- -- Solvent Cement D2661 ABS Pipe Fittin
f+ ++o o M_ s_ _z m d_-> _- Zz ,_ u _ss _ z _- +_ _ ..... _o _z S:_:_ _-_ 0-!1" 4 < - uo _> _ _ z _ __ I- i <_ =_-'_o_ _88_=_o_oo _ < _ _ _8o g oo_%<_z _-+mm_oS_ _ <<_z_+_>> _uuu o u 8# 3Z ON "_ PRINTED C IRC IUT BO ARD | [ caw J A03229 Fig.
Multistory and common venting are prohibited. DIRECT VENT/2-PIPE SYSTEM (ALL SIZES) In a direct-vent (2-pipe) system, all air for combustion is taken directly from outdoor atmosphere, and all flue products are discharged to outdoor atmosphere. A factory accessory vent termination kit MUST be used in a direct vent (2-pipe) system. NON-DIRECT VENT/I-PIPE SYSTEM (SIZES 040 THROUGH 120 ONLY) FIRE AND EXPLOSION Failure to follow this warning could damage, personal injury, or death.
BLOWER TWINNING AND/OR COMPONENT TEST TERMINAL OFF-DELAY BLOWER OFF DELAY HUMIDIFIER TERMINAL (24-VAC 0.5 AMP MAX.) 24-V THERMOSTAT TERMINALS TRANSFORMER 24-VAC CONNECTIONS 3-AMP FUSE ob F_ DIAGNOSTIC LIGHT LED OPERATION & 115-VAC(L2) CONNECTIONS 4 II!IIW sEc2sEcl PL1 -LOW VOLTAGE MAIN HARNESS CONNECTOR Joe ............ )I-.. €DD SPARE-2 11 VACtL1! UNE PL2 HOTSURFAOE CO..EOTO FAN \ s\ / / VOLTAGE CONNECTION \ IGNITER & INDUCER EAC-1 TERMINAL (1 15-VAC 1.0 AMP MAX.) _J A02142 Fig.
may require removal of the coupling for easier installation of the inducer outlet restrictor. UNIT MAY NOT OPERATE Failure to combustion, follow this caution may flame disturbance, or flame result in incomplete sense lockout. When installing combustion air and vent system of short pipe length, the smallest allowable pipe diameter must be used. NOTE: furnace casing A 2-in. casing. (51 mm) Make diameter pipe all pipe diameter must transitions be used outside within furnace per Fig. 41.
A ARF.
H 25-24-65-2 [_ VENTTERMINAL Item \\ Clearance A Clearance above anticipated B snow Clearance C Clearance D Vertical grade, or door clearance that to a ventilated deck, Clearance to an unventilated F Clearance to an outside G Clearance to an inside H Clearance to each may balcony, or be opened soffit located extended regulator regulator above assembly Clearance to a mechanical Clearance under M Clearance to each below terminal vent outlet air supply a
Table 10 - Maximum Allowable Exposed in Winter FURNACE WINTER DESIGN TEMPERATURE SIZE - Ft. (M) With and Without Insulation Ambient* MAX PIPE DIAMETER WITHOUT INSULATION WITH 3/8-1N. (10 mm) OR THICKER INSULATIONI- °F (°C) IN (mm) FT (a) FT (a) 1.5 (38) 51 (16) 70 (21) 0 (-18) 1.5 (38) 28 (9) 70 (21) 1.
NOTE: Select 1 vent pipe connection 1 combustion-air pipe and NOTE: Select connection. ! vent pipe connection 1 combustion-air pipe VENT and connection. PIPE General AIR Furnace vent connection must be attached as shown in Fig. 39. COMBUSTION-AIR _ COMBUSTION-AIR VENT CARBON DAMAGE COMBUSTIONAIR z UPFLOW POISONING Failure to follow this warning personal injury, or death.
Table ALTITUDE FT (i) UNIT SIZE (BTUH) 11 - Maximum DIRECT VENT (2-PIPE) TERMINATION TYPE Allowable ONLY 40,000 60,000 80,000 O to 2000 (O to 610) 100,000 120,000 140,000 ALTITUDE UNIT SIZE FT (i) (BTUH) 40,000 60,000 80,000 2001 to 3000 (610 to 914) 100,000 120,000 140,000 See notes at end 2 Pipe or 2-in. (51 mm) Concentric PIPE DIA IN. (mm)* 1 2 3 4 5 6 1 (25) 5 (1.5) NA NA NA NA NA 1-1/2 (38) 1-1/2 (38) 7O (21.3) 70 (21.3) 65 (19.8) 60 (18.3) 60 (18.
Table ALTITUDE FT (i) UNIT SIZE (BTUH) 40,000 60,000 80,000 3001 to 4000 (914 to 1219) 100,000 120,000 140,000 ALTITUDE UNIT SIZE FT (M) (BTUH) 40,000 60,000 80,000 4001 to 50005 (1219 to 1524) 100,000 120,000 140,000 See notes at end ll--Maximum Allowable DIRECT VENT (2-PIPE) TERMINATION TYPE ONLY PIPE DIA IN (mm)* Pipe Length - Ft. (M) (Continued) NON-DIRECT VENT (1-PIPE) ONLY NUMBER OF 90 ° ELBOWS PIPE DIA IN (mm)* 1 2 3 4 5 6 59 (18.0) 54 (16.5) 49 (14.
Table ALTITUDE FT (i) UNIT SIZE (BTUH) 40,000 60,000 80,000 5001 to 60005 (1524 to 1829) 100,000 120,000 140,000 ALTITUDE UNIT SIZE FT (i) (BTUH) 40,000 60,000 80,000 6001 to 70005 (1829 to 2134) 100,000 120,000 140,000 ll--Maximum Allowable DIRECT VENT (2-PIPE) TERMINATION TYPE ONLY Pipe Length - Ft. (M) (Continued) NON-DIRECT VENT (1-PIPE) ONLY PIPE DIA IN. (mm)* NUMBER OF 90 ° ELBOWS PIPE DIA IN. (mm)* 1 2 3 4 5 6 52 (15.8) 47 (14.3) 42 (12.8) 40 (12.2) 35 (10.
Table ALTITUDE FT (i) UNIT SIZE (BTUH) ll--Maximum DIRECT VENT (2-PIPE) TERMINATION TYPE 40,000 60,000 80,000 7001 to 8000:[: (2134 to 2438) 100,000 120,000 Allowable ONLY PIPE DIA IN. (mm)* Pipe Length - Ft. (M) (Continued) NON-DIRECT VENT (1-PIPE) ONLY PIPE DIA IN. (mm)* 1 2 3 4 5 6 1-1/2 (38) 49 (14.9) 44 (13.4) 39 (11.9) 34 33 28 (10.4) (10.1) 65 (19.8) 63 (19.2) 62 (18.9) 60 (18.3) 59 (18.0) 2 Pipe or 2-in. (51 mm) Concentric 1-1/2 (38) 2 (51) 2 (51) 66 (20.
Table ALTITUDE FT (i) UNIT SIZE (BTUH) ll--Maximum Allowable DIRECT VENT (2-PIPE) TERMINATION TYPE Pipe Length - Ft. (M) (Continued) NON-DIRECT VENT (1-PIPE) ONLY ONLY PIPE DIA IN. (mm)* NUMBER OF 90 ° ELBOWS PIPE DIA IN. (mm)* 1 2 3 4 5 6 37 (11.3) 32 (9.8) 27 (8.2) 25 (7.6) 20 (6.1) 2 Pipe or 2-in. (51 ram) 1-1/2 (38) 1-1/2 (38) 42 (12.8) Concentric 2 (51) 2 (51) 57 (17.4) 55 (16.8) 53 (16.2) 51 (15.5) 49 (14.9) 47 (14.3) 60,000 2 Pipe or 2-in.
COMBUSTION 3/8 ID TUBE INTAKE \ -- _'_ _ L--_--_--_--_m FURNACE _ L__ AIR HOUSING BURNER ./- r_ _J BO× _ [q r i _"_ [--_ --__ COMBUSTION-AIR PIPE (DIRECT ............ j_# VENT/2 PIPE) :_J_]__ D31L 6 i- HORIZONTAL NOT IN SECTION ii I E_ EDI TRANSITION IN VERTICAL SECTION _ IN TRAP JI _ [ _ I _ _ ,o_ COMBUSTION-AIR PIPE (NON-DIRECT VENT/I-PIPE) [ o TO OPEN DRAIN A05093 A93034 Fig. 41 - Combustion-Air Transition Location and Vent Pipe Diameter and Elbow Fig.
Roo_ _ rmlnafion (Preferred) Con c_mtric V#nt and Combustion Roo f T#rruination (preferred} ¢4 Vertical separation between combustion air and vent Air ............ ................... Ix,0ZI. w 24 in above roof of A05090 Fig. 44 - Combustion Air and Vent Pipe Termination Roof Termination 12 in 24 in (610ram) (305ram) abov_ Vent (2-pipe) System (Preferred) .... Maintain above highest anticipated snow level maximum of for Direct I"'-. " ' ""- , roof .. .....:i ......
EXAMPLE: UNIT DAMAGE Failure to follow component damage. Vent pipe must housing internal condensate this caution be installed stop. Clamp may result in unit and fully seated against inducer must be tightened to prevent any leakage. 6. Install casing hole filler parts bag) in unused Attachment Furnaces An 080-12 size furnace located in Indianapolis, elevation 650 ft. (198 M) above sea level, could be installed as either a direct vent/2-pipe system that requires 3 elbows and 32 ft. (9.
Table 13 - Vent Termination DIRECT VENT (2-PIPE) TERMINATION KIT Kit for Direct TERMINATION Vent/2-Pipe DIAM. OF COMBUSTION AIR AND VENT PIPES - IN (mm) SYSTEM 2-in. (51 ram) Concentric Vent Kit Single Penetration of Wall or Roof 3-in. (76 ram)Concentric Vent Kit Single Penetration of Wall or Roof 2-in. (51 ram)Termination Bracket Kit 2-Pipe Termination System 3-in. (76 ram) Termination Bracket Kit 2-Pipe Termination System 4.
Furnace 3.2 to condensate 4.5. Due is mildly acidic, typically in the pH range to corrosive nature of this condensate, condensate pH neutralizing local authorities to determine filter may be desired. Check if a pH neutralizer is required. of a CONDENSATE with APPLICATION The furnace, drained supplied A/C, and humidifier together. The A/C trap prior to the may be combined and drain must have an external, furnace drain connection.
A99118 Fig. 48 - Inducer Step 2--Prime Housing Condensate Drain Tube Cap Trap With Water A99119 Fig. 49 - Filling UNIT Failure MAY NOT to Condensate Trap OPERATE follow this caution may result in Step 4---Sequence intermittent of Operation unit operation. Condensate trap must be PRIMED or proper draining may not occur. The condensate trap has 2 internal chambers which can ONLY be primed by pouring water into the inducer drain side of condensate trap.
The wall thermostat The furnace control switch contacts "calls for heat," closing the R to W circuit. performs a self-check, verifies the pressure PRS are open, and starts a. Inducer Prepurge Period- the inducer motor IDM. As the inducer motor IDM comes up to speed, the pressure switch contacts close to begin a 15-second prepurge period. stop, and the furnace continue operating on additional 90 seconds. Jumper Y/Y2 to DHUM to reduce the cooling off-delay to 5 seconds. (See Fig. 31.) b.
THERMIDISTAT SINGLE-STAGE FURNACE SINGLE-SPEED AIR CONDITIONER THERMIDISTAT SINGLE-STAGE FURNACE SINGLE-SPEED HEAT PUMP N/A RVS COOLING N/A N/A [_ HEAT STAGE 1 COOL STAGE 1 24 VAC FAN [_ HOT [_ DEHUMIDIFY 24 VAC HEAT H EA Z / _ cOoQMLpSTA sGoER 1) 24 VAC [_ COMM STAGE 2 (FURNACE) FAN [_ HOT [_ E2_ DEHUMIDIFY [_ 24 VAC COMM [_ HUM [] HUMIDIFY _ HUM,D,F,ER _ i [_ (24 HUMIDIFY N/A _ VAC) [_ HUM HUM'D'F'ER _ i (24 VAC) [_ o tooo N/A [_ °S_E_#°° #_ /_ OUTDOOR SE
DUAL FUEL SINGLE-STAGE THERMOSTAT RVS SINGLE-SPEED FURNACE HEAT DUAL PUMP COOLING RVS N/A FUEL SINGLE-STAGE THERMOSTAT TWO-SPEED FURNACE COOLING HEAT PUMP [_ [_ HEAT/COOL STAGE 1 (COMPRESSOR LO) HEAT STAGE (FURNACE) HEAT/COOL STAGE (COMPRESSOR) 24 VAC 24 VAC 2 HEAT FAN [_ HOT [_ COMM N/A RVS SENSING OUTDOOR STAGE 3 [_ (FURNACE) HEAT/COOL STAGE (COMPRESSOR 1 24 VAC [_ 24 VAC [_ 2 HI) FAN [_ HOT [_ COMM N/A [_ [_ RVS [_ SENSING [_ °s_.
NOTES 1. Heat pump MUST 2. Refer to outdoor 3. Select the "ZONE" 4. Outdoor have a high pressure equipment switch Installation position Air Temperature for additional heat pump must be attached should be set in OFF 6. Dip switch No. 1 on Thermidistat should be set in ON position 7. Dip switch No. 2 on Thermidistat should be set in OFF 8. Dip switch No. 2 on Thermidistat should be set in ON position Option 11. The RVS Sensing 12. DO NOT No.
Table 14 - Model 58MXB Orifice Size and Manifold For Use with 040 through (Tabulated D _" (n ::5 1000 Ft. (305 M) Above Sea Level) * GRAVITY OF NATURAL GAS 3.7 43 3.8 42 3.2 42 3.3 42 3.4 3.5 43 3.6 43 3.7 43 3.8 42 3.2 900 44 3.7 43 3.4 43 3.5 43 3.6 43 3.7 o 925 44 3.5 44 3.7 44 3.8 43 3.4 43 3.5 To 950 44 3.4 44 3.5 44 3.6 44 3.7 44 3.8 2000 975 44 3.2 44 3.3 44 3.4 44 3.5 44 3.6 1000 45 3.7 45 3.8 44 3.2 44 3.4 44 3.
TABLE 13--Model 58MXB Orifice Size and Manifold Pressure for Correct Input (Continued) for Use With 040 Through 120 Size Furnaces Only (Tabulated Data Based on 20,000 Btuh per Burner, Derated 2 Percent for Each 1000 Ft.
Table 13--Model 58MXB Orifice Size and Manifold Pressure for Correct Input (Continued) For Use with 040 through 120 Size Furnaces Only (Tabulated Data Based on 20,000 Btuh per Burner, Derated 2% for Each 1000 Ft.
Table 15 - Model 58MXB Orifice Size and Manifold For Use with (Tabulated ALTITUDE RANGE Ft (i) -o 0 To 2000 (0 to 610) 0% derate -o ALTITUDE RANGE Ft (i) U.S.A. Altitudes 2001 to 3000 (810 to <. 914) or Canada Altitudes 2001 to 4500 (810 to 1372) 5% derate ALTITUDE RANGE Ft (i) >, • _. "_ 3001 to 4000 (914 to 1219) 7% derate Data Based on 23,000 Btuh per Burne_; Pressure 140 Size Furnaces Derated for Correct 2% for Each 1000 SPECIFIC Input Only Ft.
Table 14--Model 58MXB Orifice Size and Manifold Pressure for Correct Input (Continued) for Use With 140 Size Furnaces Only (Tabulated Data Based on 23,000 Btuh per Burner, Derated 2% for Each 1000 Ft. (305 M) Above Sea Level) * ALTITUDE RANGE Ft (i) _>, 725 41 3.6 41 3.7 41 3.8 40 3.6 40 3.8 750 42 3.7 42 3.8 41 3.6 41 3.7 41 3.8 775 42 3.5 42 3.6 42 3.7 42 3.8 41 3.6 800 42 3.3 42 3.4 42 3.5 42 3.6 42 3.7 825 43 3.7 42 3.2 42 3.3 42 3.4 42 3.
COMPONENT TEST NOTE: The fi_rnace control component test allows all components to run for a short time; except the gas valve and humidifier terminal HUM are not energized for safety reasons. The EAC-1 terminal is energized when the blower is energized. This feature helps diagnose a system problem in case of a component failure. The component test feature will not operate if any thermostat signal is present ant the control and not until all time delays are completed. 1.
BURNER NOTE: If orifice hole appears damaged or it is suspected to have been redrilled, check orifice hole with a numbered drill bit of correct size. Never aligned orifice an orifice. hole is essential ONiO['[" % "NPT redrill A burr-free for proper Switch flame Regulator Inlet Under and BURNER squarely characteristics. Seal Cap Cap I/8 NPT Inlet Pressure 'Yap !/," NPT Outlet MANIFOLD I/8" NPT Manitbld Pressure Tap A89020 A07536 Fig. 57 - Redundant Automatic Gas Control Fig.
f. Measure time (in sec) for gas meter 1 revolution. g. Refer to Table Table to dial to complete SIZE OF TEST DIAL SECONDS FOR 1 REVOLUTION 17 for cu fl of gas per hr.
Table 18 - Speed COLOR SPEED FACTORY SHIPPED CONNECTION Black High Cool Yellow (When Present) Medium High Spare Blue Medium Low Heat Red Low Fan White Common Table 19 - Blower THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED Selector HOOK-AROUND VO LT/AM M ETER COM Off Delay Jumper Positions PINS 1 AND 2 2 AND 3 3 AND 4 4AND 5 Time (in sec) 90 120 150 180 Step 6--Check Safety 10TURNS Controls FROM UNIT 24-VOLT TERMINAL BLOCK This section covers the safety control
CHECKLIST_DIRECT LOAD VENT CALCULATION (2-PIPE) INSTALLATION Condensate Drain Heating Load (Btuh) Unit Level or Pitched Forward Cooling Load (Btuh) Internal Tubing Connections Free of Kinks and Traps Furnace Model Selection COMBUSTION Termination AIR AND VENT External Drain Connection Leak Tight and sloped PIPING Location Condensate Trap Primed before Start-Up Roof or Sidewall Heat Tape Installed if Required Termination CHECKLIST--START-UP Kit -- 2 Pipe or Concentric (;as Input Rate