Table 63 — Testing Circuit A Oil Solenoid
LEGEND FOR FIG. 63-65
MODE
(Red LED)
SUB-MODE
KEYPAD
ENTRY
ITEM
DISPLAY
EXPANSION
VALUE
DESCRIPTION
(Units)
COMMENT
SERVICE TEST
Service Test Mode
TEST Manual Sequence
QUIC Q.REQ
PASS WORD
Password may be required
0111
Each will lock in the next
digit. If 0111 is not the password,
use the arrow keys to change the
password digit and press
when correct.
Q.REQ
Returns to the original field
OFF
OFF
OFF will flash
ON
The Enable/Off/Remote Contact
switch must be in the OFF
position.
Q.REQ
EXV.A
Press 15 times.
OLS.A Oil Solenoid Cap.A
OFF
OFF
OFF will flash
ON
ON
OLS.A will turn on.
ON
1 will flash
OFF
OFF
OLS.A will turn off.
ALM Alarm HGBP Hot Gas Bypass
ALT Alert LWT Leaving Water Temperature
CB Circuit Breaker MBB Main Base Board
CLR Clear MLV Minimum Load Valve
CPM Compressor Protection Module MM Low Ambient Temperature Head Pressure Control
CWFS Chilled Water Flow Switch OAT Outdoor Air Temperature
DPT Discharge Pressure and Temperature PMP Pump
ECEXV Economizer Electronic Expansion Valve SGT Saturated Gas Temperature
ECTA Economizer A Temp SHD Loadshed
EMM Energy Management Module SPT Space Temperature
EXV Electronic Expansion Valve TB Terminal Block
FC Fuse UPC Universal Protocol Converter/BacNet
Communications OptionFIOP Factory-Installed Option