Operating instructions

137
APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
ITEM EXPANSION UNITS RANGE COMMENT DEFAULT CCN TABLE CCN POINT PAGE NO.
RSET RESET, DEMAND LIMIT, MASTER/SLAVE
CRST Cooling Reset Type No Reset
Out Air Temp
Delta T Temp
4-20 mA Input
Space Temp
NO RESET USER cr_sel 38,40,42,69
HRST Heating Reset Type No Reset
Out Air Temp
Delta T Temp
4-20 mA Input
NO RESET USER hr_sel
DMDC Demand Limit Select None
Switch
4-20 mA Input
NONE USER lim_sel 42,43,44,69
DMMX mA for 100% Demand Limit XX.X (mA) 0.0 USER lim_mx 44,45
DMZE mA for 0% Demand Limit XX.X (mA) 10.0 USER lim_ze 44,45
MSSL Master/Slave Select Disable
Master
Slave
DISABLE MST_SLV ms_sel 32,34-
37,70,95,
99,100
SLVA Slave Address XXX 1-236 2 MST_SLV slv_addr 32,34-37
LLBL Lead/Lag Balance Select Always Lead
Lag if Fail
Runtime Sel
Always
Lead
MST_SLV ll_bal 32,34-37,
68
LLBD Lead/Lag Balance Delta XXX (hours) 40-400 168 MST_SLV ll_bal_d 32,34-37,68
LLDY Lead/Lag Delay XX (minutes) 2-30 10 MST_SLV lsrt_tim 32,34-37,68
LL.ER Start if Error Higher XX.X
(deg F/deg C)
3-18 4 MST_SLV start_dt 32,34-37
LAG.M Lag Minimum Running Time XXX
(min)
0-150 0 MST_SLV lag_mini 32,34-37
LAGP Lag Unit Pump Select OFF if U stp
ON if U stp
OFF if U stp MST_SLV lag_pump 32,34-37,68
LPUL Lead Pulldown Time XX (minutes) 0-60 0 MST_SLV lead_pul 34-37,67,68
SERI Chillers in Series NO/YES NO MST_SLV ll_serie 32,34-37