Operating instructions

21
CONFIGURATION
Touch Pilot™ Operation Configuration
Tables
The Touch Pilot display operation is controlled by
configuration information entered in the following configura-
tion tables. These tables are accessible by using Network
Service Tool or ComfortVIEW™ software. The tables are the
CtrlID (Controller Identification) configuration table and the
USERCONF (User Configuration) table. See Tables 15 and 16.
NOTE: Always perform an Upload to obtain the latest config-
uration before making configuration table changes.
Table 15 — Touch Pilot Controller Identification Configuration Table
Table 16 — Touch Pilot™ User Configuration (USERCONF) Table
Fig. 16 — ComfortLink™ CCN Communication Wiring
CONTROLLER ID DATA BLOCK NO. VALUE AND RANGE QUALIFIERS
Device Name 1
CHILLDSP
8 character Name field
Default
Optional
Local address 2 115 Default
Bus number 2 0 Default
Device (driver) type 2
0 = Non-bridge
3 = Broadcast Acknowledger
Default
Optional
Primary baud rate 3 38400 Default
Secondary baud rate 3 38400 Fixed
Device description 4
Global Chiller Display
24 character text field
Default
Optional
Device location 4
(Blank)
24 character text field
Default
Optional
Software part number 4 CESR-131363-01 Fixed
Model number 4 (Blank) Fixed
Serial number 4 (Blank) Fixed
Reference number 4 Version 1.0 Fixed
Broadcast address processing list (primary) 5
241-251, 254, 255 enabled
241-255 enabled/disabled
Defaults
Optional
Broadcast address processing list (secondary) 5 none Not applicable
DESCRIPTION LIMITS UNITS NAME DEFAULT
Backlight always on? No - Yes BACKLITE No
Full access password 0 - 9999 PSWDFULL 3333
Limited access password 0 - 9999 PSWDLMTD 2222
Active language 0 - 1 ACTLANG 0
Time format 0 - 1 TIMEFMT 0
Date format 0 - 2 DATEFMT 0
Units base US - Metric UNITBASE US
Contrast control Manual - Auto CONTRAST Auto
Network mode 0 - 1 NETWORK 0
Network settings
Alarm acknowledger No - Yes ALARMACK No
Broadcast acknowledger No - Yes BROADACK No
Equipment CCN address
Bus number 0 - 239 EQUIPBUS 0
Element number 1 - 239 EQUIPELE 1
Control variables
Equipment status (Not Used) Name char 8 EQSTATUS NOT USED
Equipment start/stop (Not Used) Name char 8 STARSTOP NOT USED
Alarm status (Not Used) Name char 8 ALSTATUS NOT USED
Alarm reset (Not Used) Name char 8 ALRESET NOT USED