Table 26 — Cooling Set Point Selection Touch Pilot™ Parameters
Table 27 — Cooling Set Point Selection Navigator™ Parameters
SET POINT
CONFIGURATION
(Setpoint Select)
ICE MODE
ENABLE
(ice_cnfg)
DUAL SET
POINT INPUT
(SETP_SW)
ICE DONE INPUT
(ICE_SW)
TIME
SCHEDULE 2
ACTIVE
SET POINT
0
(Auto)
NO
Occupied Cooling Setpoint 1
Unoccupied Cooling Setpoint 2
YES
Open Unoccupied Cooling Ice Setpoint
Closed Unoccupied Cooling Setpoint 2
Occupied Cooling Setpoint 1
1 (Setp 1) Cooling Setpoint 1
2 (Setp 2) Cooling Setpoint 2
3 (4-20 mA) 4 to 20 mA Input
4 (Setp Sw)
NO
Open Cooling Setpoint 1
Closed Cooling Setpoint 2
YES
Open Cooling Setpoint 1
Closed Open Cooling Ice Setpoint
Closed Closed Cooling Setpoint 2
PARAMETER STATUS
ACTIVE
SET POINT
Control Method
(OPER)
Heat/Cool
Select (HC.SE)
Setpoint
Select (SP.SE)
Ice Mode
Enable (ICE.M)
Ice Done
(ICE.D)
Dual Setpoint
Switch (DUAL)
Setpoint
Occupied
(SP.OC)
LOCAL COOL
Setpoint Occ Occupied CSP.1
Setpoint Occ Unoccupied CSP.2
Setpoint Occ Enable Open Unoccupied CSP.3
Setpoint 1 CSP.1
Setpoint 2 CSP.2
4-20mA Setp 4_20mA
Enable Open Closed CSP.3
Enable Closed Closed CSP.2
Open CSP.1
Dual Setp Sw Closed CSP.2
CCN COOL
Occupied CSP.1
Unoccupied CSP.2
0
10
20
30
40
50
60
70
80
90
02 468 10 12 14 16 18 20
mA Signal
Set Point
Max LWT
Min LWT, Cooler Fluid Type = 1, FLUD=Brine
Min LWT, Cooler Fluid Type = 1, FLUD=Water
Fig. 20 — 4 to 20 mA Set Point Control