Specifications

96
APPENDIX B — CCN TABLES (cont)
CCN CONFIGURATION TABLES — OPTIONS1 (Options 1 Configuration)
CCN CONFIGURATION TABLES — OPTIONS2 (Options 2 Configuration)
CCN CONFIGURATION TABLES — SCHEDOVR (Timed Override Setup)
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
Cooler Fluid 1 = Water
2 = Med. Brine
1FLUIDTYP
Minimum Load Vlv Select No/Yes No MLV_FLG
CSB Board Enable Dsable/Enable Enable CSB_ENA
Cooler Pump Control Off/On Off CPC
Cooler Pump 1 Enable No/Yes No PMP1_ENA
Cooler Pump 2 Enable No/Yes No PMP2_ENA
Cooler Pmp Periodic Strt No/Yes No PUMP_PST
Cooler Pump Select 0 = Automatic, 1 =
Pump 1, 2 = Pump 2
0 PMP_SLCT
Cooler Pump Shutdown Dly 0 to 10 1 minutes PUMP_DLY
Pump Changeover Hours 10 to 2000 100 hours PMP_DLTA
EMM Module Installed No/Yes No EMM_BRD
Cnd HX Typ: 0=RTPF 1=MCHX 0/1 1 COILTYPE
EXV MOP Set Point nn.n 50 °F MOP_SP
Config Approach Setpoint nn.n 9.0 °F IAPPROSP
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
Control Method 0 = Switch
2 = Occupancy
3 = CCN
0 CONTROL
Loading Sequence Select 1 = Equal Loading
2 = Staged Loading
1 SEQ_TYP
Lead/Lag Circuit Select 1 = Automatic
2 = Circuit A Leads
3 = Circuit B Leads
1 LEAD_TYP
Cooling Setpoint Select 0 = Single
1 = Dual, remote switch controlled
2 = Dual CCN occupancy
3 = 4-20 mA input
0 CLSP_TYP
Ramp Load Select Enable/Dsable Enable RAMP_EBL
Heat Cool Select Cool/Heat Cool HEATCOOL
High LCW Alert Limit 2 to 60 60.0 F LCW_LMT
Minutes off time 0 to 15 0 min DELAY
Deadband Multiplier 1.0 to 4.0 1.0 Z_GAIN
Ice Mode Enable Enable/Dsable Dsable ICE_CNFG
Low Sound Mode Select 0 = Disabled
1 = Fan only
2 = Capacity/Fans
0LS_MODE
Low Sound Start Time 00:00 to 23:59 00:00 LS_START
Low Sound End Time 00:00 to 23:59 00:00 LS_END
Low Sound Capacity Limit 0 to 100 100 % LS_LIMIT
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
Schedule Number 0 to 99 1 SCHEDNUM
Override Time Limit 0 to 4 0 hours OTL
Timed Override Hours 0 to 4 0 hours OVR_EXT
Timed Override No/Yes No TIMEOVER