30RAP010-060 Air-Cooled Chillers with COMFORTLINK™ Controls AQUASNAP® Controls, Start-Up, Operation, Service, and Troubleshooting CONTENTS Page SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . .2 GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18 Conventions Used in this Manual. . . . . . . . . . . . . . . . . . . .3 Basic Controls Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 CONTROLS. . . . . . . . . . . . . . . . . .
CONTENTS (cont) WARNING Page Complete Unit Stoppage and Restart . . . . . . . . . . . . . . 64 • GENERAL POWER FAILURE • UNIT ENABLE-OFF-REMOTE CONTACT SWITCH IS OFF • CHILLED FLUID PROOF-OF-FLOW SWITCH OPEN • OPEN 24-V CONTROL CIRCUIT BREAKERS • COOLING LOAD SATISFIED • THERMISTOR FAILURE • LOW SATURATED SUCTION • COMPRESSOR SAFETIES Alarms and Alerts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 APPENDIX A — DISPLAY TABLES . . . . . . . . . . . . . .
Control System for 30RAP units. The display has up and down arrow keys, an ENTER key, and an ESCAPE key. These keys are used to navigate through the different levels of the display structure. Press the ESCAPE key until the highest operating level is displayed to move through the top 11 mode levels indicated by LEDs on the left side of the display. See Fig. 1 and Tables 2-14.
the Navigator module, press the ESCAPE key until the display reads, “Select a menu item.” Using the arrow keys move to the Configuration mode. Press ENTER to obtain access to this mode. The display will read: ACCESSORY NAVIGATOR™ DISPLAY MODULE — The Navigator module provides a mobile user interface to the ComfortLink™ control system, which is only available as a field-installed accessory. The display has up and down arrow keys, an ENTER key, and an ESCAPE key.
Table 2 — Scrolling Marquee Display Menu Structure* MODE RUN STATUS Auto View of Run Status (VIEW) Unit Run Hour and Start (RUN) SERVICE TEST TEMPERATURES PRESSURES SET POINTS INPUTS OUTPUTS CONFIGURATION TIME CLOCK OPERATING MODES ALARMS Service Test Mode (TEST) Ent and Leave Unit Temps (UNIT) Pressures Ckt A (PRC.A) Cooling Setpoints (COOL) General Inputs (GEN.I) General Outputs (GEN.
Table 3 — Run Status Mode and Sub-Mode Directory SUB-MODE KEYPAD ENTRY ITEM DISPLAY VIEW ENTER EWT XXX.X F ENTERING FLUID TEMP LWT XXX.X F LEAVING FLUID TEMP SETP XXX.X F ACTIVE SETPOINT CTPT XXX.X F CONTROL POINT LOD.F XXX LOAD/UNLOAD FACTOR STAT X CONTROL MODE SUB-ITEM DISPLAY SUB-ITEM DISPLAY LD.
Table 3 — Run Status Mode and Sub-Mode Directory (cont) SUB-MODE KEYPAD ENTRY ITEM PM (cont) DISPLAY SUB-ITEM DISPLAY SUB-ITEM DISPLAY PMDT P.1.M0 MM/DD/YY HH:MM P.1.M1 MM/DD/YY HH:MM P.1.M2 MM/DD/YY HH:MM P.1.M3 MM/DD/YY HH:MM P.1.M4 MM/DD/YY HH:MM P.2.M0 MM/DD/YY HH:MM P.2.M1 MM/DD/YY HH:MM P.2.M2 MM/DD/YY HH:MM P.2.M3 MM/DD/YY HH:MM P.2.M4 MM/DD/YY HH:MM STRN ENTER STRAINER MAINTENANCE SI.ST XXXX HRS STRAINER SRVC INTERVAL S.T.DN XXXX HRS STRAINER SRVC COUNTDOWN S.T.
Table 4 — Service Test Mode and Sub-Mode Directory SUB-MODE TEST KEYPAD ENTRY ITEM ITEM EXPANSION SERVICE TEST MODE DISPLAY ON/OFF ENTER OUTS COMMENT To Enable Service Test Mode, move Enable/Off/Remote Contact switch to OFF. Change TEST to ON. Move switch to ENABLE. OUTPUTS AND PUMPS ENTER EXV.A 0 to 100% EXV A % OPEN EXV.
Table 5 — Temperature Mode and Sub-Mode Directory SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION ENT AND LEAVE UNIT TEMPS ENTER CEWT XXX.X F COOLER ENTERING FLUID CLWT XXX.X F COOLER LEAVING FLUID OAT XXX.X F OUTSIDE AIR TEMPERATURE SPT XXX.X F SPACE TEMPERATURE DLWT XXX.X F UNIT COMMENT LEAD/LAG LEAVING FLUID CIR.A TEMPERATURES CIRCUIT A ENTER SCT.A XXX.X F SATURATED CONDENSING TMP SST.A XXX.X F SATURATED SUCTION TEMP RGT.A XXX.X F COMPR RETURN GAS TEMP D.
Table 8 — Inputs Mode and Sub-Mode Directory SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION GENERAL INPUTS ENTER STST STRT/STOP START/STOP SWITCH FLOW ON/OFF COOLER FLOW SWITCH PM.F.1 OPEN/CLSE COOLER PUMP 1 INTERLOCK PM.F.2 OPEN/CLSE COOLER PUMP 2 INTERLOCK HT.
Table 9 — Outputs Mode and Sub-Mode Directory (cont) SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION OUTPUTS CIRCUIT A EXV ENTER EXV.A 0 to 100% EXV % OPEN APPR ON/OFF CIRCUIT A APPROACH A.EXV AP.SP APPROACH SETPOINT X.SH.R SH RESET AT MAX UNL-DIG S.SH.R DIGLOAD TO START SH RST SH_R AMOUNT OF SH RESET OVR.A EXVA OVERRIDE SPH.A SUCTION SUPERHEAT TEMP ASH.S ACTIVE SUPERHEAT SETPT AMP.S ACTIVE MOP SETPT PLM.A CIR A EXV POSITION LIMIT SPR.1 COMMENT SPARE 1 TEMPERATURE B.
Table 10 — Configuration Mode and Sub-Mode Directory SUB-MODE KEYPAD ENTRY UNIT ENTER ITEM EXPANSION ITEM DISPLAY COMMENT SIZE XX UNIT SIZE SZA.1 XX COMPRESSOR A1 SIZE Unit Dependent SZA.2 XX COMPRESSOR A2 SIZE Unit Dependent SZA.3 XX COMPRESSOR A3 SIZE Unit Dependent SZA.4 XX COMPRESSOR A4 SIZE Unit Dependent SZB.1 XX COMPRESSOR B1 SIZE Unit Dependent SZB.2 XX COMPRESSOR B2 SIZE Unit Dependent SZB.3 XX COMPRESSOR B3 SIZE Unit Dependent SZB.
Table 10 — Configuration Mode and Sub-Mode Directory (cont) SUB-MODE KEYPAD ENTRY ITEM DISPLAY CTRL X ITEM EXPANSION UNIT OPTIONS 2 CONTROLS CONTROL METHOD LOAD X LOADING SEQUENCE SELECT LLCS X LEAD/LAG CIRCUIT SELECT LCWT XX.X F HIGH LCW ALERT LIMIT DELY XX MINUTES OFF TIME Default: 0 Minutes Range: 0 to 15 Minutes ICE.M ENBL/DSBL ICE MODE ENABLE Default: Disable LS.MD X LOW SOUND MODE SELECT LS.ST 00:00 LOW SOUND START TIME Default: 00:00 LS.
Table 10 — Configuration Mode and Sub-Mode Directory (cont) SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION CIR A EXV CONFIGURATION ENTER STR.A XXX EXV CIRC.A START POS Range: 0 - 100 Default: 30 MIN.A XXX EXV CIRC.A MIN POSITION Range: 0 - 100 Default: 8 RNG.A XXXXX EXVA STEPS IN RANGE SPD.A XXXXX EXVA STEPS PER SECOND POF.A XXX EXVA FAIL POSITION IN % MIN.A XXXXX EXVA MINIMUM STEPS Range: 0 - 65535 Default: 0 MAX.A XXXXX EXVA MAXIMUM STEPS Range: 0 - 65535 Default: * OVR.
Table 10 — Configuration Mode and Sub-Mode Directory (cont) SUB-MODE KEYPAD ENTRY ITEM DISPLAY CRST X ITEM EXPANSION RESET COOL TEMP COOLING RESET TYPE MA.DG XX.X F 4-20 - DEGREES RESET RM.NO XXX.X F REMOTE - NO RESET TEMP Default: 125F (51.7C) Range: 0° to 125F RM.F XXX.X F REMOTE - FULL RESET TEMP Default: 0.0F (-17.8C) Range: 0 to 125F RM.DG XX.X F REMOTE - DEGREES RESET Default: 0.0F Range: –30 to 30F RT.NO XXX.X F RETURN - NO RESET TEMP Default: 10.0F (5.
Table 10 — Configuration Mode and Sub-Mode Directory (cont) SUB-MODE KEYPAD ENTRY ITEM DISPLAY ENTER T.D.BC ON/OFF CCN TIME/DATE BROADCAST OAT.B ON/OFF CCN OAT BROADCAST G.S.BC ON/OFF GLOBAL SCHEDULE BROADCAST BC.AK ON/OFF CCN BROADCAST ACK’ER BCST ITEM EXPANSION BROADCAST CONFIGURATION COMMENT Table 11 — Time Clock Mode and Sub-Mode Directory SUB-MODE KEYPAD ENTRY ITEM DISPLAY ENTER HH.MM XX.
Table 11 — Time Clock Mode and Sub-Mode Directory (cont) SUB-MODE KEYPAD ENTRY ITEM DISPLAY ENTER OVR.T X TIMED OVERRIDE HOURS Default: 0, Range 0-4 hours OVR.L X OVERRIDE TIME LIMIT Default: 0, Range 0-4 hours T.
Table 14 — Operating Modes MODE NO. ITEM EXPANSION DESCRIPTION 01 CSM CONTROLLING CHILLER Chillervisor System Manager (CSM) is controlling the chiller. 02 WSM CONTROLLING CHILLER Water System Manager (WSM) is controlling the chiller. 03 MASTER/SLAVE CONTROL Ramp load (pull-down) limiting in effect. In this mode, the rate at which leaving fluid temperature is dropped is limited to a predetermined value to prevent compressor overloading. See Cooling Ramp Loading (ConfigurationSLCTCRMP).
set to ‘On’ for these boards. The auxiliary board (AUX) has an 8-position DIP switch. Switches 2, 5, and 7 are set to ‘On.’ CONTROLS General — The 30RAP air-cooled scroll chillers contain the ComfortLink™ electronic control system that controls and monitors all operations of the chiller. The control system is composed of several components as listed in the sections below. See Fig. 3-5 for typical control box drawings. See Fig. 6 and 7 for control schematics.
3. Connect the red wire to (+) terminal on LVT of the plug, the white wire to COM terminal, and the black wire to the (–) terminal. 4. The RJ14 CCN connector on LVT can also be used, but is only intended for temporary connection (for example, a laptop computer running Service Tool). Table 18 — CCN Communication Bus Wiring MANUFACTURER Alpha American Belden Columbia Manhattan Quabik IMPORTANT: A shorted CCN bus cable will prevent some routines from running and may prevent the unit from starting.
3. Insert and secure the white (ground) wire to terminal 4 of the space temperature sensor. 4. Insert and secure the black (–) wire to terminal 2 of the space temperature sensor. 5. Connect the other end of the communication bus cable to the remainder of the CCN communication bus.
LOCATED OVER EMM AND EXV EMM EXV FB-1 CHC TRAN CCB AUX CSB-A1 LON UPC DISCONNECT OPTION/TB TB1 TB4 FAN 1 C-A1 MBB COMPRESSOR MS- MSCWP1 CWP2 CWP1 CWP2 MM A1 CONTROL BOX a30-4962 Fig. 3 — Typical Control Box for 30RAP010,015 FB-1 EXV EMM AUX LON CHC CCB-1 FB-3 TRAN TB1 CSB-A1 CCB-2 CSB-A2 UPC TB4 MBB DISCONNECT OPTION/TB MS- MSCWP1 CWP2 C-A1 FC1/MM CWP1 CWP2 FC2 Fig.
TRAN-2 FR-1 CB-1 C-A1 CSB-A1 TRAN-1 FR-2 C-A2 CSB-A2 CB-2 FC-1 MM 23 FC-3 AUX MBB UPC TB4 TB1 LOCATED OVER EMM AND EXV LON EXV CHC B1 B2 CONTROL BOX END A1 A2 COMPRESSORS FAN 2 FAN 1 FR-4 CSB-B2 CB-4 C-B2 055,060 UNIT ONLY CWP1 CWP2 FAN 4 FR-3 MS- MSCWP1 CWP2 FAN 3 C-B1 CSB-B1 CB-3 Fig.
STANDARD TERMINAL BLOCK OPTIONAL DISCONNECT CB1A TB1A PER NEC TO FUSED DISCONNECT PER NEC 2 3 21 11 TO FUSED DISCONNECT 1 CCB-1 22 12 23 13 BLK BLK BLK YEL YEL YEL 11 12 22 BLU 13 23 YEL BLU BLK CCB-2 BLK 11 21 YEL 12 22 BLU 13 23 H2 H3 HF ~ TRAN3 H1 SECONDARY 115V X1 YEL BLU GRN/YEL XF GFI-CO FIOP/ACCESSORY 2 BLK 2 BLK 22 YEL 13 23 BLU 1 T1 2 COMP A1 T2 3 T3 GRN/YEL CH-A2 11 21 BLK 12 22 YEL 13 23 BLU 1 T1 2 COMP A2 T2 3 T3 CHILL
CB1 3.
STANDARD TERMINAL BLOCK OPTIONAL DISCONNECT CB1A CCB-1 TB1A PER NEC TO FUSED DISCONNECT PER NEC 2 3 11 TO FUSED DISCONNECT 1 12 21 BLK BLK BLK BLK BLK 22 YEL YEL YEL YEL YEL 13 23 BLU YEL BLU BLK CCB-2 BLK 11 21 YEL 12 22 BLU 13 23 CCB-3 ~ ~ FU6 BLK RED 1 1 H2 H3 HF ~ TRAN3 H1 11 YEL 12 22 BLU 13 23 YEL BLU BLK BLK 2 LINE SERIES TERMINAL CONNECTIONS FOR PRIMARY SIDE 575-3-60 100 H1-H2 XF-X2 230-3-60 400,500 H2-H4 XF-X2 208-3-60 500 H3-H4 XF-X2
CB1 3.
RED LED - STATUS GREEN LED LEN (LOCAL EQUIPMENT NETWORK) YELLOW LED CCN (CARRIER COMFORT NETWORK) INSTANCE JUMPER CEPL130346-01 K11 J1 J4 K8 STATUS J2 K7 K10 K9 K5 K6 J10 LEN J3 K4 K3 K1 K2 CCN J5 J6 J7 J9 J8 Fig. 8 — Main Base Board a30-4967 Fig. 9 — Enable/Off/Remote Contact Switch, and Emergency On/Off Switch Locations T-55 SPACE SENSOR a30-4968 SPT (T10) PART NO.
compressor to start next. If no compressors have been running for more than 30 minutes and the leaving fluid temperature is greater than the saturated condensing temperature, the wear factor is still used to determine which compressor to start next. If the leaving fluid temperature is less than the saturated condensing temperature, then the control will start either compressor A1 or compressor B1 first, depending on the user-configurable circuit lead-lag value.
J2 LEN J3 TEST 1 PWR J4 J1 STATUS CEPL130351-01 CEBD430351-0396-01C J5 J7 J6 RED LED - STATUS TEST 2 GREEN LED LEN (LOCAL EQUIPMENT NETWORK) ADDRESS DIP SWITCH Fig. 12 — Energy Management Module when the control is attempting to remove the last stage of capacity. Slow Change Override — The control prevents the capacity stages from being changed when the leaving fluid temperature is close to the set point (within an adjustable deadband) and moving towards the set point.
Table 19 — Part Load Data Percent Displacement, Standard Units with Minimum Load Valve CONTROL STEPS 30RAP UNIT SIZE 010 015 1 1 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 018 020 025 030 035 040 045 050 055 060 CAPACITY STEPS % Displacement 100 100 100 50 20* 100 50 24* 100 50 29* 100 50 32* 100 77 50 23 9* 100 73 50 23 11* 100 74 50 24 12* 100 75 50 25 14* 100 73 50 23 13* 100 75 50 25 16* *Minimum Load Valve energized.
be added to the current fan stage. Fan On Set Point (F.ON) equals Head Set Point (Set PointsHEADH.DP) except after a fan stage increase when the Head Set Point is increased by Fan Stage Delta (Set PointsHEADF.DLT). A fan stage is decreased when the SCTs of both circuits are less than the Fan Off Set Point (Set PointsHEAD F.OFF) for two minutes. Table 20 shows the number of fan stages, contactors energized and the fans that are on during the fan stage. Unit sizes 035 to 060 have common fan control.
OFM1 CONTROL BOX CONTROL BOX a30-4970 OFM1 Top View Sizes 018-030 OFM1 CONTROL BOX CONTROL BOX Top View Sizes 010,015 OFM2 OFM3 OFM2 Top View Sizes 035-050 OFM1 OFM3 OFM2 OFM4 Top View Sizes 055,060 Fig.
Table 21 — Control Methods and Cooling Set Points CONTROL TYPE (CTRL) 0 (switch) 2 (Occupancy) 3 (CCN) OCCUPANCY STATE Occupied Unoccupied Occupied Unoccupied Occupied Unoccupied 0 (single) ON,CSP1 ON,CSP1 ON,CSP1 OFF ON,CSP1 ON,CSP1 COOLING SET POINT SELECT (CLSP) 1 2 (dual, switch) (dual, occ) ON* ON,CSP1 ON* ON,CSP2 ON* Illegal OFF Illegal ON* ON,CSP1 ON* ON,CSP2 3 (4 to 20 mA) ON† ON ON† OFF ON† ON† *Dual set point switch input used. CSP1 used when switch input is open.
interlock contacts should be rated for dry circuit application capable of handling 5 vdc at 2 mA. SINGLE INTEGRAL PUMP CONTROL — With a single pump, the following options must be configured: • Cooler Pump Control (ConfigurationOPT1CPC) = ON. • Cooler Pump 1 Enable (ConfigurationOPT1 PM1E) = YES. • Cooler Pump 2 Enable (ConfigurationOPT1 PM2E) = NO. With a single integral pump, the Cooler Pump Starter will be energized when the machine is occupied.
If the control starts a pump and the wrong interlock circuit closes for at least 20 seconds, an A189 – Cooler Pump and Aux Contact Input Miswire Alarm will be generated. The unit will be prevented from starting. The control will allow for pump changeover. Two methods will change the pump sequence. Before the changeover can occur, the unit must be at Capacity Stage 0. During changeover the chilled water flow switch input is ignored for 10 seconds to avoid a nuisance alarm.
Table 22 — Dual Chiller Configuration (Master Chiller Example) SUB-MODE ITEM KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENTS ENTER CTRL CONTROL METHOD ENTER 0 SWITCH DEFAULT 0 ESCAPE OPT2 CCN ADDRESS DEFAULT 1 CCN BUS NUMBER DEFAULT 0 DISP UNIT OPT1 OPT2 CTRL CCN CCNA ENTER 1 CCNB CCN CCNB ENTER 0 ESCAPE CCN PROCEED TO SUBMODE RESET RSET ENTER LLEN LLEN MSSL CRST COOLING RESET TYPE LLEN LEAD/LAG CHILLER ENABLE 15 ITEMS ENTER DSBL SCROLLING STOPS ENTER DSBL VALUE FLAS
Table 22 — Dual Chiller Configuration (Master Chiller Example) (cont) SUB-MODE ITEM KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENTS LLBL ENTER 2 LEAD/LAG BALANCE SELECT CHANGE ACCEPTED ESCAPE LLBL LLBD LLBD LEAD/LAG BALANCE DELTA ENTER 168 LEAD/LAG BALANCE DELTA ESCAPE LLBD LLDY RSET LLDY LLDY PARA DEFAULT 168 LAG START DELAY ENTER 5 SCROLLING STOPS ENTER 5 VALUE FLASHES 10 SELECT 10 ENTER 10 ESCAPE LLDY ESCAPE RSET ENTER YES LAG START DELAY CHANGE ACCEPTED MASTER C
Table 23 — Dual Chiller Configuration (Slave Chiller Example) SUB-MODE ITEM KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENTS ENTER CTRL CONTROL METHOD 0 SWITCH DEFAULT 0 CCN ADDRESS SCROLLING STOPS DISP UNIT OPT1 OPT2 CTRL ESCAPE OPT2 CCN CCNA CCNA ENTER 1 ENTER 1 VALUE FLASHES 2 SELECT 2 (SEE NOTE 1) CCN CCNA CCNB ENTER 2 ESCAPE CCN ENTER 0 ESCAPE CCN CCN ADDRESS CHANGE ACCEPTED CCN BUS NUMBER DEFAULT 0 (SEE NOTE 2) PROCEED TO SUBMODE RSET RSET ENTER LLEN LLEN CRST
Table 24 — 4 to 20 mA Reset SUB-MODE DISPLAY ITEM EXPANSION CRST 1 COOLING RESET TYPE MA.DG 5.0 F (2.8 C) DEGREES COOL RESET KEYPAD ENTRY ITEM ENTER RSET COMMENT 0 = no reset 1 = 4 to 20 mA input 2 = Outdoor air temp 3 = Return Fluid 4 = Space Temperature Default: 0° F (0° C) Reset at 20 mA Range: –30 to 30 F (–16.7 to 16.7 C) NOTE: The example above shows how to configure the chiller for 4 to 20 mA reset. No reset will occur at 4.0 mA input, and a 5.0 F reset will occur at 20.0 mA.
Table 26A — Configuring Outdoor Air and Space Temperature Reset MODE (RED LED) KEYPAD ENTRY SUBMODE ENTER DISP KEYPAD ENTRY DISPLAY ITEM EXPANSION COMMENT 4 COOLING RESET TYPE 2 = Outdoor-Air Temperature 4 = Space Temperature (Connect to TB5-5,6) 85 °F 72 °F REMOTE - NO RESET TEMP Default: 125.0 F (51.7 C) Range: 0° to125 F RM.F 55 °F 68 °F REMOTE - FULL RESET TEMP Default: 0.0° F (-17.7 C) Range: 0° to 125 F RM.
Under normal operation, the chiller will maintain a constant leaving fluid temperature approximately equal to the chilled fluid set point. As the cooler load varies, the entering cooler fluid will change in proportion to the load as shown in Fig. 20. Usually the chiller size and leaving-fluid temperature set point are selected based on a full-load condition. At part load, the fluid temperature set point may be colder than required.
length of time that a loadshed condition is allowed to exist. The control will disable the Redline/Loadshed command if no Cancel command has been received within the configured maximum loadshed time limit. DEMAND LIMIT (CCN Loadshed Controlled) — To configure Demand Limit for CCN Loadshed control set the Demand Limit Select (ConfigurationRSETDMDC) to 3.
Table 27 — Configuring Demand Limit MODE CONFIGURATION KEYPAD ENTRY SUB-MODE KEYPAD ENTRY ITEM DISPLAY ITEM EXPANSION ENTER DISP ENTER TEST ON/OFF Test Display LEDs UNIT ENTER TYPE X Unit Type OPT1 ENTER FLUD X Cooler Fluid OPT2 ENTER CTRL X Control Method ENTER CRST X Cooling Reset Type COMMENT HP.A HP.B EXV.A EXV.B M.
2. Use the scrolling marquee display to adjust the Cooling Set Point. 3. Fill chilled fluid circuit with clean water (with recommended inhibitor added) or other non-corrosive fluid to be cooled. Bleed all air out of the high points of the system. If chilled water is to be maintained at a temperature below 40 F (4.4 C) or outdoor temperatures are expected to be below 32 F (0° C), a brine of sufficient concentration must be used to prevent freeze-up at anticipated suction temperatures. See Table 28. 4.
Unbalanced 3-Phase Supply Voltage — Never operate a motor where a phase imbalance between phases is greater than 2%. To determine percent voltage imbalance: max voltage deviation from avg voltage % Voltage Imbalance = 100 x average voltage The maximum voltage deviation is the largest difference between a voltage measurement across 2 legs and the average across all 3 legs. Example: Supply voltage is 240-3-60. AB = 243 v BC = 236 v AC = 238 v CAUTION Never charge liquid into low-pressure side of system.
determines the saturated temperature of suction gas. The difference between the temperature of the superheated gas and the saturated suction temperature is the superheat. The EXV board controls the position of the electronic expansion valve stepper motor to maintain superheat set point. The MBB controls the superheat leaving cooler to approximately 9° F (5° C). Because EXV status is communicated to the main base board (MBB) and is controlled by the EXV boards, it is possible to track the valve position.
INCLUDED IN CABLE KIT CABLE CABLE CABLE RETAINER MOTOR AND ADAPTER ASSEMBLY MOTOR ADAPTER ASSEMBLY CABLE RETAINER GASKET MOTOR ADAPTER ASSEMBLY SIGHTGLASS SPORLAN FLOW DIRECTION NORMAL FLOW DIRECTION a30-4971 Fig. 24 — Electronic Expansion Valve Details During the next several seconds, carefully connect the negative test lead to pins 1,2,4 and 5 in succession (plug J6 for Circuit A, plug J7 for Circuit B). Digital voltmeters will average this signal and display approximately 6 vdc.
CAUTION BLK WHT If the existing motor has been removed for inspection or cleaning, be sure that the piston is fully retracted into the motor assembly before installation on the valve. Failure to do so will permanently damage the drive and motor. Replacement motor assemblies are shipped in the retracted position and may be installed as received. GRN RED Compressor Replacement (Refer to Fig. 26 and 27) — All models contain scroll compressors and have from one to four compressors.
Mobil . . . . . . . . . . . . . . . . . . . . . . . . . . .EAL Arctic 32-3MA Uniqema . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RL32-3MAF Do not reuse oil that has been drained out, or oil that has been exposed to atmosphere. 2. Disconnect the liquid-in and liquid-out connections at the heat exchanger. 3. Recover the refrigerant from the system, and unsolder the refrigerant-in and refrigerant-out connections. 4. Remove the old heat exchanger.
DPT HPS SUCTION ACCESS VALVE EWT SPT RGT COMPRESSOR A2 FLOW SWITCH LWT a30-4973 COMPRESSOR A1 DTT Fig. 26 — Compressor Location — 30RAP010-030 DPT HPS SUCTION RGT SPT ACCESS VALVE SPT RGT a30-4974 DISCHARGE ACCESS VALVE EWT DTT A1 A2 B1 B2 OIL SIGHTGLASS DISCHARGE ACCESS VALVE LWT DPT FLOW SWITCH HPS Fig. 27 — Compressor Location — 30RAP035-060 DPT DTT EWT HPS LWT RGT SPT — — — — — — — LEGEND FOR FIG.
HEATER CABLE — Optional factory-installed cooler and/or hydronic package heaters are cycled based on the input from the outside-air temperature sensor. These heaters, when installed, are designed to protect the cooler and/or hydronic package from freezing down to –20 F (–29 C). Power for these heaters is supplied from the main unit power. The input from the low pressure transducer provides a backup cooler freeze protection package.
necessary, build-up (e.g., lime) can be removed with a common vinegar cleansing agent. The flow sensor cable is provided with (3) LEDs that indicate if 24 vac power is present and also status of the switch contacts. The LEDs are as follows: • Green LED ON – 24 vac present • One Yellow LED ON – Flow sensor switch OPEN • Two Yellow LED ON – Flow sensor switch CLOSED If nuisance trips of the sensor are occurring, follow the steps below to correct the situation: 1.
Table 33 — 5K Thermistor Temperatures (°F) vs. Resistance/Voltage Drop (Voltage Drop for EWT, LWT, RGT, and OAT) TEMP (F) –25 –24 –23 –22 –21 –20 –19 –18 –17 –16 –15 –14 –13 –12 –11 –10 –9 –8 –7 –6 –5 –4 –3 –2 –1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 VOLTAGE DROP (V) 3.699 3.689 3.679 3.668 3.658 3.647 3.636 3.624 3.613 3.601 3.588 3.576 3.563 3.550 3.536 3.523 3.509 3.494 3.
Table 34 — 5K Thermistor Temperatures (°C) vs. Resistance/Voltage Drop (Voltage Drop for EWT, LWT, RGT, and OAT) TEMP (C) –32 –31 –30 –29 –28 –27 –26 –25 –24 –23 –22 –21 –20 –19 –18 –17 –16 –15 –14 –13 –12 –11 –10 –9 –8 –7 –6 –5 –4 –3 –2 –1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 VOLTAGE DROP (V) 3.705 3.687 3.668 3.649 3.629 3.608 3.586 3.563 3.539 3.514 3.489 3.462 3.434 3.406 3.376 3.345 3.313 3.281 3.247 3.212 3.177 3.140 3.103 3.065 3.025 2.985 2.945 2.903 2.860 2.817 2.774 2.730 2.685 2.639 2.593 2.547 2.
Table 35 — 10K Thermistor Temperature (°F) vs. Resistance/Voltage Drop (For SPT) TEMP (F) –25 –24 –23 –22 –21 –20 –19 –18 –17 –16 –15 –14 –13 –12 –11 –10 –9 –8 –7 –6 –5 –4 –3 –2 –1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 VOLTAGE DROP (V) 4.758 4.750 4.741 4.733 4.724 4.715 4.705 4.696 4.686 4.676 4.665 4.655 4.644 4.633 4.621 4.609 4.597 4.585 4.572 4.560 4.546 4.533 4.519 4.
Table 36 — 10K Thermistor Temperature (°C) vs. Resistance/Voltage Drop (For SPT) TEMP (C) –32 –31 –30 –29 –28 –27 –26 –25 –24 –23 –22 –21 –20 –19 –18 –17 –16 –15 –14 –13 –12 –11 –10 –9 –8 –7 –6 –5 –4 –3 –2 –1 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 VOLTAGE DROP (V) 4.762 4.748 4.733 4.716 4.700 4.682 4.663 4.644 4.624 4.602 4.580 4.557 4.533 4.508 4.482 4.455 4.426 4.397 4.367 4.335 4.303 4.269 4.235 4.199 4.162 4.124 4.085 4.044 4.003 3.961 3.917 3.873 3.828 3.781 3.734 3.686 3.637 3.587 3.537 3.485 3.433 3.
1 2 3 4 5 6 7 8 9 10 11 J8 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 ACCSY DPT LWT LVT OAT RGT SEN SPT 1 RGTA RED 2 LOW SOUND FAN — A shroud and a wire guard provide protection from the rotating fan. The exposed end of the fan motor shaft is protected from weather by grease. If fan motor must be removed for service or replacement, be sure to regrease fan shaft and reinstall fan guard. The fan motor has a step in the motor shaft.
VFD. It should not be removed with power applied to the VFD. LOSS OF CCN COMMUNICATIONS — Carrier Comfort Network® (CCN) communications with external control systems can be affected by high frequency electrical noise generated by the Motormaster V control. Ensure unit is well grounded to eliminate ground currents along communication lines.
LOW AMBIENT OPERATION (MOTORMASTER V) FIOP/ACCESSORY MM-A FB1 FB3 1 BLK 11 21 BLK 11 21 BLK L1 T1 BLK-1 YEL 12 22 YEL 12 22 YEL L2 T2 BLK-2 BLU 13 BLU 23 13 L3 BLU 23 T3 VIO 11 *1 25 240 1/4W 2 FB2 BLK 11 21 BLK 11 YEL 12 22 YEL 12 BLU 13 23 BLU 13 22 BLK-2 BLK-3 BLK WHT LEGEND Auxiliary Fuse Block Motormaster Outdoor Fan Motor Terminal Block 8 6 BLK VOLTAGE HZ 1 208/230/460/575 60 13A 380 60 1 2 OFM2 3 1 GRN/YEL 3 2 BLK BLK COOLER/PUM
Table 38 — Fault Codes FAULT CODE AF CF cF CL CURRENT LIMIT: The output current has exceeded the CURRENT LIMIT setting (Parameter 25) and the drive is reducing the output frequency to reduce the output current. If the drive remains in CURRENT LIMIT too long, it can trip into a CURRENT OVERLOAD fault (PF). Data Fault: User data and OEM defaults in the EPM are corrupted. High DC Bus Voltage Fault: Line voltage is too high; Deceleration rate is too fast; Overhauling load.
Table 39 — Motormaster® V Program Parameters for Operating Modes PARAMETERS P01 P02 P03 P04 P05 P06 P08 P09 P10 P11 P12 P13 P14 P15 P16 P17 P19 P20 P21 P22 P23 P24 P25 P26 P27 P28 P29 P30 P31 P32 P33 P34 P35 P36 P37 P38 P39 P40 P41 P42 P43 P44 P45 P46 P47 P48 P61 P62 P63 P64 P65 P66 P67 P68 DESCRIPTION Line Voltage: 01 = low line, 02 = high line Carrier Freq: 01 = 4 kHz, 02 = 6 kHz, 03 = 8 kHz Startup mode: flying restart Stop mode: coast to stop Standard Speed source: 01= keypad, 04=4-20mA (NO PI), 05= R2
uncommon for actual pump duty to be different than what was anticipated at time of selection. In many cases, it may be desirable to make some field modifications to obtain optimum pump performance. Before any pump modifications are made, it is recommended that actual pump performance be verified and compared to the applicable pump curve. See base unit installation instructions. This can be done in a variety of ways: 1. If pump impeller diameter is known: a.
core face. Reduce pressure and use caution to prevent damage to air centers. • Check condenser coils for debris, clean as necessary. Every month: • Check moisture indicating sight glass for possible refrigerant loss and presence of moisture. Every 3 months (for all machines): • Check refrigerant charge. • Check all refrigerant joints and valves for refrigerant leaks, repair as necessary. • Check chilled water flow switch operation. • Check all condenser fans for proper operation.
High-Pressure Switch Trip — The high pressure switch has opened. Below are the factory settings for the fixed high pressure switch. 30RAP UNIT SIZE 010-060 CUTOUT psig 650 reset automatically before the motor protector resets, which may take up to 2 hours. High Discharge Gas Temperature Protection — Units equipped with digital compressors have an additional thermistor located on the discharge line, If discharge temperature exceeds 265 F (129.4 C), the digital compressor will be shut off.
Table 41 — Troubleshooting SYMPTOMS Cooler Circulating Pump Does Not Run CAUSE Power line open Control fuse or circuit breaker open REMEDY Reset circuit breaker. Check control circuit for ground or short. Reset breaker and replace fuse. Check the controls. Find the cause of trip and reset breaker. Check connections. Check wiring and rewire if necessary. Check line voltage — determine location of voltage drop and remedy deficiency. Check motor winding for open or short. Replace compressor if necessary.
Table 42 — Alarm and Alert Codes ALARM/ ALERT CODE ALARM OR ALERT DESCRIPTION WHY WAS THIS ALARM GENERATED? ACTION TAKEN BY CONTROL RESET METHOD PROBABLE CAUSE Compressor feedback signal does not match relay state Compressor A1 shut down. Manual High-pressure switch open, faulty CSB, loss of condenser air, filter drier plugged, noncondensables, operation beyond capability.
Table 42 — Alarm and Alert Codes (cont) ALARM/ ALERT CODE ALARM OR ALERT T110 Alert Circuit A Loss of Charge If the compressors are off and discharge pressure reading is < 26 psig for 30 sec. Circuit not allowed to start. Manual Refrigerant leak or transducer failure T111 Alert Circuit B Loss of Charge If the compressors are off and discharge pressure reading is < 26 psig for 30 sec. Circuit not allowed to start.
Table 42 — Alarm and Alert Codes (cont) ALARM/ ALERT CODE ALARM OR ALERT WHY WAS THIS ALARM GENERATED? ACTION TAKEN BY CONTROL RESET METHOD T153 Alert Real Time Clock Hardware Failure Internal clock on MBB fails Occupancy schedule will not be used. Chiller defaults to Local On mode. Automatic when correct clock control restarts. Time/Date/Month/ Day/Year not properly set. A154 Alarm Serial EEPROM Hardware Failure Hardware failure with MBB Chiller is unable to run.
Table 42 — Alarm and Alert Codes (cont) ALARM/ ALERT CODE ALARM OR ALERT DESCRIPTION WHY WAS THIS ALARM GENERATED? ACTION TAKEN BY CONTROL RESET METHOD Manual PROBABLE CAUSE T197 Alert Flow Lost While Pump 2 Running Cooler flow switch contacts open for 3 seconds after initially made All compressors shut down. Pump 2 turned off. Pump 1 will be started if available. Chiller allowed to run if Pump 1 successfully starts and flow switch is closed.
Table 42 — Alarm and Alert Codes (cont) ALARM/ ALERT CODE ALARM OR ALERT DESCRIPTION WHY WAS THIS ALARM GENERATED? ACTION TAKEN BY CONTROL RESET METHOD PROBABLE CAUSE Alert Strainer Blowdown Scheduled Maintenance Due Strainer Service Countdown (S.T.DN) expired. Complete strainer blowdown and enter 'YES' for Strainer Maintenance Done (S.T.MN) item. None Automatic Routine strainer maintenance required T303 Alert Condenser Coil Maintenance Due Coil Service Countdown (C.L.DN) expired.
of –40 to 245 F (–40 to 118 C). Failure of this thermistor will disable any elements of the control which requires its use. The cause of the alert is usually a faulty thermistor in the T55, or T58 device, a shorted or open thermistor caused by a wiring error, or a loose connection. T090 (Circuit A Discharge Pressure Transducer Failure) T091 (Circuit B Discharge Pressure Transducer Failure) — Alert codes 090 and 091 are for circuits A and B respectively.
T153 (Real Time Clock Hardware Failure) — A problem has been detected with MBB real time clock hardware. Try resetting the power and check the indicator lights. If the alarm continues, the board should be replaced. A154 (Serial EEPROM Hardware Failure) — A problem has been detected with the EEPROM on the MBB. Try resetting the power and check the indicator lights. If the alarm continues, the board should be replaced.
APPENDIX A — DISPLAY TABLES Run Status Mode and Sub-Mode Directory SUB-MODE ITEM EWT LWT SETP CTPT LOD.F DISPLAY ITEM DESCRIPTION AUTO VIEW OF RUN STATUS xxx.x ºF Entering Fluid Temp xxx.x ºF Leaving Fluid Temp xxx.x ºF Active Set Point xxx.x ºF Control Point xxx Load/Unload Factor STAT Control Mode VIEW LD.PM OCC LS.AC MODE CAP STGE ALRM TIME YES/NO YES/NO YES/NO xxx x xxx xx.
APPENDIX A — DISPLAY TABLES (cont) Run Status Mode and Sub-Mode Directory (cont) SUB-MODE STRT PM VERS ITEM ST.A1 ST.A2 ST.B1 ST.B2 PUMP SI.PM P.1.DN P.2.DN P.1.MN P.2.MN PMDT P.1.M0 P.1.M1 P.1.M2 P.1.M3 P.1.M4 P.2.M0 P.2.M1 P.2.M2 P.2.M3 P.2.M4 STRN SI.ST S.T.DN S.T.MN ST.DT S.T.M0 S.T.M1 S.T.M2 S.T.M3 S.T.M4 COIL SI.CL C.L.DN C.L.MN CL.DT C.L.M0 C.L.M1 C.L.M2 C.L.M3 C.L.
APPENDIX A — DISPLAY TABLES (cont) Service Test Mode and Sub-Mode Directory SUB-MODE ITEM DISPLAY ITEM DESCRIPTION TEST OUTS CMPA CMPB Service Test Mode EXV.A EXV.B FAN1 FAN2 FAN3 FAN4 FAN5 FAN6 V.HPA V.HPB CLP.1 CLP.2 UL.TM CL.HT RMT.A xxx% xxx% ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF xx xx ON/OFF ON/OFF xx ON/OFF ON/OFF CC.A1 UL.TM CC.A2 MLV ON/OFF xx ON/OFF ON/OFF CC.B1 CC.B2 ON/OFF ON/OFF COMMENT To enable Service Test mode, move Enable/Off/Remote contact switch to OFF.
APPENDIX A — DISPLAY TABLES (cont) Set Points Mode and Sub-Mode Directory SUB-MODE COOL HEAD FRZ ITEM DISPLAY CSP.1 CSP.2 CSP.3 xxx.x °F xxx.x °F xxx.x °F H.DP F.ON F.OFF B.OFF F.DLT xxx.x °F xxx.x °F xxx.x °F xx.x xxx BR.FZ xx.
APPENDIX A — DISPLAY TABLES (cont) Outputs Mode and Sub-Mode Directory SUB-MODE GEN.O A.EXV B.EXV CIR.A CIR.B ITEM FAN1 FAN2 FAN3 FAN4 FAN5 FAN6 V.HPA V.HPB C.WP1 C.WP2 CLHT MLV.R EXV.A APPR AP.SP X.SH.R S.SH.R SH_R OVR.A SPH.A ASH.S AMP.S PLM.A SPR.1 EXV.B APPR AP.SP OVR.B SPH.B ASH.S AMP.S PLM.B SPR.2 CC.A1 DPE.R CC.A2 CC.A3 CC.A4 CC.B1 CC.B2 CC.B3 CC.
APPENDIX A — DISPLAY TABLES (cont) Configuration Mode and Sub-Mode Directory SUB-MODE DISP UNIT OPT1 ITEM DISPLAY ITEM DESCRIPTION DISPLAY CONFIGURATION Test Display LEDs Metric Display TEST METR ON/OFF ON/OFF LANG X PAS.E PASS ENBL/DSBL XXXX SIZE SZA.1 SZA.2 SZA.3 SZA.4 SZB.1 SZB.2 SZB.3 SZB.4 SH.SP FAN.S EXV A1.TY XX XX XX XX XX XX XX XX XX X YES/NO YES/NO MAX.T XX FLUD X MLV.S CSB.E CPC PM1E PM2E PM.P.S PM.
APPENDIX A — DISPLAY TABLES (cont) Configuration Mode and Sub-Mode Directory (cont) SUB-MODE OPT2 ITEM DISPLAY ITEM DESCRIPTION UNIT OPTIONS 2 CONTROLS CTRL X Control Method LOAD X Loading Sequence Select LLCS X Lead/Lag Circuit Select LCWT XX High LCW Alert Limit DELY XX Minutes Off Time ICE.M LS.MD ENBL/DSBL X Ice Mode Enable Low Sound Mode Select LS.ST LS.ND 00:00 00:00 Low Sound Start Time Low Sound End Time LS.
APPENDIX A — DISPLAY TABLES (cont) Configuration Mode and Sub-Mode Directory (cont) SUB-MODE EXV.A ITEM DISPLAY ITEM DESCRIPTION CIR A EXV CONFIGURATION STR.A XXX EXV CIrc.A Start Pos MIN.A XXX EXV Circ.A Min Position RNG.A XXXXX EXVA Steps In Range SPD.A XXXXX EXVA STeps Per Second POF.A XXX EXVA Fail Position In % MIN.A XXXXX EXVA Minimum Steps MAX.A XXXXX EXVA Maximum Steps OVR.A XXX EXVA Overrun Steps TYP.A 0,1 EXVA Stepper Type H.SCT XXX High SCT Threshold X.
APPENDIX A — DISPLAY TABLES (cont) Configuration Mode and Sub-Mode Directory (cont) SUB-MODE MM RSET ITEM DISPLAY ITEM DESCRIPTION MOTORMASTER Motormaster Select MMR.S YES/NO P.GAN XX Head Pressure P Gain I.GAN XX.X Head Pressure I Gain D.GAN XX.X Head Pressure D Gain MIN.S XX Minimum Fan Speed RESET COOL TEMP COMMENT Default: NO Default: 1 Range: 1 to 4 Default: 0.1 Range: -20 to 20 Default: 0.0 Range: -20 to 20 Default: 5 CRST X Cooling Reset Type MA.DG XX.
APPENDIX A — DISPLAY TABLES (cont) Configuration Mode and Sub-Mode Directory (cont) SUB-MODE SLCT SERV BCST ITEM DISPLAY ITEM DESCRIPTION SETPOINT AND RAMP LOAD CLSP X Cooling Set Point Select RL.S ENBL/DSBL Ramp Load Select CRMP ENBL/DSBL Cooling Ramp Loading SCHD XX Schedule Number Z.GN X.X Deadband Multiplier EN.A1 EN.A2 EN.B1 EN.B2 YES/NO YES/NO YES/NO YES/NO T.D.B OAT.B G.S.BC BC.
APPENDIX A — DISPLAY TABLES (cont) Time Clock Mode and Sub-Mode Directory SUB-MODE TIME DATE ITEM HH.MM XX Month of Year DOM XX Day of Month DAY X Day of Week STR.M STR.W STR.D MIN.A STP.M STP.W STP.D MIN.S HOL.L HD.01 HD.02 HD.03 HD.04 HD.05 HD.06 HD.07 HD.08 ITEM DESCRIPTION TIME OF DAY XX.
APPENDIX A — DISPLAY TABLES (cont) Time Clock Mode and Sub-Mode Directory (cont) SUB-MODE HD.09 HD.10 HD.11 HD.12 HD.13 HD.14 HD.15 HD.16 HD.17 HD.18 HD.
APPENDIX A — DISPLAY TABLES (cont) Time Clock Mode and Sub-Mode Directory (cont) SUB-MODE HD.20 HD.21 HD.22 HD.23 HD.24 HD.25 HD.26 HD.27 HD.28 HD.29 HD.
APPENDIX A — DISPLAY TABLES (cont) Time Clock Mode and Sub-Mode Directory (cont) SUB-MODE SCH.N SCH.L PER.1 PER.2 PER.3 PER.4 PER.5 ITEM OCC.1 UNC.1 MON.1 TUE.1 WED.1 THU.1 FRI.1 SAT.1 SUN.1 HOL.1 OCC.2 UNC.2 MON.2 TUE.2 WED.2 THU.2 FRI.2 SAT.2 SUN.2 HOL.2 OCC.3 UNC.3 MON.3 TUE.3 WED.3 THU.3 FRI.3 SAT.3 SUN.3 HOL.3 OCC.4 UNC.4 MON.4 TUE.4 WED.4 THU.4 FRI.4 SAT.4 SUN.4 HOL.4 OCC.5 UNC.5 MON.5 TUE.5 WED.5 THU.5 FRI.5 SAT.5 SUN.5 HOL.
APPENDIX A — DISPLAY TABLES (cont) Time Clock Mode and Sub-Mode Directory (cont) SUB-MODE PER.6 PER.7 PER.8 OVR ITEM OCC.6 UNC.6 MON.6 TUE.6 WED.6 THU.6 FRI.6 SAT.6 SUN.6 HOL.6 OCC.7 UNC.7 MON.7 TUE.7 WED.7 THU.7 FRI.7 SAT.7 SUN.7 HOL.7 OCC.8 UNC.8 MON.8 TUE.8 WED.8 THU.8 FRI.8 SAT.8 SUN.8 HOL.8 OVR.T OVR.L T.
APPENDIX A — DISPLAY TABLES (cont) Operating Mode and Sub-Mode Directory SUB-MODE MODE ITEM DISPLAY MD01 MD02 MD03 MD05 MD06 MD07 MD08 MD09 MD10 MD13 MD14 MD15 MD16 MD17 MD18 MD19 MD20 MD21 MD22 MD23 MD24 MD25 ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ON/OFF ITEM DESCRIPTION MODES CONTROLLING UNIT CSM Controlling Chiller WSM Controlling Chiller Master/Slave Control Ramp Load Limited Timed Override
APPENDIX B — CCN TABLES CCN DISPLAY TABLES — A_UNIT (General Unit Parameters) DESCRIPTION Control Mode Occupied CCN Chiller Low Sound Active Alarm State Active Demand Limit Override Modes in Effect Percent Total Capacity Requested Stage Active Set Point Control Point Entering Fluid Temp Leaving Fluid Temp Emergency Stop Minutes Left for Start PUMPS Cooler Pump Relay 1 Cooler Pump Relay 2 Cooler Pump 1 Interlock Cooler Pump 2 Interlock Cooler Flow Switch Lead Pump Rotate Cooler Pumps Now Heat/Cool Select V
APPENDIX B — CCN TABLES (cont) CCN DISPLAY TABLES — CIRCADIO (Circuit A Discrete Inputs/Outputs) DESCRIPTION CIRC. A DISCRETE OUTPUTS Compressor A1 Relay Compressor A2 Relay Minimum Load Valve Relay VALUE UNITS POINT NAME FORCIBLE On/Off On/Off On/Off K_A1_RLY K_A2_RLY MLV_RLY N N N CIRC.
APPENDIX B — CCN TABLES (cont) CCN DISPLAY TABLES — OPTIONS (Unit Parameters) DESCRIPTION FANS Fan 1 Relay Fan 2 Relay Cooler/Pump Heater VALUE Off/On Off/On Off/On UNIT ANALOG VALUES Cooler Entering Fluid Cooler Leaving Fluid Lead/Lag Leaving Fluid snnn.n snnn.n snnn.
APPENDIX B — CCN TABLES (cont) CCN CONFIGURATION TABLES — OPTIONS2 (Options 2 Configuration) DESCRIPTION Control Method Loading Sequence Select Lead/Lag Circuit Select Cooling Setpoint Select Ramp Load Select Heat Cool Select High LCW Alert Limit Minutes off time Deadband Multiplier Ice Mode Enable Low Sound Mode Select Low Sound Start Time Low Sound End Time Low Sound Capacity Limit VALUE 0 = Switch 2 = Occupancy 3 = CCN 1 = Equal Loading 2 = Staged Loading 1 = Automatic 2 = Circuit A Leads 3 = Circuit B
APPENDIX B — CCN TABLES (cont) CCN CONFIGURATION TABLES — DUALCHIL (Dual Chiller Configuration Settings) DESCRIPTION LEAD/LAG Lead/Lag Chiller Enable Master/Slave Select Slave Address Lead/Lag Balance Select Lead/Lag Balance Delta Lag Start Delay Parallel Configuration VALUE Enable/Dsable Master/Slave 0 to 239 0 = None 40 to 400 0 to 30 Yes DEFAULT Dsable Master 2 0 168 5 Yes UNITS POINT NAME LL_ENA MS_SEL SLV_ADDR LL_BAL LL_BAL_D LL_DELAY PARALLEL hours minutes CCN CONFIGURATION TABLES — DISPLAY (Mar
APPENDIX B — CCN TABLES (cont) CCN SERVICE TABLES — SERVICE DESCRIPTION SERVICE Brine Freeze Point Pump Service Interval COMPRESSOR ENABLE Enable Compressor A1 Enable Compressor A2 Enable Compressor B1 Enable Compressor B2 VALUE DEFAULT UNITS F hours nnn.
APPENDIX B — CCN TABLES (cont) CCN MAINTENANCE TABLES — CIRB_EXV DESCRIPTION EXV % Open Circuit B Approach Approach Setpoint EXVB Override Suction Superheat Temp Active Superheat Setpt Active MOP Setpt Cir B EXV Position Limit VALUE nnn nnn.n nnn.n nnnnn nnn.n nn.n nn.
APPENDIX B — CCN TABLES (cont) CCN MAINTENANCE TABLES — ALARMS DESCRIPTION Active Alarm #1 Active Alarm #2 Active Alarm #3 Active Alarm #4 Active Alarm #5 Active Alarm #6 Active Alarm #7 Active Alarm #8 Active Alarm #9 Active Alarm #10 Active Alarm #11 Active Alarm #12 Active Alarm #13 Active Alarm #14 Active Alarm #15 Active Alarm #16 Active Alarm #17 Active Alarm #18 Active Alarm #19 Active Alarm #20 Active Alarm #21 Active Alarm #22 Active Alarm #23 Active Alarm #24 Active Alarm #25 VALUE Axxx or Txxx A
APPENDIX B — CCN TABLES (cont) CCN MAINTENANCE TABLES — PM-PUMP DESCRIPTION Pump Service Interval Pump 1 Service Countdown Pump 1 Maintenance Done Pump 2 Service Countdown Pump 2 Maintenance Done Pump 1 Maintenance Date Pump 1 Maintenance Date Pump 1 Maintenance Date Pump 1 Maintenance Date Pump 1 Maintenance Date Pump 2 Maintenance Date Pump 2 Maintenance Date Pump 2 Maintenance Date Pump 2 Maintenance Date Pump 2 Maintenance Date VALUE nnnnnn nnnnnn Yes/No nnnnnn Yes/No mm/dd/yy hh:mm mm/dd/yy hh:mm mm/d
APPENDIX B — CCN TABLES (cont) CCN MAINTENANCE TABLES — RUNTEST DESCRIPTION Percent Total Capacity Percent Available Cap. Discharge Pressure Suction Pressure Head Setpoint Saturated Condensing Tmp Saturated Suction Temp Compr Return Gas Temp Discharge Gas Temp Suction Superheat Temp Compressor A1 Relay Compressor A2 Relay Minimum Load Valve Relay Compressor A1 Feedback Compressor A2 Feedback Percent Total Capacity Percent Available Cap.
APPENDIX B — CCN TABLES (cont) CCN MAINTENANCE TABLES — DUALCHIL DESCRIPTION Dual Chiller Link Good? Master Chiller Role VALUE Yes/No Stand Alone, Lead Chiller, Lag Chiller Stand Alone, Lead Chiller, Lag Chiller snnn.n snnn.n snnn.n UNITS F F F LEAD_CP LAG_CP CTRL_PNT Cool EnteringFluid-Slave Cool Leaving Fluid-Slave Cooler Entering Fluid Cooler Leaving Fluid Lead/Lag Leaving Fluid snnn.n snnn.n snnn.n snnn.n snnn.n F F F F F COOLEWTS COOLLWTS COOL_EWT COOL_LWT DUAL_LWT Percent Avail.
APPENDIX C — FACTORY SETTINGS FOR PUMP AND MANUAL STARTERS PUMP OPTION PUMP SIZE 1, 8 1.0 HP 2, 9 1.5 HP 3, B 2.0 HP 4, C 3.0 HP 5, 6, D, F 5.0 HP 7, G 7.5 HP UNIT VOLTAGE V-Hz (3 Ph) 208/230-60 380-60 460-60 575-60 208/230-60 380-60 460-60 575-60 208/230-60 380-60 460-60 575-60 208/230-60 380-60 460-60 575-60 208/230-60 380-60 460-60 575-60 208/230-60 380-60 460-60 575-60 101 OVERLOAD SETTING 4.0 2.0 1.6 2.4 5.4 2.7 2.2 3.3 6.6 3.3 2.6 4.0 8.8 4.4 3.5 5.3 14.0 7.0 5.6 8.5 22.8 11.4 9.1 13.
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING Optional BACnet Communications Wiring — 6 5 7 8 2 34 5 6 10's 1 9 0 2 34 7 8 9 0 1 The following section is used to configure the UPC Open controller which is used when the BACnet communications option is selected. The UPC Open controller is mounted in the main control box per unit components arrangement diagrams. TO ADDRESS THE UPC OPEN CONTROLLER — The user must give the UPC Open controller an address that is unique on the BACnet* network.
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont) CONFIGURING THE BAS PORT FOR BACNET MS/ TP — Use the same baud rate and communication settings for all controllers on the network segment. The UPC Open controller is fixed at 8 data bits, No Parity, and 1 Stop bit for this protocol's communications. If the UPC Open controller has been wired for power, pull the screw terminal connector from the controller's power terminals labeled Gnd and HOT.
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont) Fig. E — BT485 Terminator Installation temperature rating specifications list two acceptable alternatives. The Halar specification has a higher temperature rating and a tougher outer jacket than the SmokeGard specification, and it is appropriate for use in applications where the user is concerned about abrasion. The Halar jacket is also less likely to crack in extremely low temperatures.
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont) Table D — Open System Wiring Specifications and Recommended Vendors WIRING SPECIFICATIONS Wire Type RECOMMENDED VENDORS AND PART NUMBERS Connect Air Contractors Belden RMCORP Wire and Cable International Description 22 AWG, single twisted shielded pair, low capacitance, CL2P, TC foam FEP, plenum rated. See MS/TP Installation Guide for specifications.
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont) If the UPC Open is used with the chiller application of Lead/Lag/Standby, all chillers and UPC Open's CCN element numbers must be changed to a unique number in order to follow CCN specifications. In this application, there can only be a maximum of 3 UPC Open controllers on a CCN bus. For the CCN Alarm Acknowledger configuration, the UPC Open defaults to CCN Acknowledger.
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont) Table G — Network Points List POINT DESCRIPTION 4-20 ma Demand Signal 4-20 ma Reset Signal Active Demand Limit Active Setpoint Alarm State CCN Chiller CCN Loadshed Signal Circuit A Run Hours Circuit A Starts Circuit B Run Hours Circuit B Starts Coil Cleaning Maint.
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont) Table G — Network Points List (cont) POINT DESCRIPTION POINT NAME Cooling Setpoint 2 CSM Controlling Chiller Demand Level 1 Demand Level 2 Demand Level 3 Demand Limit Switch 1 Demand Limit Switch 2 Demand/Sound Limited Discharge Gas Temp Discharge Pressure Discharge Pressure Dual Setpoint Dual Setpoint Switch Element Comm Status Element Communications Alarm Emergency Stop Entering Fluid Temp EXV % Open EXV % Open Fan 1 Relay Fan 2 Relay Head Setpoi
APPENDIX D — OPTIONAL BACNET COMMUNICATIONS WIRING (cont) Table G — Network Points List (cont) POINT DESCRIPTION Percent Total Capacity Percent Total Capacity Percent Total Capacity Pump 1 Maintenance Done Pump 1 Run Hours Pump 1 Service Countdown Pump 2 Maintenance Done Pump 2 Run Hours Pump 2 Service Countdown Pump Changeover Hours Pump Off Delay Time Pump Service Interval Ramp Load Limited Requested Stage Rotate Cooler Pumps Now Saturated Condensing Tmp Saturated Condensing Tmp Saturated Suction Temp Sat
APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS 30RAP Maintenance Interval Requirements WEEKLY Compressor Check oil level. Economizer Cooler None. Controls Condenser None. Starter None. Review Alarm/Alert History. None. MONTHLY Compressor Check oil level. Cooler None. Condenser None. Economizer Controls Starter None. Inspect sight glass for moisture and refrigerant level. None. QUARTERLY Compressor Cooler Condenser Check oil level Economizer Check refrigerant charge.
APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS (cont) 30RAP Weekly Maintenance Log Plant ___________________________ Machine Model No. ________________ DATE OIL LEVEL CHECK ALARMS / FAULTS OPERATOR INITIALS REMARKS NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements are not covered under warranty.
APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS (cont) 30RAP Monthly Maintenance Log Month Date Operator UNIT SECTION Compressor Cooler Condenser Controls Starter 112 System 1 / ACTION Check Oil Level Send Oil Sample Out for Analysis Leak Test Inspect and Clean Cooler Inspect Cooler Heater Leak Test Record Water Pressure Differential (PSI) Inspect Water Pumps Leak Test Inspect and Clean Condenser Coil General Cleaning and Tightening Connections Check Pressure Transducers Confirm Accuracy of Thermisto
APPENDIX E — MAINTENANCE SUMMARY AND LOG SHEETS (cont) 30RAP Seasonal Shutdown Log Month Date Operator UNIT SECTION Cooler Controls 1 / 2 / / 3 / ACTION Isolate and Drain Cooler Add Glycol for Freeze Protection Do Not Disconnect Control Power NOTE: Equipment failures caused by lack of adherence to the Maintenance Interval Requirements are not covered under warranty.
Copyright 2010 Carrier Corporation Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53300067-01 Printed in U.S.A.
START-UP CHECKLIST FOR 30RAP LIQUID CHILLER (Remove and use for Job File) I.
YES NO 6. CHILLED WATER FLOW SWITCH IS OPERATIONAL. YES NO 7. WATER LOOP VOLUME GREATER THAN MINIMUM REQUIREMENTS. (See Table 40). YES NO 8. PROPER LOOP FREEZE PROTECTION PROVIDED TO _____ °F (°C). YES ANTIFREEZE TYPE _____________________ CONCENTRATION __________%. IF OUTDOOR AMBIENT IS BELOW 32 F (0° C) THEN ITEMS 9-11 HAVE TO BE COMPLETED TO PROVIDE COOLER FREEZE PROTECTION TO –20 F (–29 C). (REFER TO WINTER SHUTDOWN FOR PROPER COOLER WINTERIZATION PROCEDURE.
OPERATING DATA: RECORD THE FOLLOWING INFORMATION FROM THE PRESSURES AND TEMPERATURES MODES WHEN MACHINE IS IN A STABLE OPERATING CONDITION: PRESSURE/TEMPERATURE CIRCUIT A CIRCUIT B DISCHARGE PRESSURE DP.A DP.B SUCTION PRESSURE SP.A SP.B SATURATED CONDENSING TEMP SCT.A SCT.B SATURATED SUCTION TEMP SST.A SST.B RETURN GAS TEMPERATURE RGT.A RGT.B LIQUID LINE TEMPERATURE* DISCHARGE LINE TEMPERATURE* *Readings taken with a digital thermometer.
SUB-MODE VERS ITEM MBB AUX1 EXV EMM MARQUEE NAVIGATOR DISPLAY ITEM EXPANSION CESR-131460- _ _-_ _ CESR-131333- _ _-_ _ CESR-131172- _ _-_ _ CESR-131174- _ _-_ _ CESR-131171- _ _-_ _ CESR-131227- _ _-_ _ (PRESS ENTER AND ESCAPE SIMULTANEOUSLY TO OBTAIN SOFTWARE VERSIONS) COMMENTS: _________________________________________________________________________________________ _________________________________________________________________________________________ _______________________________________________
III. Unit Start-Up (cont) RECORD CONFIGURATION SETTINGS UNIT (Configuration Settings) SUBMODE ITEM ITEM EXPANSION DISPLAY ENTRY UNIT CONFIGURATION UNIT SIZE UNIT SIZE XXX SZA.1 COMPRESSOR A1 SIZE XX SZA.2 COMPRESSOR A2 SIZE XX SZA.3 COMPRESSOR A3 SIZE XX SZA.4 COMPRESSOR A4 SIZE XX SZB.1 COMPRESSOR B1 SIZE XX SZB.2 COMPRESSOR B2 SIZE XX SZB.3 COMPRESSOR B3 SIZE XX SZB.4 COMPRESSOR B4 SIZE XX SH.SP SUPERHEAT SETPOINT XX.X F FAN.
PRESS ESCAPE KEY TO DISPLAY ‘OPT1’. PRESS DOWN ARROW KEY TO DISPLAY ‘OPT2’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW. OPTIONS2 (Options Configuration) SUBMODE ITEM ITEM EXPANSION DISPLAY ENTRY UNIT OPTIONS 2 CONTROLS OPT2 CTRL CONTROL METHOD X LOAD LOADING SEQUENCE SELECT X LLCS LEAD/LAG CIRCUIT SELECT X LCWT HIGH LCW ALERT LIMIT XX.X F DELY MINUTES OFF TIME XX ICE.M ICE MODE ENABLE ENBL/DSBL CLS.C CLOSE CONTROL SELECT ENBL/DSBL LS.
III. Unit Start-Up (cont) PRESS ESCAPE KEY TO DISPLAY ‘HP.B’. PRESS DOWN ARROW KEY TO DISPLAY ‘EXV.A’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW. EXV.A (Circuit A EXV Configuration) SUB-MODE EXV.A ITEM ITEM EXPANSION DISPLAY STR.A EXV CIRC.A START POS XXX MIN.A EXV CIRC.A MIN POSITION XXX RNG.A EXVA STEPS IN RANGE XXXXX SPD.A EXVA STEPS PER SECOND XXXXX POF.A EXVA FAIL POSITION IN % XXX MIN.A EXVA MINIMUM STEPS XXXXX MAX.A EXVA MAXIMUM STEPS XXXXX OVR.
PRESS ESCAPE KEY TO DISPLAY ‘MM’. PRESS DOWN ARROW KEY TO DISPLAY ‘RSET’. PRESS ENTER KEY. RECORD CONFIGURATION INFORMATION BELOW. RSET (Reset Configuration Settings) SUBMODE ITEM RSET ITEM EXPANSION DISPLAY ENTRY RESET COOL TEMP CRST COOLING RESET TYPE X MA.DG 4-20 - DEGREES RESET XX.X °F RM.NO REMOTE - NO RESET TEMP XXX.X °F RM.F REMOTE - FULL RESET TEMP XXX.X °F RM.DG REMOTE - DEGREES RESET XX.X °F RT.NO RETURN - NO RESET TEMP XXX.X °F RT.F RETURN - FULL RESET TEMP XXX.X °F RT.
III. Unit Start-Up (cont) PRESS ESCAPE KEY SEVERAL TIMES TO GET TO THE MODE LEVEL (BLANK DISPLAY). USE THE ARROW KEYS TO SCROLL TO THE SET POINT LED. PRESS ENTER TO DISPLAY SETPOINTS. RECORD CONFIGURATION INFORMATION BELOW: SETPOINT SUBMODE ITEM COOL ITEM EXPANSION DISPLAY COOLING SETPOINTS CSP.1 COOLING SETPOINT 1 XXX.X °F CSP.2 COOLING SETPOINT 2 XXX.X °F ICE SETPOINT XXX.X °F CSP.3 HEAD PRESSURE SETPOINTS HEAD H.DP HEAD SET POINT XXX.X °F F.ON FAN ON SET POINT XXX.X °F F.
COMPONENT TEST USE ESCAPE/ARROW KEYS TO ILLUMINATE CONFIGURATION LED. PRESS ENTER TO DISPLAY ‘DISP’. PRESS ENTER AGAIN TO DISPLAY ‘TEST’ FOLLOWED BY ‘OFF’. PRESS ENTER TO STOP DISPLAY AT ‘OFF’ AND ENTER AGAIN SO ‘OFF’ DISPLAY FLASHES. ‘PASS’ AND ‘WORD’ WILL FLASH IF PASSWORD NEEDS TO BE ENTERED. PRESS ENTER TO DISPLAY PASSWORD FIELD AND USE THE ENTER KEY FOR EACH OF THE FOUR PASSWORD DIGITS. USE ARROW KEYS IF PASSWORD IS OTHER THAN STANDARD.