Product data

15
50P1H,P1V009
325 CFM NOMINAL AIRFLOW COOLING/325 CFM NOMINAL AIRFLOW HEATING*
LEGEND *Performance capacities shown in thousands of Btuh.
NOTES:
1. Interpolation is permissible; extrapolation is not.
2. All entering air conditions are 80 F db and 67 F wb in cooling, and 70 F db in heat-
ing. AHRI/ISO certified conditions are 80.6 F db and 66.2 F wb in cooling and
68 F db in heating.
3. Table does not reflect fan or pump power corrections for AHRI/ISO conditions.
4. All performance is based upon the lower voltage of dual voltage rated units.
5. Operation below 40 F EWT is based upon a 15% methanol antifreeze solution.
6. Operation below 60 F EWT requires optional insulated water/refrigerant circuit.
7. See performance correction tables for operating conditions other than those listed
above.
EWT
(F)
GPM
PRESSURE DROP COOLING — EAT 80/67 F HEATING — EAT 70 F
PSI ft wg
Airflow
CFM
TC TSC
Sens/Tot
Ratio
kW THR EER
Airflow
CFM
THC kW HE LAT COP
20
2.3 4.5 10.5
Operation Not Recommended
250 6.5 0.73 4.2 94.2 2.6
2.3 4.5 10.5
330 6.7 0.66 4.4 88.8 3.0
30
1.1 1.3 3.0 250 10.2 6.0 0.59 0.39 11.6 26.6
250 7.1 0.74 4.7 96.3 2.8
1.1 1.3 3.0 330 10.7 6.8 0.64 0.40 12.0 26.6
330 7.3 0.67 5.0 90.4 3.2
1.7 1.9 4.4 250 10.5 6.0 0.57 0.36 11.7 29.5 250 7.4 0.75 4.9 97.4 2.9
1.7 1.9 4.4 330 10.9 6.8 0.62 0.37 12.2 29.5
330 7.6 0.67 5.3 91.2 3.3
2.3 3.5 8.1 250 10.6 6.0 0.56 0.34 11.8 31.1 250 7.5 0.75 5.1 97.9 2.9
2.3 3.5 8.1 330 11.0 6.8 0.61 0.36 12.3 31.1
330 7.7 0.68 5.4 91.7 3.4
40
1.1 0.9 2.0 250 9.9 6.0 0.61 0.43 11.3 22.8
250 8.0 0.76 5.5 99.8 3.1
1.1 0.9 2.0 330 10.3 6.8 0.66 0.45 11.8 22.8
330 8.2 0.69 5.9 93.1 3.5
1.7 1.5 3.5 250 10.1 6.0 0.59 0.40 11.5 25.4 250 8.4 0.77 5.8 101.1 3.2
1.7 1.5 3.5 330 10.5 6.8 0.64 0.41 12.0 25.4
330 8.6 0.69 6.2 94.1 3.6
2.3 3.0 6.8 250 10.3 6.0 0.59 0.38 11.6 26.8 250 8.6 0.78 6.0 101.8 3.2
2.3 3.0 6.8 330 10.7 6.8 0.64 0.40 12.0 26.9
330 8.8 0.70 6.4 94.7 3.7
50
1.1 0.6 1.5 250 9.4 6.0 0.63 0.48 11.1 19.5
250 9.0 0.79 6.4 103.3 3.4
1.1 0.6 1.5 330 9.8 6.7 0.69 0.50 11.6 19.5
330 9.2 0.71 6.8 95.8 3.8
1.7 1.3 2.9 250 9.7 6.0 0.62 0.45 11.3 21.7 250 9.4 0.80 6.7 104.8 3.5
1.7 1.3 2.9 330 10.1 6.8 0.67 0.47 11.7 21.7
330 9.6 0.72 7.2 97.0 3.9
2.3 2.6 6.0 250 9.9 6.0 0.61 0.43 11.3 23.0 250 9.6 0.80 6.9 105.6 3.5
2.3 2.6 6.0 330 10.3 6.8 0.66 0.45 11.8 23.0
330 9.8 0.72 7.4 97.6 4.0
60
1.1 0.5 1.2 250 9.0 5.9 0.65 0.54 10.8 16.5 250 9.9 0.81 7.2 106.8 3.6
1.1 0.5 1.2 330 9.4 6.7 0.71 0.57 11.3 16.5 330 10.2 0.73 7.7 98.5 4.1
1.7 1.1 2.5 250 9.3 5.9 0.64 0.50 11.0 18.5 250 10.4 0.82 7.6 108.4 3.7
1.7 1.1 2.5 330 9.7 6.7 0.69 0.52 11.5 18.5 330 10.6 0.74 8.1 99.8 4.2
2.3 2.3 5.4 250 9.5 6.0 0.63 0.48 11.1 19.6 250 10.6 0.83 7.8 109.3 3.7
2.3 2.3 5.4 330 9.8 6.7 0.69 0.50 11.6 19.6 330 10.9 0.75 8.3 100.5 4.3
70
1.1 0.4 0.9 250 8.5 5.8 0.68 0.61 10.6 14.0 250 10.8 0.84 8.0 110.1 3.8
1.1 0.4 0.9 330 8.8 6.5 0.74 0.63 11.0 14.0 330 11.1 0.75 8.5 101.1 4.3
1.7 1.0 2.3 250 8.8 5.8 0.66 0.56 10.7 15.6 250 11.3 0.85 8.4 111.9 3.9
1.7 1.0 2.3 330 9.2 6.6 0.72 0.59 11.2 15.6 330 11.6 0.77 9.0 102.5 4.4
2.3 2.1 4.9 250 9.1 5.9 0.65 0.53 10.9 17.1 250 11.4 0.85 8.5 112.1 3.9
2.3 2.1 4.9 330 9.5 6.7 0.71 0.55 11.3 17.1 330 11.6 0.77 9.0 102.7 4.4
80
1.1 0.3 0.8 250 8.0 5.6 0.70 0.67 10.3 11.8 250 11.7 0.87 8.7 113.3 4.0
1.1 0.3 0.8 330 8.3 6.3 0.77 0.70 10.7 11.8 330 12.0 0.78 9.3 103.6 4.5
1.7 0.9 2.1 250 8.3 5.7 0.69 0.63 10.5 13.2 250 12.2 0.88 9.1 115.1 4.0
1.7 0.9 2.1 330 8.6 6.5 0.75 0.66 10.9 13.2 330 12.5 0.79 9.8 105.0 4.6
2.3 2.0 4.6 250 8.6 5.8 0.67 0.59 10.6 14.4 250 12.2 0.88 9.2 115.4 4.1
2.3 2.0 4.6 330 8.9 6.5 0.73 0.62 11.1 14.4 330 12.5 0.79 9.8 105.2 4.6
85
1.1 0.3 0.7 250 7.7 5.5 0.71 0.70 10.1 11.0 250 12.0 0.88 9.0 114.5 4.0
1.1 0.3 0.7 330 8.0 6.2 0.78 0.73 10.5 11.0 330 12.3 0.80 9.6 104.6 4.6
1.7 0.9 2.0 250 8.0 5.6 0.70 0.67 10.3 12.1 250 12.6 0.90 9.5 116.5 4.1
1.7 0.9 2.0 330 8.4 6.4 0.76 0.69 10.7 12.1 330 12.9 0.80 10.1 106.1 4.7
2.3 1.9 4.4 250 8.3 5.7 0.69 0.63 10.5 13.3 250 12.6 0.90 9.5 116.8 4.1
2.3 1.9 4.4 330 8.7 6.5 0.75 0.65 10.9 13.3 330 12.9 0.80 10.2 106.3 4.7
90
1.1 0.3 0.6 250 7.5 5.4 0.72 0.73 10.0 10.2 250 12.3 0.89 9.3 115.7 4.1
1.1 0.3 0.6 330 7.8 6.2 0.79 0.76 10.4 10.2 330 12.6 0.80 9.9 105.5 4.6
1.7 0.8 1.9 250 7.7 5.5 0.71 0.70 10.1 11.1 250 12.9 0.91 9.8 117.9 4.2
1.7 0.8 1.9 330 8.1 6.3 0.78 0.73 10.6 11.1 330 13.3 0.82 10.5 107.2 4.8
2.3 1.8 4.3 250 8.0 5.6 0.70 0.66 10.3 12.1 250 13.0 0.91 9.9 118.2 4.2
2.3 1.8 4.3 330 8.4 6.4 0.76 0.69 10.7 12.1 330 13.3 0.82 10.5 107.4 4.8
100
1.1 0.2 0.6 250 6.8 5.1 0.76 0.82 9.6 8.2
Operation Not Recommended
1.1 0.2 0.6 330 7.0 5.8 0.82 0.86 10.0 8.2
1.7 0.8 1.7 250 7.1 5.3 0.74 0.78 9.8 9.2
1.7 0.8 1.7 330 7.4 6.0 0.81 0.81 10.2 9.2
2.3 1.7 4.0 250 7.3 5.4 0.73 0.75 9.9 9.7
2.3 1.7 4.0 330 7.6 6.1 0.80 0.78 10.3 9.7
110
1.1 0.2 0.5 250 6.1 4.8 0.79 0.90 9.2 6.8
1.1 0.2 0.5 330 6.3 5.4 0.85 0.94 9.5 6.8
1.7 0.7 1.6 250 6.5 5.0 0.77 0.86 9.4 7.6
1.7 0.7 1.6 330 6.8 5.6 0.84 0.89 9.8 7.6
2.3 1.6 3.8 250 6.7 5.1 0.76 0.83 9.5 8.0
2.3 1.6 3.8 330 7.0 5.8 0.83 0.87 9.9 8.0
120
1.1 0.2 0.4 250 5.4 4.4 0.82 0.98 8.7 5.5
1.1 0.2 0.4 330 5.6 5.0 0.89 1.02 9.1 5.5
1.7 0.7 1.6 250 5.8 4.6 0.80 0.94 9.0 6.2
1.7 0.7 1.6 330 6.0 5.2 0.87 0.98 9.4 6.2
2.3 1.6 3.6 250 6.0 4.7 0.79 0.91 9.1 6.5
2.3 1.6 3.6 330 6.2 5.4 0.86 0.95 9.5 6.5
AHRI Air Conditioning, Heating, and Refrigeration Institute
COP Coefficient of Performance
db Dry Bulb
EAT Entering Air Temperature
EER Energy Efficiency Ratio
EWT Entering Water Temperature
GPM Gallons Per Minute
HE Heat of Extraction (MBtuh)
ISO International Organization for Standardization
LAT Leaving Air Temperature (F)
MBtuh Btuh in Thousands
TC Total Capacity (MBtuh)
THC Total Heating Capacity (MBtuh)
THR Total Heat Rejection (MBtuh)
TSC Total Sensible Capacity (MBtuh)
wb Wet Bulb