Product data

29
ELECTRICAL DATA — 50P1H, P1V UNITS WITH STANDARD PSC MOTOR
LEGEND
NOTES:
1. HACR circuit breaker in USA only.
2. All fuses Class RK-5.
50P1
UNIT
SIZE
RATED
VOLTAGE
V-Ph-Hz
VOLTAGE
MIN/MAX
COMPRESSOR
FAN
MOTOR
FLA
TOTAL
UNIT
FLA
MIN
CIRCUIT
AMP
MAX
FUSE/
HACR
BRKR
RLA LRA Qty
006
208/230-1-60 197/254 3.3 17.7 1 0.40 3.7 4.5 15
265-1-60 239/292 2.9 13.5 1 0.40 3.3 4.0 15
009
208/230-1-60 197/254 5.6 22.2 1 0.80 6.4 7.8 15
265-1-60 239/292 3.8 18.8 1 0.70 4.5 5.5 15
012
208/230-1-60 197/254 5.1 32.5 1 0.80 5.9 7.2 15
265-1-60 239/292 4.0 31.5 1 0.70 4.7 5.7 15
015
208/230-1-60 197/254 6.0 29.0 1 1.00 7.0 8.5 15
265-1-60 239/292 5.4 28.0 1 0.86 6.3 7.6 15
018
208/230-1-60 197/254 7.2 33.0 1 1.00 8.2 10.0 15
265-1-60 239/292 5.9 28.0 1 0.86 6.8 8.2 15
024
208/230-1-60 197/254 12.8 58.3 1 1.50 14.3 17.5 30
265-1-60 239/292 9.6 54.0 1 1.30 10.9 13.3 20
030
208/230-1-60 197/254 14.1 73.0 1 3.00 17.1 20.6 30
265-1-60 239/292 11.2 60.0 1 2.70 13.9 16.7 25
208/230-3-60 197/254 8.9 58.0 1 3.00 11.9 14.1 20
460-3-60 414/506 4.2 28.0 1 1.70 5.9 7.0 15
036
208/230-1-60 197/254 16.7 79.0 1 1.80 18.5 22.7 35
265-1-60 239/292 13.5 72.0 1 2.00 15.5 18.9 30
208/230-3-60 197/254 10.4 73.0 1 1.80 12.2 14.8 25
460-3-60 414/506 5.8 38.0 1 1.24 7.0 8.5 15
042
208/230-1-60 197/254 17.9 112.0 1 3.00 20.9 25.4 40
208/230-3-60 197/254 13.5 88.0 1 3.00 16.5 19.9 30
460-3-60 414/506 6.0 44.0 1 1.70 7.7 9.2 15
575-3-60 518/633 4.9 34.0 1 1.40 6.3 7.5 15
048
208/230-1-60 197/254 21.8 117.0 1 3.40 25.2 30.7 50
208/230-3-60 197/254 13.7 83.1 1 3.40 17.1 20.5 30
460-3-60 414/506 6.2 41.0 1 1.80 8.0 9.6 15
575-3-60 518/633 4.8 33.0 1 1.40 6.2 7.4 15
060
208/230-1-60 197/254 26.3 134.0 1 4.90 31.2 37.8 60
208/230-3-60 197/254 15.6 110.0 1 4.90 20.5 24.4 40
460-3-60 414/506 7.8 52.0 1 2.50 10.3 12.3 20
575-3-60 518/633 5.8 38.9 1 1.90 7.7 9.2 15
BRKR Breaker
FLA Full Load Amps
HACR Heating, Air Conditioning and Refrigeration
LRA Locked Rotor Amps
RLA Rated Load Amps
Electrical data
1110