ELECTRICAL DATA — 50P1H, P1V UNITS WITH HIGH-STATIC PSC MOTOR
AND INTERNAL SECONDARY PUMP (SPECIAL ORDER OPTION)
*Neutral connection required. All 460-v units with internal secondary
pumps require a 4-wire power supply with neutral. Inernal secondary
pumps are rated 265 vac and are wired between one hot leg and
neutral.
LEGEND
NOTES:
1. HACR circuit breaker in USA only.
2. All fuses Class RK-5.
50P1
UNIT
SIZE
RATED
VOLTAGE
V-Ph-Hz
VOLTAGE
MIN/MAX
COMPRESSOR FAN
MOTOR
FLA
TOTAL
UNIT
FLA
PUMP
FLA
MIN
CIRCUIT
AMP
MAX
FUSE/
HACR BRKR
RLA LRA Qty
015
208/230-1-60 197/254 6.0 29.0 1 1.00 7.4 0.4 8.9 15
265-1-60 239/292 5.4 28.0 1 0.86 7.0 0.7 8.3 15
018
208/230-1-60 197/254 7.2 33.0 1 1.50 9.5 0.8 11.3 15
265-1-60 239/292 5.9 28.0 1 1.30 7.9 0.7 9.4 15
024
208/230-1-60 197/254 12.8 58.3 1 3.00 16.6 0.8 19.8 30
265-1-60 239/292 9.6 54.0 1 2.70 13.0 0.7 15.4 25
030
208/230-1-60 197/254 14.1 73.0 1 3.00 17.9 0.8 21.4 35
265-1-60 239/292 11.2 60.0 1 2.70 14.6 0.7 17.4 25
208/230-3-60 197/254 8.9 58.0 1 3.00 12.7 0.8 14.9 20
460-3-60* 414/506 4.2 28.0 1 1.70 6.6 0.7 7.7 15
036
208/230-1-60 197/254 16.7 79.0 1 3.00 20.5 0.8 24.7 40
265-1-60 239/292 13.5 72.0 1 2.70 16.9 0.7 20.3 30
208/230-3-60 197/254 10.4 73.0 1 3.00 14.2 0.8 16.8 25
460-3-60* 414/506 5.8 38.0 1 1.70 8.2 0.7 9.7 15
042
208/230-1-60 197/254 17.9 112.0 1 3.00 21.7 0.8 26.2 40
208/230-3-60 197/254 13.5 88.0 1 3.00 17.3 0.8 20.7 30
460-3-60* 414/506 6.0 44.0 1 1.70 8.4 0.7 9.9 15
048
208/230-1-60 197/254 21.8 117.0 1 4.90 27.8 1.1 33.2 50
208/230-3-60 197/254 13.7 83.1 1 4.90 19.7 1.1 23.1 35
460-3-60* 414/506 6.2 41.0 1 2.50 9.8 1.1 11.3 15
060
208/230-1-60 197/254 26.3 134.0 1 5.80 33.2 1.1 39.7 60
208/230-3-60 197/254 15.6 110.0 1 5.80 22.5 1.1 26.4 40
460-3-60* 414/506 7.8 52.0 1 2.60 11.5 1.1 13.4 20
BRKR Breaker
FLA Full Load Amps
HACR Heating, Air Conditioning and Refrigeration
LRA Locked Rotor Amps
RLA Rated Load Amps
Electrical data (cont)