Product data

35
Complete C
UNITS WITH COMPLETE C CONTROLLER, 208/230 V, THREE-PHASE UNITS
*Optional.
AL Alarm Relay Contacts
BM Blower Motor
BMC Blower Motor Contactor
BR Blower Relay
CB Circuit Breaker
CC Compressor Contactor
CO Condensate Overflow Sensor
COMPR Compressor
FP1 Water Coil Freeze Protection Sensor
FP2 Air Coil Freeze Protection Sensor
HP High-Pressure Switch
HPWS High Pressure Water Switch
JW Jumper Wire
LOC Loss of Charge Pressure Switch
MV Motorized Valve
MVES Motorized Valve End Switch
NEC National Electrical Code
P1 Field Wiring Terminal Block
RV Reversing Valve Solenoid
LEGEND
TRANS Transformer
TXV Thermostatic Expansion Valve
UPS Unit Performance Sentinel
Factory Low Voltage Wiring
Factory Line Voltage Wiring
Field Low Voltage Wiring
Field Line Voltage Wiring
Printed Circuit Trace
Optional Wiring
Relay/Contactor Coil
Thermistor
Condensate Pan
Circuit Breaker
Solenoid Coil
Relay Contacts - N.C.
Relay Contacts - N.O.
Capacitor
Temperature Switch
Low Pressure Switch
High Pressure Switch
Wire Nut
Splice Cap
LED
G
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. 208/230 v transformer will be connected for 208 v operation. For 230 v
operation, disconnect RED lead at L1 and attach ORANGE lead to L1.
Insulate open end of RED lead. Transformer is energy limiting or may
have circuit breaker.
4. FP1 thermistor provides freeze protection for water. When using anti-
freeze solutions, cut JW3 jumper.
5. Check installation wiring information for specific thermostat hookup. Refer
to thermostat installation instructions for wiring to the unit. Thermostat
wiring must be “Class 1” and voltage rating equal to or greater than unit
supply voltage.
6. 24-v alarm signal shown. For dry alarm contact, cut JW1 jumper and dry
contact will be available between AL1 and AL2.
7. Transformer secondary ground via Complete C board standoffs and
screws to control box. (Ground available from top two standoffs as
shown.)
8. Aquastat is supplied with unit and must be wired in series with the hot leg
to the pump. Aquastat is rated for voltage up to 277 v.
9. Fan motors factory wired for medium speed. For high and low speed
remove BLU wire from fan motor speed tap ‘M’ and connect to ‘H’ for high
or ‘L’ for low.
COMPLETE C CONTROLLER FAULT CODES
DESCRIPTION OF OPERATION LED ALARM RELAY
Normal Mode ON Open
Normal Mode with UPS Warning ON
Cycle (Closed 5 Sec.
Open 25 Sec.)
Complete C is Non-Functional OFF Open
Fault Retry Slow Flash Open
Lockout Fast Flash Closed
Over/Under Voltage Shutdown Slow Flash Open (Closed After 15 Min.)
Test Mode-No Fault in Memory Flashing Code 1 Cycling Code 1
Test Mode-HP Fault in Memory Flashing Code 2 Cycling Code 2
Test Mode-LP Fault in Memory Flashing Code 3 Cycling Code 3
Test Mode-FP1 Fault in Memory Flashing Code 4 Cycling Code 4
Test Mode-FP2 Fault in Memory Flashing Code 5 Cycling Code 5
Test Mode-CO Fault in Memory Flashing Code 6 Cycling Code 6
Test Mode-Over/Under Shutdown
in Memory
Flashing Code 7 Cycling Code 7
Test Mode-UPS in Memory Flashing Code 8 Cycling Code 8
Swapped FP1/FP2 Lockout Flashing Code 9 Cycling Code 9