Product data

37
Deluxe D
UNITS WITH DELUXE D CONTROLLER, SINGLE-PHASE
*Optional.
AL Alarm Relay Contacts
BM Blower Motor
BMC Blower Motor Capacitor
CB Circuit Breaker
CC Compressor Contactor
CO Condensate Overflow Sensor
FP1 Water Coil Freeze Protection Sensor
FP2 Air Coil Freeze Protection Sensor
HP High-Pressure Switch
HPWS High Pressure Water Switch
JW Jumper Wire
LOC Loss of Charge Pressure Switch
MV Motorized Valve
MVES Motorized Valve End Switch
NEC National Electric Code
P1 Field Wiring Terminal Block
RVS Reversing Valve Solenoid
TRANS Transformer
TXV Thermostatic Expansion Valve
LEGEND
Factory Low Voltage Wiring
Factory Line Voltage Wiring
Field Low Voltage Wiring
Field Line Voltage Wiring
Printed Circuit Trace
Optional Wiring
Relay/Contactor Coil
Thermistor
Condensate Pan
Circuit Breaker
Ground
Solenoid Coil
Relay Contacts - N.C.
Relay Contacts - N.O.
Capacitor
Temperature Switch
Low Pressure Switch
High Pressure Switch
Wire Nut
Splice Cap
LED
G
NOTES:
1. Compressor and blower motor thermally protected internally.
2. All wiring to the unit must comply with NEC and local codes.
3. 208/230 v transformer will be connected for 208 v operation. For 230 v
operation, disconnect RED lead at L1 and attach ORANGE lead to L1.
Insulate open end of RED lead. Transformer is energy limiting or may have
circuit breaker.
4. FP1 thermistor provides freeze protection for water. When using antifreeze
solutions, cut JW3 jumper.
5. Check installation wiring information for specific thermostat hookup. Refer
to thermostat installation instructions for wiring to the unit. Thermostat wir-
ing must be “Class 1” and voltage rating equal to or greater than unit sup-
ply voltage.
6. 24-v alarm signal shown. For dry alarm contact, cut JW4 jumper and dry
contact will be available between AL1 and AL2.
7. Transformer secondary ground via Deluxe D board standoffs and screws
to control box. (Ground available from top two standoffs as shown.)
8. Aquastat is supplied with unit and must be wired in series with the hot leg
to the pump. Aquastat is rated for voltage up to 277 v.
9. Blower motor is factory wired for high and low speeds. No other combina-
tion is available.
NOTES:
1. Status LED (GREEN) Slow Flash - Controller In - Fault Retry Mode. Fast Flash - Controller in Lockout Mode.
Slow Flash = 1 Flash per every 2 seconds. Fast Flash = 2 Flashes per every 1 second.
2. Fault LED (RED) flashes a code representing last fault in memory. If no fault in memory code 1 is flashed.
3. Cycles appropriate code, by cycling alarm relay in the same sequence as fault LED.
4. Alarm relay closes after 15 minutes.
5. Alarm relay cycles. Closed for 5 seconds and open for 25 seconds.
DELUXE D CONTROLLER FAULT CODES
OPERATION
STATUS LED
(GREEN)
TEST LED
(YELLOW)
FAULT LED
(RED)
ALARM RELAY
Normal Mode ON OFF Note 2 Open
Deluxe D is Non-Functional OFF OFF OFF Open
Test Mode ON Note 2 Cycle (Note 3)
Night Setback Flashing Code 2 Note 2
Emergency Shut Down Flashing Code 3 Note 2
Invalid Thermostat Inputs Flashing Code 4 Note 2
No Fault in Memory ON OFF Flashing Code 1 Open
HP Fault/(Lockout) Note 1 Slow Flash/(Fast Flash) OFF Flashing Code 2 Open/(Closed)
LP Fault/(Lockout) Note 1 Slow Flash/(Fast Flash) OFF Flashing Code 3 Open/(Closed)
FP1 Fault/(Lockout) Note 1 Slow Flash/(Fast Flash) OFF Flashing Code 4 Open/(Closed)
FP2 Fault/(Lockout) Note 1 Slow Flash/(Fast Flash) OFF Flashing Code 5 Open/(Closed)
CC Fault/(Lockout) Note 1 Slow Flash/(Fast Flash) OFF Flashing Code 6 Open/(Closed)
Over-Under Voltage Slow Flash OFF Flashing Code 7 Open (Note 4)
Normal Mode with UPS ON OFF Flashing Code 8 Cycle (Note 5)
Swapped FP1/FP2 Lockout Fast Flash OFF Flashing Code 9 Closed