Product data

9
The 50RLP model nomenclature is used to customize
the control panel options to control all WSHP system
requirements.
Panel can be ordered to include 2, 4, 6, or 8 stages of
system heat rejection.
Panel can be ordered to include 2, 4, 6, or 8 stages of
system heat addition.
Panel can be ordered with unique WSHP zone opera-
tion capabilities for stand-alone systems (i.e., noncom-
municating) to control 10 or 18 zones of WSHP units.
Panel can be ordered to control variable frequency cool-
ing tower fan operation.
System pumping operation can be configured for start/
stop, lead/lag, or variable frequency pump operation.
Direct Digital Controls (DDC) compatible using the Car-
rier Comfort Network
®
(CCN) and WSHP units utilizing
PremierLink™ CCN controllers.
Carrier’s line of Aquazone thermostats are both
attractive and multi-functional, accommodating stand-
alone water source heat pump installations.
Programmable 7-day thermostat
— Thermostat offers
2-stage heat, 2-stage cool, auto changeover, 7-day pro-
grammable with copy command, 4 settings per day, fully
electronic, 24 vac, backlit LCD, keypad lockout, no
batteries required, 5-minute compressor protection,
NEVERLOST™ memory, 3 security levels, and tempera-
ture display in degrees F or C.
Programmable 7-day light-activated thermostat
— Ther-
mostat offers same features as the 7-day programmable
thermostat and includes occupied comfort settings with
lights on, unoccupied energy savings with lights off.
Programmable 7-day flush-mount thermostat
Thermo-
stat offers same features as the 7-day programmable
thermostat and includes locking coverplate with tamper
proof screws, flush to wall mount, holiday/vacation
programming, set point limiting, dual point with adjustable
deadband, O or B terminal, and optional wall or
duct-mounted remote sensor.
Programmable 5-day thermostat
Thermostat offers
2-stage heat, 2-stage cool, auto changeover, 5-minute
built-in compressor protection, locking cover included,
temperature display in degrees F or C, keypad lockout,
backlit display, 5-1-1 programming, O or B terminal, dual
set point with adjustable deadband, configurable display,
self-prompting program, and 4 settings per day.
Non-programmable thermostat
Thermostat offers
2 heat stages, 2 cool stages, auto changeover, 5-minute
built-in compressor protection, locking cover included,
temperature display in degrees F or C, keypad lockout,
large display, backlit display, O or B terminal, dual set
point with adjustable deadband, and backplate with termi-
nals.
UC Open XP loop controller with six stages (2 stages
for heating and 4 stages for cooling) includes:
Loop temperature alarms
Two pump single loop flow monitoring with the ability
to manually select the lead pump
One common alarm signal and indicating light and one
audible alarm
Loop water temperature sensor test circuit
Functional test simulation from operator keypad
Real timeclock, industrial noise ratings
Loop water temperature control switch
Filter rack (2 in.) is available in place of the standard
1-in. return air filter to enhance the filtration system of the
water source heat pump. The 2-in. filter rack does not
include filters.
Fire-rated hoses are 2 ft long and have a fixed MPT on
one end and a swivel with an adapter on the other end.
Hose kits are provided with both a supply and return hose
and can be either stainless steel or galvanized. Two sizes
are available (
3
/
4
and 1 in.).
Ball valves (brass body) are used for shutoff and balanc-
ing water flow and are available with memory, memory
stop, and pressure temperature ports. Ball valves consist of
UL-listed brass body, ball and stem type with Teflon* seats
and seals. Two sizes are available (
3
/
4
and 1 in.).
Y strainers (bronze body) are “Y” type strainers with a
brass cap. With a maximum operating pressure rating of
450 psi, the strainer screen is made of stainless steel and is
available with blow down valves. Two sizes are available
(
3
/
4
and 1 in.).
Solenoid valves (brass body) offer 3.5 watt coil,
24 volt, 50/60 Hz, 740 amps inrush, .312 amps holding.
Solenoid valves have slow operation for quiet system appli-
cation. Two sizes are available (
3
/
4
and 1 in.).
Hose kit assemblies provide all the necessary compo-
nents to hook up a water-side system. Supply hose
includes a ported ball valve with pressure temperature
(P/T) plug ports, flexible stainless steel hose with swivel
and nipple. Return hose includes a ball valve, preset auto-
matic balancing valve (gpm) with two P/T ports, flexible
stainless steel hose with a swivel and nipple, balancing
valve, and low-pressure drop water control valve.
Remote sensors are available for Aquazone flush-mount
thermostats and for wall (wired and wireless) or duct
mounted applications.
SPT Standard
offers space temperature sensor with com-
munication port.
SPT Plus
offers space temperature sensor with set point
adjust, local override with indicating light and communica-
tion port.
SPT Pro
offers space temperature sensor with LCD dis-
play, set point adjust, local override, alarm icon, outside
air, and unit status with heating and cooling set points.
SPT Pro+
offers space temperature sensor with LCD dis-
play, set point adjust, local override, alarm icon, outside
air, unit status with heating and cooling set points, and fan
speed control.
LON wall sensors
are available in 3 models: sensor only,
sensor with status override indicator, and sensor with set
point, status adjustment override, and digital LCD display.
PremierLink™ accessories are available for providing a
fully integrated WSHP DDC system. Accessories include
supply air temperature sensors (with override and/or set
point adjustment), communicating room sensors, CO
2
*Registered trademark of DuPont.