® Turn to the Expertg Installation Guide This Installation Guide is intended to be used in conjunction Manual. with the Owner's The Owner's Manual must first be read thoroughly prior to installation Standby generator. A_ intended for outdoor A_ Not intended applications. c_0s LISTED of the Home installation for life support only.
ELECTRICAL INTERCONNECTION DRAWING ® Turn to the Expertg \ \ \ N1 N2 GENERATOR (LOCATED GROUND ON THE / 23 194 I \ / \ REAR OF UNIT) / \ GENERATOR OUTPUT CIRCUmT BREAKER 2 POLE / \ \EARTH SPIKE / \ "_ \ \ \ \ /
TO HOUSE BRANCH CiRCUiTS SPLICED USING WiRE NUTS EMERGENCY CiRCUiTS IllU 40A OR 70A 2-POLE CIRCUIT BREAKER i BAR SERVICE UL LISTED PANEL BOARD (8,10,12 OR 16 CIRCUIT TRANSFER SWITCH) CONNECTION BOX EXTERNAL CUSTOMER CONNECTION TO EXTERNAL OF GENERATOR CONNECTION PANEL 4 PmN L 1 = CONNECTOR N 0 I
The product contains or emits chemicals known to the state of California to cause cancer, birth defects or other reproductive harm. Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Becomefamiliar with this Installation Guide and the Instaflation & Owner'sManualincluded with the unit. The generatorcan Thank you for purchasing this model of the CARRIERproduct line.
Never use thegenerator oranyofitsparts asastep. Stepping ontheunit canstress andbreak parts, andmayresultindangerous operating conditions fromleaking exhaust gases, fuelleakage, oilleakage, etc. ELECTRICAL HAZARD All generatorscoveredby this manualproducedangerouselectrical voltagesand can causefatal electricalshock.Utility powerdelivers extremelyhigh and dangerousvoltagesto thetransfer switchas does the standbygeneratorwhenit is in operation.Avoidcontactwith bare wires,terminals,connections, etc.
It will be necessaryto paya visit to your local municipaloffices to applyfor a building permit. Building permitsare necessaryto ensure proper installation, safety and adherenceto all local building code specifications.The location and phone number can befoundin the governmentsectionof yourlocal phonebook. Plan the location of your generator.NOTE:Do not place the generatordirectlyunder a window.Selectan area outside of your homenearestyour incominggas service.
lOa. Determinewherethe flexible conduit will pass through the housefrom inside to outside. Whenyouare certainyouhaveclearanceon eachsideand within the wall, drill a small pilot holethrough the wall to markthe location. ID Theouterdiameterof thethreadedendis 15/16". lOb. Using a hole saw,drill a 1-3/4 inch diameterhole in the house'swall to allow the conduit to fit through. lla.
- continuedfrompage7 Wire nut the black wire to the matching circuit lead wire from the emergency circuit breakerfrom load center in the transferswitch.(Allcircuit wiresare color coded and labeled for easy identification). UL approved wire Iocknutsare includedin installation kit. WARNING If theutilitypowersupplyisnot turnedoff, sparkingcan occurat thebatterypostsandcausean explosion. NOTE: Dielectricgreaseshouldbe usedon batterypoststo aid in the prevention of corrosion.