Specifications

Network Time Requester When the Network Time
Request option is set to ON, the monitor thermostat will re-
quest CCN time and date from the network once per minute.
If there are multiple monitor thermostats on a network, there
must be at least one monitor thermostat requesting time.
When the Network Time Request option is set to OFF, the
monitor thermostat will not request time and date.
The Network Time Request option is only required for
VVTt systems and can be placed anywhere on the system
(on the primary or secondary communication bus).
To set the option, configure category 9, option 3. Use the
left set point buttons to toggle the option ON or OFF. The
default is OFF.
Receive Network Time When the Receive Net-
work Time option is set to ON, the monitor thermostat will
accept a broadcast of CCN time and date from the network.
When the Receive Network Time option is set to OFF,
the monitor thermostat will not accept a CCN time and date
broadcast.
To set the option, configure category 9, option 4. Use the
left set point buttons to toggle the option ON or OFF. The
default is ON.
Broadcast Acknowledger When the Broadcast
Acknowledger option is set to ON, the monitor thermostat
will acknowledge any CCN broadcast. Every primary and
secondary bus must have only one broadcast acknowledger.
When the Broadcast Acknowledger option is set to
OFF, the monitor thermostat will not acknowledge a CCN
broadcast.
To set the option, configure category 9, option 1. Use the
left set point buttons to toggle the option ON or OFF. The
default is OFF.
NOTE: Avoid using a monitor thermostat as a broadcast ac-
knowledger when possible. Broadcast acknowledgement works
best with a zone controller, TEMP system thermostat, or other
CCN devices.
Global Schedule Broadcast When the Global
Schedule Broadcast is set to ON, the monitor thermostat will
broadcast its occupancy schedule on the CCN. The schedule
number will be used to define the number of the occupancy
table broadcasted. Global schedules are occupancy sched-
ules 65-99.
NOTE: Unoccupied Override will not work if the monitor
thermostat is following a global schedule.
When the Global Schedule Broadcast is set to OFF,
the monitor thermostat will not broadcast its occupancy
schedule.
To set the option, configure category 9, option 2. Use the
left set point buttons to toggle the option ON or OFF. The
default is OFF.
NOTE: If using Global Schedule Broadcast, then Schedule
Number (category 2, option 9) must be set to a value be-
tween 65 and 99.
NOTE: The zone controller will not receive the holiday sig-
nal as part of the global schedule broadcast. The holiday will
be active at the monitor thermostat but not at the zone
controller.
Daylight Savings Time The monitor thermostat sup-
ports daylight savings time. The start date and stop dates are
entered by the user and the time is automatically adjusted
forward and backward at the configured times. The modi-
fied date and time is sent to other network devices if the
monitor thermostat is a Network Time Broadcast
Device.
Only the time broadcaster can do a daylight savings broad-
cast. If other monitor thermostats are on the network,
and they are configured not to receive network time, these
monitor thermostats will not support daylight savings time
functions.
DAYLIGHT SAVINGS TIME START MONTH The
Daylight Savings Time Start Month tells the monitor ther-
mostat which month to move its internal clock forward
for daylight savings time. To set the month, configure
category 9, option 6. Use the left set point buttons to raise
or lower the value. January is 1, February is 2, and so on.
The range of values is 1 to 12. The default is 4.
DAYLIGHT SAVINGS TIME START WEEK The Day-
light Savings Time Start Week tells the monitor thermostat
which week to move its internal clock forward for daylight
savings time. To set the week, configure category 9,
option 7. Use the left set point buttons to raise or lower the
value. The first week of the month is 1, the second week of
the month is 2, and so on. The last week of the month (in 4
or 5 week months) is always 5. The range of values is 1 to
5. The default is 1.
DAYLIGHT SAVINGS TIME START DAY The Day-
light Savings Time Start Day tells the monitor thermostat
which day to move its internal clock forward for daylight
savings time. To set the day, configure category 9, option 8.
Use the left set point buttons to raise or lower the value. The
first day of the week (Monday) is 1, the second day of the
week (Tuesday) is 2, and so on. The range of values is 1 to
7. The default is 7 (Sunday).
DAYLIGHT SAVINGS TIME MINUTES TO ADD The
Daylight Savings Time Minutes To Add option tells the moni-
tor thermostat how many minutes to move the clock forward
for daylight savings time. To set the number of minutes, con-
figure category 9, option 9. Use the left set point buttons to
raise or lower the value. The range of values is 0 to 90 min-
utes. The default is 60 minutes.
DAYLIGHT SAVINGS TIME STOP MONTH The Day-
light Savings Time Stop Month tells the monitor thermostat
which month to move its internal clock back for the end
of daylight savings time. To set the month, configure
category 9, option 10. Use the left set point buttons to raise
or lower the value. January is 1, February is 2, and so on.
The range of values is 1 to 12. The default is 10.
DAYLIGHT SAVINGS TIME STOP WEEK The Day-
light Savings Time Stop Week tells the monitor thermostat
which week to move its internal clock back for the end of
daylight savings time. To set the week, configure category 9,
option 11. Use the left set point buttons to raise or lower the
value. The first week of the month is 1, the second week of
the month is 2, and so on. The last week of the month (in 4
or 5 week months) is always 5. The range of values is 1 to
5. The default is 5.
DAYLIGHT SAVINGS TIME STOP DAY The Daylight
Savings Time Stop Day tells the monitor thermostat which
day to move its internal clock back for the end of daylight
savings time. To set the day, configure category 9, option 12.
Use the left set point buttons to raise or lower the value. The
first day of the week (Monday) is 1, the second day of the
week (Tuesday) is 2, and so on. The range of values is 1 to
7. The default is 7 (Sunday).
DAYLIGHT SAVINGS TIME MINUTES TO SUBTRACT
The Daylight Savings Time Minutes To Subtract option
tells the monitor thermostat how many minutes to move the
clock back at the end of daylight savings time. To set the
number of minutes, configure category 9, option 13. Use the
left set point buttons to raise or lower the value. The range
of values is 0 to 90 minutes. The default is 60 minutes.
39