Install Instructions
23
Dual Element
Heater Module
Heater Mount Locations
Single Element
Heater Module
C10168
Fig. 35 - Typical Heaters
Table 2 – Heater Location for Horizontal
Return and Discharge*
Heater
kW Volts
Heater Slot Location
CRHEATERXXXX00 Left Right
288A 10.0 240
-
288A
291A 16.5 240 291A
-
288A + 291A 26.5 240 291A 288A
294A 33.5 240
-
294A
288A + 294A 43.5 240 288A{ 294A
291A + 294A 50.0 240 291A 294A
294A + 294A 67.0 240 294A{ 294A
289A 10.0 480
-
289A
292A 16.5 480 292A
-
289A + 292A 26.5 480 292A 289A
295A 33.5 480
-
295A
289A + 295A 43.5 480 289A{ 295A
292A + 295A 50.0 480 292A 295A
295A + 295A 67.0 480 295A{ 295A
290A 10.0 600
-
290A
293A 16.5 600 293A
-
290A + 293A 26.5 600 293A 290A
296A 33.5 600
-
296A
290A + 296A 43.5 600 290A{ 296A
293A + 296A 50.0 600 293A 296A
296A + 296A 67.0 600 296A{ 296A
*
XXXX - 4 digit heater in table. For example, a CRHEATER291A000 is
listed as a 291A.
{Remove Restrictor Plate to install in Left Slot Location. Use foil tape to
cover holes.
Table 3 – Heater Location for Vertical
Return and Discharge*
Heater
kW Volts
Heater Slot Location
CRHEATERXXXX00 Left Right
288A 10.0 240
-
288A
291A 16.5 240 291A
-
288A + 291A 26.5 240 291A 288A
294A 33.5 240
-
294A
288A + 294A 43.5 240 288A{ 294A
291A + 294A 50.0 240 291A 294A
294A + 294A 67.0 240 294A{ 294A
289A 10.0 480
-
289A
292A 16.5 480 292A
-
289A + 292A 26.5 480 292A 289A
295A
(See Note 2, Page
20)
33.5 480
295A {
( H P --- 1
H P --- 2 o n l y )
295A
( A C --- 1 ,
A C --- 2 ,
A C --- 3 o n l y )
289A + 295A 43.5 480 289A{ 295A
292A + 295A 50.0 480 292A 295A
295A + 295A 67.0 480 295A{ 295A
290A 10.0 600
-
290A
293A 16.5 600 293A
-
290A + 293A 26.5 600 293A 290A
296A 33.5 600
-
296A
290A + 296A 43.5 600 290A{ 296A
293A + 296A 50.0 600 293A 296A
296A + 296A 67.0 600 296A{ 296A
*
XXXX - 4 digit heater in table. For example, a CRHEATER291A000 is
listed as a 291A.
{ Remove Restrictor Plate to install in Left Slot Location. Use foil tape to