Portable Generator User Manual

GENERATOR Model ASPBS1CCA016 - Steel, Model ASPBA1CCA016 - Aluminum
Rated Maximum Continuous Power Capacity (LP)................................................................................................ 16,000 Watts*
Rated Maximum Continuous Power Capacity (NG)............................................................................................... 15,000 Watts*
Rated Voltage.............................................................................................................................................................. 120/240
Rated Maximum Continuous Load Current
120 Volts ........................................................................................................................................................ 133.3 LP/125 NG
240 Volts ....................................................................................................................................................... 66.6 LP/62.5 NG
Main Line Circuit Breaker .......................................................................................................................................... 65 Amp
Phase ............................................................................................................................................................................... 1
Number of Rotor Poles .................................................................................................................................................... 2
Rated AC Frequency .................................................................................................................................................... 60Hz
Power Factor .................................................................................................................................................................... 1
Battery Requirement (not included) .................................................................... Group 26, 12 Volt Netgative Ground and 525 Cold-cranking Amperes Minimum
Unit Weight ................................................................................................................................................ 445 lbs. (Steel), 414 lbs. (Alum)
Dimensions (L” x W” x H”).................................................................................................................................... 48 x 24 x 28-1/4
Sound output in dB(A) at 23 ft. with generator operating at full load.............................................................................. 71.5
Sound output in dB(A) at 23 ft. with generator in
Ultra Quiet
exercise mode ................................................................ 59
ENGINE Model ASPBS1CCA016 - Steel, Model ASPBA1CCA016 - Aluminum
Type of Engine........................................................................................................................................................ OHVI V-TWIN
Number of Cylinders......................................................................................................................................................... 2
Rated Horsepower................................................................................................................................................ 30 @ 3,600 rpm
Displacement................................................................................................................................................................ 992cc
Cylinder Block............................................................................................................................................ Aluminum w/Cast Iron Sleeve
Valve Arrangement................................................................................................................................................ Overhead Valve
Ignition System................................................................................................................................................. Solid-state w/Magneto
Governor System........................................................................................................................................................ Electronic
Compression Ratio......................................................................................................................................................... 9.5:1
Starter........................................................................................................................................................................... 12Vdc
Oil Capacity Including Filter................................................................................................................................. Approx. 1.7 Qts.
Standby Operating RPM.............................................................................................................................................. 3,600
Exercise RPM ............................................................................................................................................................. 2400
Fuel Consumption
Natural Gas cu.ft./hr.
........................................1/2 Load 173
........................................Full Load 245
Liquid Propane ft
3
/hr (gal/hr)
........................................1/2 Load 59 (1.59)
........................................Full Load 92 (2.51)
CONTROLS
Mode Switch
-Auto ............................................................................................................................................... Automatic Start on Utility failure
7 day exerciser
-Off ............................................................................................................................................ Stops unit. Power is removed
Control and charger still operate
-Manual/Test (start) ...................................................................................................................... Start with starter control, unit
stays on. If utility fails, transfer
to load takes place.
Engine Start Sequence Cyclic cranking: 7 sec. on, 7 rest
(90 sec. maximum duration)
Engine Warm-up ..................................................................................................................................................... 10 seconds
Engine Cool-Down ..................................................................................................................................................... 1 minute
Starter Lock-out ........................................................................................................................................ Starter cannot re-engage until
5 sec. after engine has stopped.
2.5 Amp Timed Trickle Battery Charger .................................................................................................................. Standard
Automatic Voltage Regulator w/Overvoltage Protection ............................................................................................ Standard
Automatic Low Oil Pressure Shutdown ..................................................................................................................... Standard
Overspeed Shutdown ............................................................................................................................................ Standard, 72Hz
High Temperature Shutdown ..................................................................................................................................... Standard
Overcrank Protection ................................................................................................................................................. Standard
Safety Fuse ............................................................................................................................................................... Standard
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with
BS5514, ISO3046 and DIN6271). * Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum
power decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 12° C (10° F) above 15.5° C (60°F).
Home Standby - 16kW
Required fuel pressure to generator fuel inlet at all load ranges - 5 to 7 inches of water column for natural gas, 10 to 12 inches of water column for LP gas