Portable Generator User Manual

Home Standby - 16kW
TRANSFER SWITCH & EMERGENCY LOAD CENTER Models: ASPBS1CC016 & ASPBA1CC016
No. of Poles ......................................................................................................................................... 2
Current Rating (amps) ....................................................................................................................... 100
Voltage Rating (VAC) ........................................................................................................................ 250
Utility Voltage Monitor (fixed)
-Pick-up ...................................................................................................
70%
-Dropout ...................................................................................................
60%
Return to Utility .................................................................................................... approx. 13 sec.
Exerciser weekly for 12 minutes .................................................................................................... Standard
UL Listed ....................................................................................................................................... Standard
Dimensions (H” x W” x D”) ....................................................................................................... 26.5 x 12.5 x 7
Total of Pre-wired Circuits .................................................................................................................. 16
No. 15A 120V ................................................................................................................ 5
No. 20A 120V ................................................................................................................ 5
No. 20A 240V ................................................................................................................ 1
No. 40A 240V ................................................................................................................ 1
No. 50A 240V ................................................................................................................ 1
Circuit Breaker Protected
Available RMS Symmetrical
Fault Current @ 250 Volts .................................................................................................... 10,000
Mechanical Dimensions (in inches)
Current No. of Height Width Depth
Rating Poles H1 H2 W1 W2
100 UL Listed 2 26.5 29.25 8.14 12.5 7
W1
W2
H1
H2
Terminal Wire Ranges
ATS Rated Amps Switch Terminal Neutral Lug/Stud Ground Lug
100A 2-Pole UL 1 x 1/0-12 1 x 3/8-16 Stud 1 x 2/0-14
Transfer Switch Features
• Electrically operated,
mechanically-held contacts for
fast, positive connections.
• Rated for all classes of load,
100% equipment rated, both
inductive and resistive.
• 2 pole, 250 VAC contactors.
• 160 millisecond transfer time.
• Dual coil design.
• Main contacts are silver plated
or silver alloy to resist welding
and sticking.
• Nema 1 enclosure is standard
on the 100 amp switch.
Conduit sizes
vary depending
on model #