Specifications

3
Fig. 3 — Dimensions, 30HXC116-146
NOTES:
1. Operating weight includes weight of water and refrigerant.
2. Denotes center of gravity.
3. Dimensions are in inches (mm).
4. Recommended service clearance around machine is 36 in. (914.4 mm).
5. Victaulic nozzles are standard on all models. Flow switch factory
installed in cooler outlet victaulic nozzle.
UNIT
OPERATING
WEIGHT - lb (kg)
WGT DISTRIBUTION AT EACH
MTG PLATE - lb (kg)
123456
30HXC116
6415
(2911)
728
(330)
1114
(505)
777
(352)
1053
(478)
1615
(733)
1127
(511)
30HXC126
6465
(2933)
738
(335)
1127
(511)
780
(354)
1061
(481)
1628
(738)
1131
(513)
30HXC136
6688
(3034)
758
(344)
1176
(533)
811
(368)
1083
(491)
1689
(766)
1171
(531)
30HXC146
6718
(3048)
763
(346)
1182
(536)
815
(370)
1085
(492)
1697
(770)
1172
(532)
a30-4648