7
UNIT
OPERATING
WEIGHT - lb (kg)
WGT DISTRIBUTION AT EACH
MTG PLATE - lb (kg)
123456
30HXA116
5163
(2342)
530
(240)
895
(406)
540
(245)
855
(388)
1456
(660)
887
(402)
30HXA126
5205
(2362)
540
(245)
905
(410)
541
(245)
864
(392)
1468
(666)
887
(402)
30HXA136
5309
(2408)
548
(249)
926
(420)
555
(252)
874
(396)
1498
(679)
908
(412)
30HXA146
5333
(2420)
551
(250)
930
(422)
555
(252)
883
(400)
1506
(683)
908
(412)
NOTES:
1. Operating weight includes weight of water and
refrigerant.
2. Denotes center of gravity.
3. Dimensions are in inches (mm).
4. Recommended service clearance around
machine is 36 in. (914.4 mm).
5. Victaulic nozzles are standard on all models. Flow
switch factory installed in cooler outlet victaulic
nozzle.
Fig. 7 — Dimensions, 30HXA116-146